AHRI 551 591 SI-2011 Performance Rating Of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle.pdf
《AHRI 551 591 SI-2011 Performance Rating Of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle.pdf》由会员分享,可在线阅读,更多相关《AHRI 551 591 SI-2011 Performance Rating Of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle.pdf(69页珍藏版)》请在麦多课文档分享上搜索。
1、 2011 Standard for Performance Rating Of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle AHRI Standard 551/591 (SI) Price $10.00 (M) $20.00 (NM) Copyright 2011, by Air-Conditioning, Heating and Refrigeration Institute Printed in U.S.A. Registered United States P
2、atent and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that pro
3、ducts be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and acc
4、epted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. AHRI CERTIFICATION PROGRAM PROVISIONS The scope of the Certification Program is based on the latest edition of AHRI Standard 550/590 (I-P)-201
5、1. This scope is current as of the publication date of the standard. Revisions to the scope of the certification program can be found on AHRI website www.ahrinet.org. The scope of the Certification Program should not be confused with the scope of the standard as the standard covers products that are
6、 not covered by a certification program. Included in Certification Program: 50 Hzaand 60 Hz Air-Cooled Chiller (ACCL) Product Inclusions Chillers between 0 and 700 kWbmanufactured prior to July 2011 Chillers between 0 and 1,405 kWbmanufactured between July 2011 and July 2013 Chillers between 0 and 2
7、,110 kWbmanufactured after July 2013 Units selected for use within the range of Application Rating Conditions as per AHRI Standard 551/591 (SI) Hermetic or open type, electric motor driven Up to 600 volts All compressor types Units intended for use with glycol or other secondary coolant for freeze p
8、rotection with a leaving chilled fluid temperature above 0.0C are certified when tested with water at Standard Rating Conditions. Note a: 50 Hz products selectively certified as per Section 1.4 of the Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Operations Manual Note b: The cool
9、ing capacity, in kW at full-load AHRI Standard Rating Conditions per Table 1 of AHRI Standard 551/591 (SI). 60 Hz Water -Cooled Chiller (WCCL) Product Inclusions All compressor types Chillers rated between 0 and 8,800 kWcmanufactured prior to January 2012 Chillers rated between 0 and 10,550 kWcmanuf
10、actured after to January 2012 Hermetic or open type,electric motor driven Units selected for use within the range of Application Rating Conditions as per AHRI Standard 551/591 (SI) Voltages up to 11,000 volts Voltages up to 15,000 volts after June 15, 2011 Positive Displacement Units intended for us
11、e with glycol or other secondary coolant for freeze protection with a leaving chilled fluid temperature above 0.0C are certified when tested with water at Standard Rating Conditions. Note c: Rated capacity, kW, for Positive Displacement chillers is the net cooling capacity at full-load AHRI Standard
12、 Rating Conditions per Table 1 of AHRI Standard 551/591 (SI). Rated capacity, kW, for centrifugal chillers is the net cooling capacity at full-load AHRI Application Rating Conditions within the range permitted in Table 2 of AHRI Standard 551/591 (SI). 50 Hz WCCL Product Inclusions Centrifugal test r
13、equirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, efficiency regulators, contractors and
14、users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made vapor compression refrigeration Water-Chilling and Water-Heating Packages including one or more hermetic or open drive compres
15、sors. These Water-Chilling and Water-Heating Packages include: Water-Cooled, Air-Cooled, or evaporatively-cooled condensers Water-Cooled heat reclaim condensers Air-to-water heat pump Water-to-water heat pumps with a capacity greater or equal to 40 kW. Water-to-water heat pumps with a capacity less
16、than 40 kW are covered by the latest edition of AHRI Standard 320 Note that this standard covers products that may not currently be covered under a certification program. Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Termi
17、nology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Auxiliary Power. Power provided to devices that are not integral to the operation of the vapor compression cycle. Such as, but not limited to: oil pumps, refrigerant pumps, control power,
18、 and heaters. 3.2 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.3 Capacity. A measurable physical quantity that characterizes the water side heat flow rate, kW. Capacity is defined as the mass flow rate of the water multiplied by the difference in enthalpy of wat
19、er entering and leaving the heat exchanger, kW or tons. For this standard, the enthalpy change is approximated as the sensible heat transfer using specific heat and temperature difference, and in some calculations also the energy associated with water-side pressure losses. 3.3.1 Gross Heating Capaci
20、ty. The capacity of the Water Cooled Condenser as measured by the heat transfer from the refrigerant in the condenser. This value includes both the sensible heat transfer and the pressure drop effects of the water flow through the condenser. This value is used to calculate the test heat balance. (Re
21、fer to Equations C12a and C12b). 3.3.2 Gross Refrigerating Capacity. The capacity of the water cooled evaporator as measured by the heat transfer to the refrigerant in the evaporator. This value includes both the sensible heat transfer and the pressure drop effects of the water flow through the evap
22、orator. This value is used to calculate the test heat balance. (Refer to Equation C11). AHRI STANDARD 551/591 (SI)-2011 2 3.3.3 Net Heating Capacity. The capacity of the heating condenser available for useful heating of the thermal load external to the Water-Heating Package and is calculated using o
23、nly the sensible heat transfer. (Refer to Equations 7a and 7b). 3.3.4 Net Refrigerating Capacity. The capacity of the evaporator available for cooling of the thermal load external to the Water-Chilling Package and is calculated using only the sensible heat transfer. (Refer to Equation 6). 3.4 Compre
24、ssor Saturated Discharge Temperature. For single component and azeotrope refrigerants, it is the saturated temperature corresponding to the refrigerant pressure at the compressor discharge. For zeotropic refrigerants, it is the arithmetic average of the Dew Point and Bubble Point temperatures corres
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI551591SI2011PERFORMANCERATINGOFWATERCHILLINGANDHEATPUMPWATERHEATINGPACKAGESUSINGTHEVAPORCOMPRESSIONCYCLEPDF

链接地址:http://www.mydoc123.com/p-422549.html