ANSI AMCA 540-2013 Test Method for Louvers Impacted by Wind Borne Debris《风载碎片冲击的屋顶窗试验方法》.pdf
《ANSI AMCA 540-2013 Test Method for Louvers Impacted by Wind Borne Debris《风载碎片冲击的屋顶窗试验方法》.pdf》由会员分享,可在线阅读,更多相关《ANSI AMCA 540-2013 Test Method for Louvers Impacted by Wind Borne Debris《风载碎片冲击的屋顶窗试验方法》.pdf(23页珍藏版)》请在麦多课文档分享上搜索。
1、The International Authority on Air System ComponentsAIR MOVEMENT AND CONTROLASSOCIATION INTERNATIONAL, INC.ANSI/AMCAStandard 540-13Test Method for LouversImpacted by Wind Borne DebrisAn American National StandardApproved by ANSI on June 14, 2013ANSI/AMCA Standard 540-13Test Method for LouversImpacte
2、d by Wind Borne DebrisAir Movement and Control Association International30 W. University DriveArlington Heights, Illinois60004AMCA Standard 540-13 was approved by the membership of the Air Movement and Control Association International, Inc. on May 15, 2013. It was approved by ANSI as an American Na
3、tional Standard on June 14, 2013. 2013 by Air Movement and Control Association International, Inc.All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and 108 of the United States Copyright Act without the permission of the copyright owner i
4、s unlawful. Requests for permission or further information should be addressed to the Executive Director, Air Movement and Control Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.Air Movement and Control Association International, Inc. will conside
5、r and decide all written complaints regarding its standards, certification programs, or interpretations thereof. For information on procedures for submitting and handling complaints, write to:Air Movement and Control Association International30 West University DriveArlington Heights, IL 60004-1893 U
6、.S.A.European Air Movement and Control AssociationNutkin CottageBarracks Road, AssingtonSuffolk CO10 5LPUKAsia AMCA27 Senoko Way (Level 2)Singapore 758060AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of avail-able information and accepted ind
7、ustry practices. However, AMCA does not guarantee, certify or assure the safety or performance of any products, components or systems tested, designed, installed or operat-ed in accordance with AMCA standards or that any tests conducted under its standards will be non-hazard-ous or free from risk.AM
8、CA PublicationsAuthorityCopyrightObjectionsDisclaimerDan Rau Ruskin CompanyCommittee ChairMike Astourian Metal IndustriesBill Bailey Nailor Industries Inc.Jacob Carr Architectural LouversRandal Geedey The Airolite Company, LLCKenneth Moyer Arrow UnitedMike Steele Greenheck Fan CorporationMike Traver
9、 Arrow UnitedBill Vincent Construction Specialties, Inc.Review CommitteeRelated AMCA DocumentsANSI/AMCA Standard 500-L Laboratory Methods of Testing Louvers for RatingAMCA Publication 501 Application Manual for LouversAMCA Publication 511 Certified Ratings Program - Product Rating Manual for Air Con
10、trol DevicesAMCA Publication 512 AMCA Listing Label ProgramANSI/AMCA Standard 550 Test Method for High Velocity Wind Driven Rain Resistant LouversRelatedPublications1. Purpose .12. Scope.13. Definitions.14. Test Specimens.14.1 Number of specimens .14.2 Size of specimens 15. Test Methods.25.1 Specime
11、ns 25.2 Missile .25.3 Locations of impact .36. Missiles .47. Pass/Fail Criteria48. Optional Cycling for High-Velocity Hurricane Zones 49. Product Qualification 410. Limitations.511. Report 5Annex A Test Specimen Reference Figures .10Annex B Follow-up Service (Informative) .14Annex C Bibliography .15
12、ContentsANSI/AMCA 540-13 | 1Test Method for Louvers Impacted by Wind Borne Debris1. PurposeThe purpose of this standard is to establish uniform meth-ods for laboratory testing of louvers that are impact tested with the large missile described in ASTM E 1996-04 1 and E 1886-05 2.2. ScopeThe scope of
13、this standard is for impact testing of louvers used on the outside of buildings as required by the ICC International Building Code 3 and the ICC International Residential Code 4.The following precautionary statement pertains only to the test method portion, Section 5, of this specification: This sta
14、ndard does not purport to address all of the safety con-cerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of the regu-latory limitations prior to use.3. Definitions3.1 Enh
15、anced protection (Essential Facilities) Buildings and other structures designated as essential facil-ities, including, but not limited to, hospitals; other health care facilities having emergency treatment facilities; jails and detention facilities; fire, rescue and police stations, and emergency ve
16、hicle garages; designated emergency shel-ters; communication centers and other facilities required for emergency response; power generating stations; other public utility facilities required in an emergency; and build-ings and other structures having critical national defense functions.3.2 Basic pro
17、tection Any building or structure that is not an Essential Facility as described in Section 3.1.3.3 Horizontal/vertical-bladed louverLouvers shall be designated horizontal or vertical-bladed based on the orientation of the blades on the front or exteri-or side of the louver.3.4 SpecimenA louver asse
18、mbly for testing consisting of one or more lou-ver sections.3.5 Louver SectionA single louver panel. Panels can (but are not required to) be connected to each other to make up larger assemblies for testing purposes. For example, a 2-section wide louver assembly is two panels wide.4. Test Specimens4.
19、1 Number of specimens4.1.1Per ASTM E 1996-04 and ASTM E 1886-05, a minimum of three sections shall be impacted. This requirement may be satisfied by testing one single-section and one multi-section unit or by testing three identical single-section units.4.1.2 One additional specimen may be submitted
20、 for testing should any original submitted specimen described in Section 4.1 fail any portion of the AMCA Standard 540 testing. This is described in Section 9.2. If all specimens pass the AMCA Standard 540, and then some or all of the same specimens are then subjected to Cyclic testing as described
21、in Section 8, and any one specimen fails any portion of the subsequent test(s), then one additional specimen may be submitted to re-test to the subsequent tests as long as the additional specimen first passes the AMCA Standard 540 tests.4.2 Size of specimensThe test specimen selected is intended to
22、evaluate the criti-cal failure area of the louver and provide guidance for blade support requirements. The critical failure area for louvers is the connection between the louver blade end and the perim-eter louver frame. Failures in this area result in loose mate-rial that can result in projectiles
23、in high wind events. The most stringent test specimen for this connection is a section where the blade has no additional support between these end connections. Energy from the impact is transferred to the connection with little absorption by blade flexure. This test specimen also provides guidance r
24、egarding the maxi-mum unsupported blade length that will not allow the projec-tile to pass through the louver blades. Louvers manufactured with blade spans greater than that of the test specimen shall have blade supports at a spacing that matches the tested specimen blade length. These supports are
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMCA5402013TESTMETHODFORLOUVERSIMPACTEDBYWINDBORNEDEBRIS 碎片 冲击 屋顶 试验 方法 PDF

链接地址:http://www.mydoc123.com/p-430748.html