ASHRAE OR-10-045-2010 Impact of Typical Weather Year Selection Approaches on Energy Analysis of Buildings《典型气象年选择方法对建筑物能量分析的影响RP-1477》.pdf
《ASHRAE OR-10-045-2010 Impact of Typical Weather Year Selection Approaches on Energy Analysis of Buildings《典型气象年选择方法对建筑物能量分析的影响RP-1477》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-10-045-2010 Impact of Typical Weather Year Selection Approaches on Energy Analysis of Buildings《典型气象年选择方法对建筑物能量分析的影响RP-1477》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、416 2010 ASHRAEThis paper is based on findings resulting from ASHRAE Research Project RP-1477.ABSTRACTThe paper summarizes the results of a series of analyses toassess the impact of the selection procedure used to generate oftypical year weather on annual building energy use. The build-ing energy an
2、alysis is carried out using detailed whole buildingsimulation tool that utilizes hourly typical year weather files.Annual energy use for prototypical office buildings are obtainedfor 10 sites representing a wide range of climatic conditions inthe U.S. In particular, the analyses presented in this pa
3、per eval-uate the impacts of weighting factors for various weather vari-ables and of the length of historical data used on predicting theenergy use of building systems.The results of the analysis indicated that a maximum of 5%difference in annual office building energy use can result fromthe selecti
4、on procedure used to generate typical weather yearfor the 10 US climates considered in this study.INTRODUCTIONDetailed building energy simulation tools such as DOE-2 (LBL 1981) and EnergyPlus (Crawley et al. 2000) arecommonly used to design sustainable buildings. These toolsrequire hourly typical ye
5、ar weather files in order to estimatebuilding energy use and building indoor comfort. Severalprocedures do exist to develop typical weather data using asingle year of hourly data that are selected to represent therange of weather patterns that can be found in a multi-year dataset (Keeble 1990).Sever
6、al approaches have been utilized to develop andformat a typical weather year for building energy analysisincluding the ASHRAE Test Reference Year or TRY (ASH-RAE 1976), Typical Meteorological Year or TMY (Hall et al.1978), the Weather Year for Energy Calculations (Crow 1981),TMY2 (Marion and Urban 1
7、995), ASHRAE InternationalWeather for Energy Calculations or IWEC (Thevenard andBrunger 2002), and more recently TMY3 (Wilcox and Marion2008). Other selection approaches have been proposed (Hui1996).Limited analyses have been reported to assess the impactof the selection criteria for generating the
8、typical weather yearon predicting the performance of building energy systems(Arigirou et al. 1999 and Massie and Kreider 2001). In partic-ular, Argiriou et al. (1999) tested several different TMYweather files generation procedures for Athens with 20 years(1977 to 1996) measured weather data. They co
9、nsideredseveral configurations of weighting factors and four methodsto generate typical weather year including: the TMY method(Hall et al. 1978), a Danish method (Lund and Eidorff 1980),Festa-Ratto method (Festa and Ratto 1993), and 20-year aver-age meteorological year. They developed weather data e
10、valu-ation system based on building and solar systems.Specifically, they utilized a simple solar water heating system,a building, a photovoltaic system, and a large scale solar heat-ing system with inter-seasonal storage, and PV system.TRNSYS is used in the evaluation analysis (Anon 2000). Amodified
11、 Festa-Ratto method was found to provide the bestdata set for Athens. Massie and Kreider (2001) estimated thediscrepancies between TMY and TMY2s in predicting theperformance of a photovoltaic system and a wind turbine.In this paper, a series of sensitivity analyses is presentedto assess the impact o
