1、4772 Implications of Coil Frosting on System Designs for Low-Temperature Applications Donald J. Cleland, PhD Member ASHRAE ABSTRACT Air relative humidity (RH) in a refrigerated facility is determined by the balance between moisture entry (principally through doors) and moisture removal (principally
2、as frost on the air-cooling coil). It has been shown that coil frosting is “unfavorable,” leading to very rapid decline in performance, ifthe air becomes super-saturated as it is cooled. The condi- tions for the transition to unfavorable frost formation can be predicted from coil design in formation
3、 including air-on temperature and RH, evaporation temperature, and heat load sensible heat ratio (SHR). Using advanced models for air injil- tration through doors plus standard models for other heat loads, and assuming that air cooling follows a straight line approach from the air-on condition to th
4、e saturation at the coil surface temperature, the load SHR, coil SHR, and, hence, the balancedairRHwereestimatedfora typical refrigeratedfacil- ity with a warehouse, environmental loading area (ELA), and blast freezer. It was shown that unfavorable frost formation is likely to occur in low-temperatu
5、re facilities even if ambient conditions are not that extreme and moisture entry is reduced by doorway protection. Unfavorable frosting can be best avoided by a combination of improved coil design (e.g., smaller air to refrigerant temperature diflerence, TO) and enhanced door protection (especially
6、doors opening to the ambient), but occasionally active dehumidification or special coil design (e.g., staggeredjin spacing) must be used to avoid frosting problems. INTRODUCTION Infiltration of air and, hence, moisture into refrigerated warehouses is costly to the operation of the facility. If the f
7、acil- ity operated near or below 0C (32”F), the moisture deposits on the evaporator coil surfaces as frost, decreasing the refiig- eration system efficiency. In particular, the frost both reduces the airflow through the coil and insulates the coil heat transfer surface. Periodically, the coils must
8、be defrosted to remove the accumulated frost, incurring further energy costs and causing increased risk of temperature fluctuations. In addition, the moisture can deposit as icelcondensation on floors, doors, walls, ceilings, and product (especially near to doors), creating hazards to workers, impai
9、ring productivity, causing problems with product acceptability, and requiring regular removal. To reduce the frequency of the fiostingldefrost cycle and the magnitude of the undesirable effects, a number of actions are often taken: Loading dock external truck-trailer doors are protected to reduce th
10、e infiltration of ambient air (e.g., bump or inflat- able cushions, flap curtains). Loading docks are conditioned to reduce the infiltration of moisture into the warehouse (reheat andor dehumidifica- tion coils or dessicant dehumidification). Doors between the loading dock and the warehouse are prot
11、ected (e.g., strip curtains, rapid-action doors, air curtains, door vestibules, etc.). Heat sources are used to prevent frost formation on surfaces other than the evaporator coils. For evaporator coils adjacent to areas with high air infil- tration (e.g., in vestibules), there is anecdotal evidence
12、that the coil performance deteriorates extremely rapidly, requiring seemingly continuous defrost. Smith (1989, 1992) proposed the concept of unfavorable” frost formation to describe such situations and postulated that it occurred when the line repre- senting the temperature and humidity of the air p
13、assing through the coil (the air approach line) crosses the saturation Donald J. Cleland is a professor in the Institute of Technology and Engineering, Massey University, Palmerston North, New Zealand. 336 02005 ASHRAE. I I I I I I I l Ts Temperature Ton Figure 1 Psychrometric chart showing the conc
14、ept of favorable and unfavorable frost formation and the demarcation between frost types. line of the psychrometric chart (i.e., becomes supersaturated) as shown in Figure 1. Further, the mechanism of unfavorable frost formation was postulated to be the formation of airborne water droplets or ice-cr
15、ystals, which physically deposit on any surface they encounter, in addition to the normal frost forma- tion by difision of water from high partial pressure conditions in the airstream to low partial pressure conditions at the coil (or frost) surface. Unfavorable frost is snowlike (and of low density
16、) and as a result may be more insulating, have higher impact on airflow rate reduction through the coil, and be more difficult to defrost than frost formed under less extreme condi- tions (Le., subsaturated air cooling path), which by compari- son is “favorable“ (although still undesirable). Sherif
17、et al. (2001) endorsed the theory in experiments with a typical low-temperature coil operating with an air-on temperature of -8.3“C (17“F), refrigerant evaporation temper- ature of -40C (-40“F), and variable heat load sensible heat ratios (SHR) and air-on relative humidities (RH,). However, the air-
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE47722005IMPLICATIONSOFCOILFROSTINGONSYSTEMDESIGNSFORLOWTEMPERATUREAPPLICATIONS 低温 申请 系统 设计所 线圈

链接地址:http://www.mydoc123.com/p-454355.html