ASHRAE NA-04-3-1-2004 The Acoustic Properties of Common HVAC Plena《HVAC送气扇的共同的声学特性RP-1026》.pdf
《ASHRAE NA-04-3-1-2004 The Acoustic Properties of Common HVAC Plena《HVAC送气扇的共同的声学特性RP-1026》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE NA-04-3-1-2004 The Acoustic Properties of Common HVAC Plena《HVAC送气扇的共同的声学特性RP-1026》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、NA-04-3-1 (RP-I 026) The Acoustic Properties of Common HVAC Plena Emanuel Mouratidis, P.Eng. Member ASHRAE ABSTRACT The HVAC plenum is commonly applied as a means to reduce problematic low-frequency noise produced by mechan- ical equipment in ducted systems. The predicted acoustical performance has
2、been derived from an earlier investigation Fells 1958). is early work did not focus on lowfrequency performance, the efects of wall linings, or typical geometric variables. Through the ASHRAE-sponsored research project RP-1026, conducted by Vibro-Acoustics, rigorous testing enabled the identlJicatio
3、n of comprehensive attenuation prop- erties for common HVAC plena. A two-stage prediction approach resulted, which applies an improved version of the Wells equation for mid- to high-fequency attenuation (5000 Hz upper frequency limit), quantified as a transmission loss (TL), and a surface area and w
4、all characteristic model for the critical low-fequency TL (50 Hz lower frequency limit). This method has improved the prediction accuracy of flow-through type HVACplena with a volume range of 20-1100 f (0.5-30 m3). In addition, this work has identijed acoustical effects for seven different wall-lini
5、ng systems and typical geometric variables, such as opening ofsets, opening ratio variables, and multiple openings. INTRODUCTION The acoustical plenum is a device used to attenuate sound, usually low frequency, within a ducted HVAC system. It is defined as a type of passive sound attenuator that pri
6、marily achieves its performance through a sudden area change. The resulting expansion effect creates high levels of reflections due to the acoustic impedance transfer, which is the ratio of pressure amplitude to the resulting particle velocity at a plenums entrance and termination. In typical HVAC s
7、ystems, John Becker the broadband attenuation is further enhanced by the applica- tion of absorptive wall lining materials. Plenum acoustic performance is characterized in terms of transmission loss (TL). The most common prediction tool is the equation found in the ASHRAE Handbook-HVAC Appli- cation
8、s (ASHRAE 1999), where Plenum TL is as follows: TL = -1O*log so, *(cose.-) (1) 4Kr2 Sau TL = A, (la) where ml, = s= r= a, = Ka = A, = e= area of outlet section of plenum, ft2 (m2) total inside surface area of plenum less the inlet and outlet areas, It2 (m2) distance between centers of inlet and outl
9、et sections, fi (4 directivity factor 2 (for an inlet opening at the approximate center of a wall) 4 (for an inlet opening adjacent to one wall or at a bi- hedral comer) 8 (for an inlet opening adjacent to two walls or at a tri- hedral comer) average absorption coefficient of plenum lining offset an
10、gle at the exit, relative to the inlet opening attenuation coefficient attenuation according to ASHRAE 1999 equation Emanuel Mouratidis and John Becker are with Vibro-Acoustics, Toronto, Ontario, Canada. 02004 ASHRAE. 597 Equation 1 is a derivation from the work by Wells (1958), which is a variation
11、 of the common room constant equation. It characterizes the total energy density at a point within the chamber as the sum of the direct and reverberant energy densi- ties. Wells work was based on the dynamic scaling of data from small test plena (no plenum dimension greater than 3 ft O.9m) and a 375
12、 Hz lower frequency limit. Inlet area, multi- ple outlet openings, specific location of outlet openings (e.g., side vs. end), and the presence of airflow were not considered as variables affecting the plenums performance characteris- tics. Furthermore, this early work did not identify the low- frequ
