1、 TECHNICAL REPORT ANSI/ISA-TR12.13.03-2009 ANSI Technical Report prepared by ISA Guide for Combustible Gas Detection as a Method of Protection Approved 14 December 2009 ANSI/ISA-TR12.13.03-2009, Guide for Combustible Gas Detection as a Method of Protection ISBN: 978-1-936007-32-5 Copyright 2009 by t
2、he International Society of Automation. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means (electronic mechanical, photocopying, recording, or otherwise)
3、, without the prior written permission of the Publisher. ISA 67 Alexander Drive P.O. Box 12277 Research Triangle Park, North Carolina 27709 - 3 - ANSI/ISA-TR12.13.03-2009 Preface This preface, as well as all footnotes and annexes, is included for information purposes and is not part of ANSI/ISA-TR12
4、.13.03. This document has been prepared as part of the service of the International Society of Automation (ISA) toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subject to periodic review. Toward this end, the Society
5、welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (919) 549-8288; E-mail: standardsisa.org. The ISA Standards and Practices De
6、partment is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards of incorporating suit
7、able references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommended practices, and technical reports to the greatest ex
8、tent possible. Standard for Use of the International System of Units (SI): The Modern Metric System, published by the American Society for Testing ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709. The primary reason for development of this technical report is to support the
9、 existing allowance for combustible gas detectors as a method of protection as permitted within ANSI/NFPA 70, National Electrical Code (NEC), Articles 500 and 505. This document also provides guidance on the use of combustible gas detectors as a method of area classification designation, gas free wo
10、rk permit (hot work permit) application and supplemental protection. Abstract This document provides guidance on the use of combustible gas detection as a method of protection as permitted by ANSI/NFPA 70 (NEC), the use of combustible gas detection for reduction of area designation by API 500 and AP
11、I 505, and to support the Hot Work Permit discussed in OSHA regulations 29 CFR 1910.119(k). Keywords Apparatus, combustible gas detection, fixed apparatus, combustible gas, combustible vapor, gas concentration, gas free work permit, hot work permit, portable apparatus, transportable apparatus This p
12、age intentionally left blank. - 11 - ANSI/ISA-TR12.13.03-2009 Introduction Combustible gas detection apparatus and systems should be used whenever there is the possibility of a hazard to life or property caused by the accumulation of a combustible gaseous atmosphere. Such apparatus can provide a mea
13、ns of reducing the hazard by detecting the presence of the combustible gas and issuing suitable audible or visual warnings and/or to initiate specific actions such as increased ventilation rates, plant shutdown, evacuation, and operation of fire suppression procedures. Combustible gas detection appa
14、ratus and systems may be used to monitor a gas atmosphere to initiate maintenance or operation action when low levels of combustible gas are detected. Additionally, combustible gas detection apparatus can be used to confirm that the area is suitable for engagement of work activities or to permit ene
15、rgizing electrical equipment in hazardous (classified) locations. Performance requirements for combustible gas detecting apparatus are set out in ANSI/ISA-12.13.01 (IEC 61779-1 to -5 Mod) and ANSI/FM 6325/ISA-12.13.04. This page intentionally left blank. - 13 - ANSI/ISA-TR12.13.03-2009 1 Scope Combu
16、stible gas detection used for process safety management may also be used to provide protection from explosion or fires by minimizing the possibility of an accumulation of combustible gases reaching ignitable levels. Criteria are developed to establish combustible gas levels to initiate alarms, initi
17、ate increase in ventilation rates and to initiate shutdown of processes to shutoff the flow of combustible gas that has breached containment. It is the intent of this document to compile and refine techniques for the use of combustible gas sensors and controllers to monitor and control sources of co
18、mbustible gas release into the atmosphere within designated spaces. It is also the intent that these products and techniques be adapted by industries and used with processes that have historically not employed combustible gas detection as a method of protection. 1.1 This document provides guidance o
19、n the use of a combustible gas detection system as a method of protection in Class I hazardous (classified) locations as defined within the following specific documents: ANSI/NFPA 70 (NEC) where for specific applications, electrical equipment that would not otherwise be permitted in the hazardous (c
20、lassified) location may be used in conjunction with combustible gas detection equipment; API RP 500 and API RP 505 for the use of combustible gas detection equipment to augment ventilation to ensure adequate dilution of combustible gas to prevent the possibility of ignition; Title 29 Code of Federal
21、 Regulations 1910.119(k) OSHA regulations to support the hot work permit. NOTE 1 Applicable combustible gas detection equipment performance standards include ANSI/ISA-12.13.01 and ANSI/FM 6325/ISA-12.13.04. For the purpose of this document combustible gases include combustible and flammable gases an
22、d vapors. Documents other than API RP 500 and RP 505 that describe area classification techniques, but which have not included combustible gas detection as part of the process to reduce the probability of ignition are ANSI/NFPA 497 and ANSI/ISA-TR12.24.01 (IEC 60079-10 Mod). Application of combustib
23、le gas detection and control as described in this document can provide additional protection from fire and explosion over typical area classification protection techniques by risk reduction methods. Industries that use these and other area classification documents can benefit by application of the t
24、echniques and criteria presented in this document. NOTE 2 Where mandatory text is provided in this Technical Report, the basis of the mandatory text is derived directly from referenced standards. 1.2 This document provides guidance on the use of portable combustible gas detection apparatus to allow
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIISATR1213032009GUIDEFORCOMBUSTIBLEGASDETECTIONASAMETHODOFPROTECTIONPDF

链接地址:http://www.mydoc123.com/p-437016.html