ANSI AHRI 770 I-P-2014 Performance Rating of Refrigerant Pressure Regulating Valves.pdf
《ANSI AHRI 770 I-P-2014 Performance Rating of Refrigerant Pressure Regulating Valves.pdf》由会员分享,可在线阅读,更多相关《ANSI AHRI 770 I-P-2014 Performance Rating of Refrigerant Pressure Regulating Valves.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、 2014 Standard for Performance Rating of Refrigerant Pressure Regulating Valves Approved by ANSI on May 19, 2015 ANSI/AHRI Standard 770 (I-P) Price $10.00 (M) $20.00 (NM) Copyright 2014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and T
2、rademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be de
3、signed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted indus
4、try practices. AHRI does not certify or guarantee that any tests conducted under the standards/guidelines will not be non-hazardous or free from risk. Note: This standard supersedes AHRI Standard 770-2001. For SI ratings, see ANSI/AHRI Standard 771 (SI)-2014. Price $10.00 (M) $20.00 (NM) Copyright 2
5、014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office TABLE OF CONTENTS SECTION PAGE Section 1. Purpose . 1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Test Requirements 2 Section 5. Rating Requirements 2 Sect
6、ion 6. Minimum Data Requirements for Published Ratings . 3 Section 7. Marking and Nameplate Data . 4 Section 8. Conformance Conditions 4 TABLES Table 1. Standard Rating Conditions 3 APPENDICES Appendix A. References - Normative 5 Appendix B. References - Informative 5 _ANSI/AHRI STANDARD 770 (I-P)-2
7、014 1 PERFORMANCE RATING OF REFRIGERANT PRESSURE REGULATING VALVES Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Refrigerant Pressure Regulating Valves: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking an
8、d nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section
9、2. Scope 2.1 Scope. This standard applies to Refrigerant Pressure Regulating Valves controlling volatile refrigerant flow that primarily respond to pressure. The types of Refrigerant Pressure Regulating Valves are those that are responsive to inlet, to outlet, or to differential pressures sensed loc
10、ally or remotely. 2.2 Exclusions. Excluded from this standard are thermostatic expansion valves covered under AHRI Standard 750 and electronic expansion valves. Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Terminology website (https:/w
11、ww.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.2 Dew Point. Refrigerant vapor saturation temperature at a specified pressure. 3.3 Gradient. The ch
12、ange in controlled pressure required to move the refrigerant pressure regulating Valve Closure Member from its opening point to its standard rated capacity, psi. In some types of pilot-operated controllers, the Gradient could be essentially zero. 3.4 Main. Tubing or piping by which the Refrigerant P
13、ressure Regulating Valve is connected to the apparatus. 3.5 Pressure Drop. The pressure difference between the refrigerant pressure regulating valve inlet and the refrigerant pressure regulating valve outlet, with the main port (orifice) open, psi. 3.6 Published Rating. A statement of the assigned v
14、alues of those performance characteristics under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the ra
15、ting of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 3.6.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rat
16、ing Conditions). 3.6.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. ANSI/AHRI STANDARD 770 (I-P)-2014_ 2 3.7 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to oc
17、cur. 3.7.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3.8 Refrigerant Pressure Regulating Valve. A self or pilot-operated controller in which the energy to position the Valve Closure Member is provided by the pressure of the control
18、led refrigerant, sensed locally or remotely. 3.8.1 Valve Closure Member. The part of a valve which is positioned to close, open or modulate the flow through the valve port(s). 3.9 Refrigerant Pressure Regulating Valve Capacity. The capacity of a fluid flowing through the Refrigerant Pressure Regulat
19、ing Valve equated to tons of refrigeration at the specified conditions. 3.10 Set Point. A predetermined pressure or pressure differential which the Refrigerant Pressure Regulating Valve is set to maintain, psi. 3.11 “Shall“ or “Should.“ “Shall“ or “should“ are interpreted as follows: 3.11.1 Shall. W
20、here “shall” or “shall not” is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.11.2 Should. “Should” is used to indicate provisions which are not mandatory but which are desirable as good practice. 3.12 Volatile Refrigerant. A fluid used for
21、heat transfer in a refrigerating system which absorbs heat at a low temperature and low pressure of the fluid and transfers heat at a higher temperature and a higher pressure of the fluid, usually involving changes of state of the fluid. Section 4. Test Requirements 4.1 Capacity Tests. All refrigera
22、nt pressure regulating valve capacity tests shall be in accordance with the test procedure defined in ANSI/ASHRAE Standard 158.2. Section 5. Rating Requirements 5.1 Rating Requirements. Published Ratings for capacity shall consist of Standard Ratings and may include Application Ratings. The AHRI Sta
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAHRI770IP2014PERFORMANCERATINGOFREFRIGERANTPRESSUREREGULATINGVALVESPDF

链接地址:http://www.mydoc123.com/p-430622.html