ARI 440-2008 Performance Rating of Room Fan-Coils.pdf
《ARI 440-2008 Performance Rating of Room Fan-Coils.pdf》由会员分享,可在线阅读,更多相关《ARI 440-2008 Performance Rating of Room Fan-Coils.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、 2008 Standard for Performance Rating of Room Fan-Coils ARI Standard 440Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Price $10.00 (M) $20.00 (NM) Copyright 200
2、8, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office ARI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The certification program includes Room Fan-Coils as defined in Section 3, having air-delivery c
3、apacities of 1500 cfm 0.7080 m3/s or less. Room Fan-Coils employing Volatile Refrigerant Coils or steam coils, central-station air-handling units as defined in ARI Standard 430, and unit ventilators as defined in ARI Standard 840 are not included. Certified Ratings The following certification progra
4、m ratings shall be verified by test at the Standard Rating Conditions for Cooling Capacity (Section 6.3.1), and for power input (Section 6.3.4): 1. Total Cooling Capacity, Btu/h W 2. Sensible Cooling Capacity, Btu/h W 3. Power Input, W W Conformance to the requirements of the insulation efficiency t
5、est and the low voltage test (Section 8) shall also be verified by test. Note: This standard supersedes ARI Standard 440-2005. IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, i
6、nstalled or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guid
7、eline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Copyright Air-Conditioning, Heating and Re
8、frigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PAGE Section 1. Purpose .1 Section 2. Scope 1 Section 3. Definitions 1 Section 4. Classifications .3 Section 5. Test Requirements
9、3 Section 6. Rating Requirements 3 Section 7. Minimum Data Requirements for Published Ratings .5 Section 8. Operating Requirements .6 Section 9. Marking and Nameplate Data .6 Section 10. Conformance Conditions 6 TABLES Table 1. Heating Rating Conditions .4 APPENDICES Appendix A. References - Normati
10、ve 7 Appendix B. References - Informative 7 Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditioning, Heating and Refrigeration Institute Provid
11、ed by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 440-2008 1PERFORMANCE RATING OF ROOM FAN-COILS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to provide for Room Fan-Coils: definitions; classifications;
12、 test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contract
13、ors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to Room Fan-Coils, defined in Section 3, having air-delivery capacities of 1500 cfm 0.7080 m3/s or less. 2.2 Exclusions. 2.2.1 This st
14、andard does not apply to central-station air-handling units as defined in ANSI/ARI Standard 430. 2.2.2. This standard does not apply to unit ventilator units as defined in ARI Standard 840. 2.2.3 This standard does not apply to Room Fan-Coils employing: a. Volatile Refrigerant Coils b. Steam coils S
15、ection 3. Definitions All terms in this document shall follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Capacity. 3.1.1 Cooling Capacity. The capacity associ
16、ated with the change in air enthalpy which includes both the Latent and Sensible Capacities expressed in Btu/hW. 3.1.1.1 Latent Capacity. Capacity associated with a change in humidity ratio. 3.1.1.2 Sensible Capacity. Capacity associated with a change in dry-bulb temperature. 3.1.2 Heating Capacity.
17、 The capacity associated with the change in dry-bulb temperature expressed in Btu/hW. 3.2 Fan. A device for moving air which utilizes a power-driven rotating impeller. 3.3 Forced-Air Circulation. Air circulation caused by a difference in pressure produced by a fan. 3.4 Grille. Lattice or grating cov
18、ering the delivery or intake opening of an air passage. 3.5 Non-Volatile Refrigerant Coil. A coil in which the cooling fluid (usually water) remains in the liquid state during its passage through the coil. Copyright Air-Conditioning, Heating and Refrigeration Institute Provided by IHS under license
19、with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 440-2008 2 3.6 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. The
20、se values apply to all units of like nominal size and type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufact
21、urer, at stated Rating Conditions. 3.6.1 Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions). 3.6.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.7 Rating Conditions. Any set of operating
22、 conditions under which a single level of performance results and which causes only that level of performance to occur. 3.7.1 Standard Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3.8 Room Fan-Coil (cooling, heating, or cooling and heating). A
23、 factory-made assembly which provides the functions of cooling, heating, or cooling and heating, but which does not include the source of cooling or heating. This device is designed for free-delivery of air into a room, but may be applied with minimal duct work having a static resistance generally n
24、ot exceeding 0.25 in H2O 0.062 kPa. These devices may be designed for furred-in application, or with an enclosure for application within the conditioned space. 3.8.1 Free Delivery Units. Free Delivery Units are Room Fan-Coils furnished with both integral filters and grilles on the unit. 3.8.2 Furred
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI4402008PERFORMANCERATINGOFROOMFANCOILSPDF

链接地址:http://www.mydoc123.com/p-429442.html