ASHRAE LV-11-C063-2011 Reducing Sidewall Vent Plumes and Increasing Equipment Installation Flexibility in Low Energy Design.pdf
《ASHRAE LV-11-C063-2011 Reducing Sidewall Vent Plumes and Increasing Equipment Installation Flexibility in Low Energy Design.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-C063-2011 Reducing Sidewall Vent Plumes and Increasing Equipment Installation Flexibility in Low Energy Design.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Reducing Sidewall Vent Plumes and Increasing Equipment Installation Flexibility in Low Energy Design Larry Brand Paul Glanville, PE Yanjie Yang Member ASHRAE Associate Member ASHRAE ABSTRACT High-efficiency natural gas-fired space and water heating systems are an integral part of Low Energy Design,
2、offering equipment installation flexibility at minimum operating cost. These systems are largely installed with sidewall vents in new and retrofit single family and multifamily buildings when venting through the roof is not practical, is prohibited by local code, or is beyond the maximum length of t
3、he vent system permitted by the manufacturers installation instructions. The industry continues to investigate sidewall venting systems design and installation practices to improve building design flexibility, improve vent performance under extreme conditions, avoid nuisance outages, and avoid other
4、 occurrences such as ice formation on nearby structures. This paper investigates sidewall vent plume formation and the potential for ice formation on nearby structures in very cold climates. A review of the literature on turbulent buoyant round jet formation and transition from momentum-driven to bu
5、oyancy-driven flow is discussed as well as results of computational fluid dynamics (CFD) modeling of several geometries. CFD is a finite difference model that calculates the fluid parameters based on the physics of the fluid flow and surrounding conditions. Recommendations are made for improving sid
6、ewall vent performance and supporting flexible Low Energy Design practices. INTRODUCTION Condensing furnaces and appliances are commonly installed in a direct vent configuration with vent termination on the side wall of the building. A direct vent configuration provides for combustion air from outdo
7、ors to minimize conditioned space energy loss through infiltration, with the venting of the products of combustion to the outdoors through horizontal or vertical gas tight and corrosion resistant vent pipes. These systems have been installed and operating since the 1980s with good long-term performa
8、nce records when installed according to the manufacturers installation instructions. Ice formation on adjacent structures is a phenomenon that has been identified in very cold climates where sidewall venting is used for two story residential buildings spaced closely together. Frost forms in low-wind
9、 conditions on siding or soffits with the potential to enter attic spaces depending on the placement of attic vents. In cold climates, it is possible for the outdoor temperature to remain below freezing for 30 days in a typical winter season, providing the opportunity for frost formation to become a
10、n ice build-up over time. This paper analyzes ice formation from Category IV condensing furnace sidewall vent geometries using horizontal turbulent buoyant round jet solutions from the literature, laboratory testing, and Computational Fluid Dynamics (CFD) models to investigate: 1. Mechanisms leading
11、 to ice formation on adjacent structures in very cold climates, LV-11-C063 2011 ASHRAE 5092011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, dist
12、ribution, or transmission in either print or digital form is not permitted without ASHRAES prior written permission.2. Techniques to minimize ice formation through changing vent sizes, lengths, and terminations, 3. Other research that is needed. FURNACE MANUFACTURERS INSTALLATION INSTRUCTIONS Catego
13、ry IV furnace manufacturers provide information in their installation instructions regarding the maximum length of the vent system as a function of pipe diameter and furnace capacity. Additional information is provided on the design of the vent terminals, clearance to windows and doors, and distance
14、 above the ground. Table 1 shows the pipe length for various plastic materials (PVC, CPVC, and ABS) as a function of pipe diameter in the installation instructions for a typical furnace. This information sets the upper limit for the vent system design to provide adequate venting. For each input capa
15、city, modified for altitude, the maximum pipe diameter and maximum length with elbows is specified. Figure 1 shows the recommendations for clearances to nearby windows, doors, and other construction features for combustion air and vent terminations. Manufacturers permit a “snorkel” arrangement where
16、 the combustion air and vent pipes penetrate the building envelope, turn vertical, and then terminate at a height above ground limited by the length of exposed pipe permitted for the climate. Table 1 Typical Vent Sizing Maximum Pipe Length from Manufacturers Installation Instructions (Abbreviated) A
17、ltitude, ft. (m) Capacity KBtu/hr (kW) Termination Type Pipe Diameter, inches (cm) Maximum Pipe Length for Given No. of 90 Elbows, ft. (m) 1 2 3 0 to 2000 (0 to 610) 40 (12) 2 pipe or concentric 1 (3.8) 50 (15.2) 45 (13.7) 40 (12.2) 2 (5.1) 70 (21.3) 70 (21.3) 70 (21.3) 0 to 2000 (0 to 610) 60 (18)
18、2 pipe or concentric 1 (3.8) 50 (15.2) 45 (13.7) 40 (12.2) 2 (5.1) 70 (21.3) 70 (21.3) 70 (21.3) 0 to 2000 (0 to 610) 80 (23) 2 pipe or concentric 1 (3.8) 30 (9.1) 25 (7.6) 20 (6.1) 2 (5.1) 70 (21.3) 70 (21.3) 70 (21.3) 0 to 2000 (0 to 610) 100 (29) 2 pipe or concentric 2 (5.1) 45 (13.7) 40 (12.2) 3
19、5 (10.7) 2 (6.4) 70 (21.3) 70 (21.3) 70 (21.3) Figure 1 Typical Combustion Air and Vent Termination Diagram from Manufacturers Installation Instructions (Abbreviated) Source: Carrier 58MCB Installation, Start-Up and Operating Instructions for Sizes 040-140, Series 100 510 ASHRAE TransactionsThe curr
20、ent requirement for sidewall vent terminal height is 1 ft (0.3 m) above the ground or highest anticipated snow level. In this analysis 1 ft (0.3 m) is used as a minimum height to evaluate the worst case condition and 7 ft (2.1 m) is used as the maximum height for insulated exterior vent pipe using 7
21、0 inches (1.8 m) exposed length penetrating the wall at 1 ft. (0.3m) above grade. HORIZONTAL TURBULENT BUOYANT ROUND JETS The physics of horizontal turbulent buoyant round jets has been investigated thoroughly in the power industry. Atmospheric plume dispersion modeling and jet-to-plume transitions
22、are the two primary areas of interest. The governing equations include conservation of mass and momentum and the boundary conditions. Fan (1969) investigated buoyant plumes for effluent dispersal in uniform fluids, and Xiao (2008) investigated primarily vapor-phase buoyant round jets for steam plume
23、 dispersion. Xiao provides a solution for jets with small and large density variations transforming to buoyancy-driven vertical plumes using a numerical method to solve the differential equations. Figure 2, below, shows Xiaos solution for small density variation such as flue gas into air as function
24、 of Froude number, a measure of the relationships between velocity effects and buoyancy effects. The figure shows the general relationship between the Froude number and the vapor plume trajectory with wider variations at lower Froude numbers. Figure 2 Normalized trajectories of horizontal buoyant je
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV11C0632011REDUCINGSIDEWALLVENTPLUMESANDINCREASINGEQUIPMENTINSTALLATIONFLEXIBILITYINLOWENERGYDESIGNPDF

链接地址:http://www.mydoc123.com/p-455466.html