1、 INCH - POUND MIL-PRF-32111 8 October 2002 PERFORMANCE SPECIFICATION SPACE HEATER LARGE - RADIANT, NON-POWERED, LIQUID distribution is unlimited. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32111 22.2 Government Documents. Specifications,
2、 standards, and handbooks. The following specifications, standards, and handbooks form a part of this specification to the extent specified herein. Unless otherwise specified, the issues of the documents are those listed in the issue of the Department of Defense Index of Specifications and Standards
3、 (DoDISS) cited in the solicitation. Unless otherwise specified, the issues of documents not listed in the DoDISS are the issues of the documents cited in the solicitation (see 6.2). STANDARDS DEPARTMENT OF DEFENSE MIL-STD-810 - Environmental Test Methods and Engineering Guidelines. MIL-PRF-32023 -
4、Adapter Kit - Gravity Feed, for 5-Gallon Military Fuel Can. (Unless otherwise indicated, copies of the above standard are available from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094). 3. REQUIREMENTS 3.1 First Article. When specified (see 6.2)
5、, a sample shall be subjected to a first article inspection in accordance with 4.1. 3.2 Conformance. When specified (see 6.2), a sample shall be subjected to conformance inspection in accordance with 4.1. 3.3 Operating Requirements. Each heater shall satisfy the following user-oriented requirements:
6、 3.3.1 Operation. The heaters shall operate safely with all specified fuels, listed in Table I, and under all specified conditions herein with no electrical power. 3.3.2 Burner. There shall be no exposure of flame during any mode of operation. There shall be no pool of raw liquid fuel in the burner
7、area during operation or in the case of accidental flame loss. 3.3.3 Ignition. The heaters shall not require any electrical power for ignition. Ignition shall be accomplished safely in ten minutes or less with the use of a match. 3.3.4 Monitoring. The heaters shall incorporate a sight glass or other
8、 means for viewing the entire combustion flame during operation. The heaters shall incorporate a captive cover, which can be removed and replaced over the viewing area for black out conditions with out the use of tools. Provided by IHSNot for ResaleNo reproduction or networking permitted without lic
9、ense from IHS-,-,-MIL-PRF-32111 33.3.5 Liquid Fuel . The heater shall be safely operated with all of the fuels listed in Table I. TABLE I. Compatible Fuels Ambient Temperature Range Military Symbol CONUS National Stock Number (NSN) Above +25FDF-2 9140-00-286-5294 Above +10F DF-1 9140-00-286-5286 Abo
10、ve -60F JP-8 9130-01-031-5816 Above -60F DFA 9140-00-286-5283 3.3.6 Fuel Control. The heaters shall have a fuel control that maintains a constant flow rate to the burner from a gravity feed fuel supply. The fuel control shall have a metering knob to control flow rate incrementally and shall have a m
11、inimum of seven settings. The fuel control shall have a fuel type selector knob (3 positions maximum), if necessary, which allows the operator to accommodate for varying ambient temperatures and for the different fuels listed in Table I. The fuel control shall be adjustable during operation while we
12、aring cold weather gloves NSN 8415-00-227-1220. The fuel control shall provide sufficient fuel flow to achieve the full range of required heat outputs corresponding to Table II. The fuel control shall be permanently labeled to identify settings and corresponding fuel types. The fuel control shall co
13、ntrol fuel flow to the burner to eliminate any possibility of an unsafe over fire condition when operated at the proper settings for the prevailing ambient temperatures and fuel types. The fuel control shall control the firing rate in conjunction with the heaters, such that, smoke levels do not exce
14、ed a #4 on the Bacharach smoke scale, for over 40% of the full range of settings. The fuel control shall have a heat shield if necessary to prevent excessive warming of the valve (above 110F for JP8 with and ambient of 40F) and consequent changes in the flow rate to the heater. 3.3.7 Automatic Fuel
15、Shut Off Capability. Fuel flow shall stop entering the combustion area during accidental flame loss. Fuel flow shall also not enter the combustion area if a full inverted fuel can is connected to the heater with the fuel control in the on position. At no time shall there be a puddle of raw fuel insi
16、de the burner area. 3.3.8 On/Off Switch. A single on/off switch shall be located on the fuel control and shall start and stop fuel flow to the burner. 3.3.9 Fuel Filter. The filter shall eliminate foreign particles from obstructing fuel flow. The filter shall be located within a protected area on th
17、e fuel control and shall be located to allow for 15-minute removal, cleaning and installation of filter element using only common hand tools. The filter shall not require the use of a sealer to obtain a leak free fit. The filter Provided by IHSNot for ResaleNo reproduction or networking permitted wi
18、thout license from IHS-,-,-MIL-PRF-32111 4housing shall be of a design that shall not break due to freezing of entrapped water. The filter element shall not rust. 3.3.10 Solid Fuel Operation. 3.3.10.1 Type II Heater. Type II heater shall contain all components and accessories required for combustion
19、 of solid fuel (wood or coal). All required components shall be packable inside the heater body. Firing rate shall be controllable through manual regulation of combustion air. The solid fuel burning area shall allow for placement of at least .35 cubic feet of solid fuel with an opening large enough
20、to accumulate a 16 long by 4 diameter pieces of wood. The Type II heater shall be capable of conversion to liquid fuel operation with the addition of a liquid fuel burner kit. 3.3.10.2 Type I Heater. Type I heater shall be capable of conversion to solid fuel operation with the addition of a solid fu
21、el burning kit. The requirement for a solid fuel burning kit will be called out in acquisition documents (see 6.2) 3.3.11 Combustion Efficiency. Type I heater shall have a combustion efficiency greater than 50% when operated at 60,000 BTU/hr or higher, with liquid fuels. 3.3.12 Smoke Readings. The s
22、moke reading of the heaters shall not be greater than a # 4 on the Bacharach smoke scale when operated between the ranges listed in Table II. 3.3.13 Heat Output. The heaters shall provide the minimum BTU ranges listed in Table II 5 KBTU. TABLE II Heat Output Requirements Ambient Temp (F) Fuel Type I
23、 (Low) (BTU/Hr) Type I (High) (BTU/hr) 40 DF2/JP8 30,000 60,000 -25 JP8 40,000 80,000 -60 JP8 40,000 80,000 3.3.14 Exhaust Pipe. The exhaust pipe shall be nestable for storage inside the heater body. Each section shall be permanently numbered sequentially corresponding to order of assembly. The diam
24、eter of the exhaust pipe shall be sized to fit through the 5 inch diameter stove pipe openings of the Military tents. The exhaust pipe shall be between 150 inches and 170 inches when assembled on the heater. The exhaust pipe seams shall be permanent and shall not require operator assembly. All heate
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF321112002SPACEHEATERLARGERADIANTNONPOWEREDLIQUIDSOLIDFUEL 空间 加热器 液体 固体燃料 驱动 辐射 大型 PDF

链接地址:http://www.mydoc123.com/p-447112.html