13、ency characteristics when in the presence of plane wave propagation. Since the fundamental property of a plane wave is that of constant pressure and displacement amplitude perpendicular to the direction of travel, the resulting three- dimensional interaction with a plenum chamber may be highly depen
14、dent on both the inlet duct and plenum dimensions that support these unique sound waves. In this early work, Wells described an anticipated error of IT10 dB for the frequencies below the range of cross-mode or multi-mode propagation, as determined by the cutoff frequency Xand Y = width and height of
15、 the inlet duct or opening, respectively, ft (m); and CO = speed of sound, Ws (ds). cut-off frequency is determined by For the (1,O) fundamental mode using square duct, the f =Co 2d (4) where d = duct dimension, width or height, ft (m). In this project, the inlet duct sizes selected (as noted above)
16、 corresponded with approximate cut-off frequencies of 570 Hz, 285 Hz, and 140 Hz, respectively. This represents cut- off frequencies for a wide range of inlet duct sizes commonly found in HVAC duct systems. To simpli9 the regression analysis, a power series was selected as the method to correlate th
17、e dimensionless Kfand the corresponding test data (dB) within the dual CfIfc and ffc) frequency regions. Figure 5 displays the distribution of A, versus Kf, which produced very good corresponding coe- ficients of determination (R2 = 0.78), above the critical cut-off region. As shown in Figure 6, the
18、 scatter among the low- frequency A, data versus Kfwas very large. This resulted in a very weak correlation coefficient (R2 = 0.40). As the 1999 ASHRAE Handbook-Applications chapter suggests, there is a significant dependence on cutoff frequency when applying Equation 1. ASHRAE Transactions: Symposi
19、a 599 waon&mw-,y (IWI I s i, m single metal wall 1 acoustical hing ,“, single IyeE_B metal wall 80 1 O0 125 ueL. single metal wall 2 acoustical lining 0.01 0.04 0.05 0.05 0.30 0.60 0.05 0.29 0.01 0.04 0.05 0.05 0.50 0.50 0.05 0.21 0.01 0.04 0.26 0.38 0.50 0.50 0.13 0.05 IyeE4 double metal walls uoy
20、IYeLE double metal walls double metal walls 4 acoustical blanket fill 8 acoustical blanket fill 4 no-media type 4 acoustical blanket fiil IyeLp double metal walls perf facing perf facing micro-perf facing solid facing 2500 3200 4000 5000 Figure 2 Typical wall construction details (section view). 0.0
21、2 0.05 0.94 0.97 1 .o0 1 .o0 0.21 0.05 0.03 0.07 0.92 0.95 0.94 0.96 0.18 0.05 0.03 0.07 0.88 0.91 0.93 0.93 0.13 0.05 0.03 0.07 0.81 0.83 0.86 0.86 0.05 0.05 Table 1. Random Incidence Wall Absorption Coefficients, a Metal Type D Double Wall w/ 4 in. Liner (perf/solid) 0.30 0.45 Type E Double Wall w
22、l8 in. Liner (perfholid) 0.35 0.45 TY Pe F Double Wall wl 4 in. Chamber (no liner) 0.05 0.08 Type G Double Wall wt 4 in. Liner (solid/solid) 0.26 0.48 600 ASHRAE Transactions: Symposia Table 2. Acceptable Error Tolerances, oiso SO 96141 %o I 1 113 Oct. Band Center Freq. I 50-160 I 200-315 I 400-5k I
23、 6.3k- 1Ok 3 2 1.5 2.5 i TYPICAL SOUND INTENSITY PLENUM OUTLET BLOCKAGE CONTROL VOLUME 71 USED TO DETERMINE Lp(bbckiigeZ 30 25 * *ATL k-d Min 10 X duct dia Figure 3 Test setup. Figure 4 ATL and A, for a 4 x 6 x 1 Oft Type-Cplenum. 45 40 e. 35 4 30 1 25 i: 10 5 O 00 O1 O2 03 04 05 OB 07 O8 O9 10 Awen
24、ustion CoatRoient U,) Figure 5 ATL versus Kf ( f, only) for all in-line Figure 6 ATL versus Kf (50f$Volume 1 (dB/f?) (dB/ft2) TypeB TypeC TypeD TYpeE TYPeF TYPeG 0.14 0.03 1 1 O 1 O O Wall Effect, We (dB ADD) 63 80 1 O0 125 160 0.10 0.03 1 2 3 7 1 3 0.11 0.03 2 2 3 9 2 7 0.23 0.03 2 2 4 12 1 6 0.24
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAENA04312004THEACOUSTICPROPERTIESOFCOMMONHVACPLENAHVAC 送气 共同 声学 特性 RP1026PDF

链接地址:http://www.mydoc123.com/p-455492.html