12、f the typical weather selection criteria onImpact of Typical Weather Year Selection Approaches on Energy Analysis of BuildingsDonghyun Seo Yu Joe Huang Moncef Krarti, PhD, PEStudent Member ASHRAE Member ASHRAE Member ASHRAEDonghyun Seo is a graduate student and Moncef Krarti, PhD, PE is a Professor
13、and Associate Chair in the Civil, Environmental, and Archi-tectural Engineering Department at the University of Colorado, Boulder, CO. Joe Huang is president of White Box Technologies, Inc., Moraga,CA, and formerly a staff scientist at Lawrence Berkeley National Laboratory, Berkeley, CA.OR-10-045 (R
14、P-1477) 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2010, Vol. 116, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted with
15、out ASHRAEs prior written permission. ASHRAE Transactions 417building energy analysis results. In particular, the impacts onannual energy use predictions of weighting factors associatedwith various weather variables and of the length of historicaldata used in the selection procedure are evaluated th
16、roughoutthe paper. The analysis is carried out for 10 U.S. sites for whichmeasured weather data for at least 30 years are reported. First,a brief description of the prototypical office building used inthe simulation analysis is provided. Then, the results of thesimulation analyses are presented and
17、discussed.BUILDING MODEL DESCRIPTIONFor this analysis, a prototypical office building wasmodeled using a whole-building hourly simulation tool (LBL1981). The prototypical building model consists of 3-storyoffice building with a gross floor area of 48,000 ft2(4461 m2)as illustrated in Figure 1. A pow
18、er density of 0.8 W/ft2(8.7 W/m2) is assumed for lighting systems equipped with electronicballasts and daylight control sensors. Daylight control cover-age area is 54% covering all the perimeter offices. Officeequipment power density is assumed to be 1.0 W/ft2(10.8 W/m2) for computers, laser printer
19、s, photocopiers, and facsimilemachines. The building envelope is assumed to include 40%fenestration-to-wall ratio with glazing varying by climate tomeet ASHRAE Standard 90.1 (ASHRAE 2004). The outsideair ventilation rate is set to be 20 CFM/person (9.5 L/s perperson). The HVAC system for the buildin
20、g consists of a vari-able air volume (VAV) system with hot water reheat coils anddry-bulb outside air economizer. The central plant includes0.55 kW per ton centrifugal chillers and a 90% efficiency gas-fired boiler. Table 1 provides a summary of the basic featuresof the prototypical office building.
21、 Table 2 lists the 10 U.S.sites used to carry out the analysis presented in this paper.Figure 1 Office building model.Table 1. Summary of the Basic Features of the Prototypical Office Building ModelArchitectural MechanicalFloor Area 16,000 sf (1487 m2) Design Temp. 75F/72F Cooling/Heating (24C/22C)G
22、ross Area 48000 sf (4461 m2) Thermo. Set 76F/82F (24.5C/28C) Cooling60F/64F (15.5C/18C) HeatingPeri. Depth 20 ft (6.1 m) 57% of floor area HVAC VAV+ReheatWall Wood, metal frame, R-19 batt. Overall R-10.5 Fans Variable Speed Drives (VSDs)Roof Built-up roof, metal frame, R-18 insulation, Overall R-22O
23、A 20 cfm/person (9.5 L/s per person)Economizer controlWWR 40% (floor to ceiling) Chiller 0.55 kW/tonGlazing Variable with climate Boiler 90%Daylight Control Perimeter zonesShading 3 ft (0.9 m) overhang on S, E, and W 50fc design levelLPD/ EPD 0.8 /1.0 W/sf(8.7/10.8 W/m2)Dimming controlTable 2. Selec
24、ted 10 U.S. SitesUSAF Stations STATE LAT LON ELEV (m) Climate Zone (ASHRAE Std 90.1)725180 ALBANY COUNTY ARPT NY 42.45N 073.48W 89 5A722190 ATLANTA INTL ARPT GA 33.39N 084.25W 315 3A911820 HONOLULU INTL ARPT HI 21.21N 157.56W 5 1A723860 LAS VEGAS/MCCARRAN NV 36.05N 115.10W 664 5B726410 MADISON/DANE
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR100452010IMPACTOFTYPICALWEATHERYEARSELECTIONAPPROACHESONENERGYANALYSISOFBUILDINGS 典型 气象 选择 方法

链接地址:http://www.mydoc123.com/p-455707.html