ARI 890-2001 Air Diffusers and Air Diffuser Assemblies《空气扩散器和空气扩散组装》.pdf
《ARI 890-2001 Air Diffusers and Air Diffuser Assemblies《空气扩散器和空气扩散组装》.pdf》由会员分享,可在线阅读,更多相关《ARI 890-2001 Air Diffusers and Air Diffuser Assemblies《空气扩散器和空气扩散组装》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、 4301 NORTH FAIRFAX DRIVE G6c ARLINGTON, VIRGINIA 22203 2001 STANDARD for AIR DIFFUSERS AND AIR DIFFUSER ASSEMBLIES Standard 890 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS
2、-,-,-Price $10.00 (M) $20.00 (NM) Ge3Copyright 2001, by Air-Conditioning and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled and installed i
3、n accordance with nationally recognized safety requirements appropriate for products covered by this standard. ARI, as a manufacturers trade association, uses its best efforts to develop standards employing state-of-the-art and accepted industry practices. However, ARI does not certify or guarantee
4、safety of any products, components or systems designed, tested, rated, installed or operated in accordance with these standards or that any tests conducted under its standards will be non-hazardous or free from risk. Note: This standard supersedes ARI Standard 890-94. Copyright Air-Conditioning and
5、Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose 1 Section 2. Scope. 1 Section 3. Definitions 1 Section 4. Classifications. 3 Section 5. Test Requirements
6、 3 Section 6. Rating Requirements. 3 Section 7. Minimum Data Requirements for Published Ratings . 4 Section 8. Marking and Nameplate Data . 4 Section 9. Conformance Conditions 4 FIGURES Figure 1. Air Stream Patterns. 1 APPENDICES Appendix A. References - Normative 5 Appendix B. References - Informat
7、ive. 5 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reprodu
8、ction or networking permitted without license from IHS-,-,-ARI STANDARD 890-2001 1AIR DIFFUSERS AND AIR DIFFUSER ASSEMBLIES Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Air Diffusers and Air Diffuser Assemblies used in air distribution systems: definitions; classi
9、fications; test requirements; rating requirements minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users.
10、1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to Diffusers and Diffuser Assemblies used in air distribution systems which are duct connected to a remote forced air source, as defined in Section 3
11、. 2.2 Exclusions. This standard does not apply to Grilles, Registers, and troffer diffusers. Sound and pressure performance of Diffuser Assemblies providing for automatic volume control shall be rated in accordance with ARI Standard 880. Section 3. Definitions All terms in this document shall follow
12、 the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Air Inlet. A device through which air is removed or returned from a conditioned space. (Grilles, Registers, Diffus
13、ers, and Slots may be used as Air Inlets.) 3.2 Air Outlet. A device or opening through which air is discharged into a conditioned space. It is intended for the purpose of this standard that all accessories, connecting duct adapters, or other mounting airways may be considered part of the outlet devi
14、ce being tested and shall be, in such cases, reported as a unit or assembly. Some specific outlet designations are defined below. 3.2.1 Diffuser. An Air Outlet comprised of deflecting members generally located in the ceiling and designed to distribute air in varying directions and planes. 3.2.2 Diff
15、user Assembly. A terminal assembly consisting of a specifically recommended or fabricated duct, box, or plenum with an integral or attached air outlet or diffuser, such as a slot-plenum, or slot-duct assembly. 3.2.3 Grille. A louvered or perforated face over an opening which is generally located in
16、the sidewall, sill, or floor. 3.2.4 Register. A combination Grille and damper assembly. 3.2.5 Slot Diffuser or Slot. A long narrow air outlet (aspect ratio generally greater than 10:1). 3.3 Air Stream Patterns. These are characterized by the following terms (see Figure 1): Plan View Vertical Cross S
17、ection of the Principal Jet Figure 1. Air Stream Patterns THROWDIFFUSER TERMINAL VELOCITY ENVELOPEANGLE OF DISCHARGESPREAD CENTERLINE OFPRINCIPAL JETSPREADDROPTHROW Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARINot for ResaleNo reproduction or networkin
18、g permitted without license from IHS-,-,-ARI STANDARD 890-2001 2 3.3.1 Angle of Discharge. The largest included angle between centerlines of principal jets of the primary air stream. 3.3.2 Drop. The vertical distance that the lower edge of a horizontally projected air stream drops between the outlet
19、 and the end of its throw. 3.3.3 Envelope (ISOVEL). The boundary surface of points of equal velocity which describe the air distribution profile (see Figure 1). 3.3.4 Spread. The maximum distance, in ft m, measured parallel to the plane of the outlet between the extremes of the Terminal Velocity Env
20、elope (see Figure 1). 3.3.5 Terminal Velocity (Vt). The highest sustained velocity in the air stream from an outlet, fpm m/s, which is arbitrarily specified and used to determine throw (T). 3.3.6 Throw (T). The distance, ft m, from the center of the outlet to a point in the air stream where the high
21、est sustained velocity of the air stream has been reduced to a specified Terminal Velocity (see Figure 1). 3.4 Area Factor (Ak). An empirical factor of an outlet or inlet, ft2 m2, determined from the discharge or intake velocity (Vk) and the volume flow rate, Q, cfm m3/s. GfaGfbGf9GeaGebGe9=kkkkVsLA
22、VQA 3.5 Aspect Ratio. Ratio of the length/width of a rectangular air outlet. 3.6 Discharge or Intake Velocity (Vk). The average of the velocities of the air stream, fpm m/s, of an outlet or inlet, measured at specified locations relative to the face of the outlet or inlet with a specified instrument
23、. 3.7 Flow Rate. The volume of standard air per unit of time, cfm m3/s, which moves past a given plane. 3.8 Hertz (Hz). A unit of frequency equal to one cycle per second. 3.9 Neck Velocity (Vn). This is measured in fpm m/s and is calculated as follows: GfaGfbGf9GeaGebGe9=nnnnAsLVAQV where Anis the n
24、ominal area, ft2m2, of the duct connection to the Diffuser or Diffuser Assembly. 3.10 Octave Band. A frequency band of sound covering a range of frequencies such that the highest frequency is twice the lowest. The Octave Bands used in this standard are defined in ANSI Standard S1.11. 3.11 Pressure.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI8902001AIRDIFFUSERSANDAIRDIFFUSERASSEMBLIES 空气 扩散器 扩散 组装 PDF

链接地址:http://www.mydoc123.com/p-429471.html