ANSI American Society of Sanitary Engineering 1081-2014 Performance Requirements for Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmosphe.pdf
《ANSI American Society of Sanitary Engineering 1081-2014 Performance Requirements for Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmosphe.pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1081-2014 Performance Requirements for Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmosphe.pdf(28页珍藏版)》请在麦多课文档分享上搜索。
1、Performance Requirements for Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmospheric Vent Style for Domestic and Light Commercial Water Distribution SystemsASSE InternationalASSE Standard #1081-2014ASSE Board Approved: December 2014ANSI Approved: January 20
2、15An American National StandardBackflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate iAtmospheric Vent Style for Domestic and Light Commercial Water Distribution Systems ASSE Standard #1081-2014ASSE InternationalMokena, IllinoisCopyright 2014All rights reserved.Neith
3、er this standard, nor any portion thereof, may be reproduced without the written consent of ASSE International.No product may be said to be listed by ASSE unless the manufacturer has applied to ASSE International, has had its product tested according to the applicable standards and, when the product
4、 has passed the test, displays the ASSE Seal on the product.Instructions for receiving the authorization to display the seal are available from the ASSE International office. Organizations wishing to adopt or list any ASSE standard should print the ASSE standard number on the cover page first and in
5、 equal or larger type to that of the adopting or listing organization.General Informationii Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmospheric Vent Style for Domestic and Light Commercial Water Distribution Systems ASSE Standard #1081-2014This foreword
6、 shall not be considered a part of the standard. However, it is offered to provide background information.ASSE standards are developed in the interest of consumer safety. The ASSE International Product Standards Committee encourages manufacturers to participate in the development of performance requ
7、irement standards and testing procedures for their products. These standards have the consensus of manufacturers and others who have pertinent interests in plumbing systems and are acceptable to this organization.This standard was developed to provide performance standards and testing procedures for
8、 a pressure reducing boiler feed valve that offers protection of potable water within a premises by means of an integral backflow preventer with intermediate atmospheric vent. Serious contamination of the potable water supply within a premises can be hazardous to the health of occupants therein unle
9、ss every potentially offending outlet is protected. Within every occupancy there are piped systems fed by potable water inlets that could potentially cause backflow and be sources of contamination. The devices covered by this standard are designed to reduce and maintain a preset pressure at the boil
10、er inlet and give protection against low hazard backflow resulting from backpressure and/or back-siphonage at the potable water inlet or boiler feed location. They are not designed, nor intended, for building-isolation or high hazard conditions, which could find full protection only by the reduced p
11、ressure backflow preventer. These devices are fill valves intended for maintaining a minimum pressure in closed systems. Due to the fact that the devices are fill valves, and that the proximity of the two sets of valve internals affect pressure drops across the device, consideration is not given to
12、maintaining strict requirements for minimum flow capacity. The devices are used for maintaining a set pressure and for backflow prevention by way of intermittent flow only. They are not free flowing pressure reducers; therefore, flow capacity is of little significance other than for purposes of comp
13、arison. Measurement and published flow capacity will not be addressed as a functional requirement and, if published, will be the responsibility of the manufacturer. It is assumed that the potable water feeding the boiler line through the device will be at a temperature consistent with the requiremen
14、ts of local codes and will not reach the upper limits of the device (Section 1.2.4). The exhaust of the device will experience an elevated temperature due to the heat from the circulating water in the boiler system. The device will cool once flow begins in order to maintain the set pressure. The tem
15、perature performance requirements of Section 3.14 are written with this use case in mind.Testing procedures and test equipment diagrams have been added to this standard to enable uniform testing by certified testing agencies with adequate facilities and qualified personnel. The testing methods and e
16、quipment required are intended to reflect the requirements and intent of the standards listed below. The intent of this standard is to clarify the interdependent performance characteristics of two separate devices, now in close proximity in one housing. If the devices were not in close proximity, th
17、ey would be independently governed by: ASSE 1003-2009, Performance Requirements for Water Pressure Reducing Valves for Domestic Water Distribution Systems ASSE 1012-2009, Performance Requirements for Backflow Preventers with an Intermediate Atmospheric VentForewordBackflow Preventers with Integral P
18、ressure Reducing Boiler Feed Valve and Intermediate iiiAtmospheric Vent Style for Domestic and Light Commercial Water Distribution Systems ASSE Standard #1081-2014ASSE 1081-2014, Performance Requirements for Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmos
19、pheric Vent Style for Domestic and Light Commercial Water Distribution Systems, must be reviewed periodically and upgraded as research, field conditions and experience suggest. The policy of ASSE International is to review each standard on a five-year cycle for revisions or reaffirmation. Although m
20、any of the material specifications are detailed within Section IV of this standard, it is the responsibility of the manufacturer to comply with the requirements of the Safe Drinking Water Act, United States Public Law 93-523, if and when the product is intended to be installed in potable water servi
21、ce lines. The intent of the standard, however, is to provide performance standards for boiler feed and not intended for potable water service.The ASSE 1081 working group, which developed this standard, was set up within the framework of the ASSE International Product Standards Committee.Recognition
22、is made of the time volunteered by members of this working group and of the support of manufacturers, who also participated in meetings for this standard.This standard does not imply ASSE Internationals endorsement of a product that conforms to these requirements. Compliance with this standard does
23、not imply acceptance by any code body.It is recommended that these devices be installed, consistent with local codes, by qualified and trained professionals.This standard was promulgated in accordance with procedures developed by the American National Standards Institute (ANSI).This edition of the s
24、tandard was approved by the ASSE International Board of Directors on Dec. 19, 2014 as an ASSE standard.iv Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate Atmospheric Vent Style for Domestic and Light Commercial Water Distribution Systems ASSE Standard #1081-201
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10812014PERFORMANCEREQUIREMENTSFORBACKFLOWPREVENTERSWITHINTEGRALPRESSUREREDUCINGBOILERFEEDVALVEANDINTERMEDIATEATMOSPHEPDF

链接地址:http://www.mydoc123.com/p-430876.html