《ASTM F2522-12(2017) Standard Test Method for Determining the Protective Performance of a Shield Attached on Live Line Tools or on Racking Rods for Electric Arc Hazards.pdf》由会员分享,可在线阅读,更多相关《ASTM F2522-12(2017) Standard Test Method for Determining the Protective Performance of a Shield Attached on Live Line Tools or on Racking Rods for Electric Arc Hazards.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F2522 12 (Reapproved 2017)Standard Test Method forDetermining the Protective Performance of a ShieldAttached on Live Line Tools or on Racking Rods for ElectricArc Hazards1This standard is issued under the fixed designation F2522; the number immediately following the designation indicate
2、s the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method is used to determine the heat
3、 attenua-tion factor (HAF), the effective heat attenuation factor (EHAF),and the shields mechanical strength (SMS) of a shield attachedon live line tools or racking rods intended for protection ofworkers exposed to electric arcs.1.2 The materials used in this test method of workerprotection are in t
4、he form of a shield attached on live line toolsor on the racking rods.1.3 The protective shield described in this test method shallbe transparent and shall be easily attached and removed fromlive line tools or from racking rods.1.4 The protective shield described in this test method has24-in. (0.61-
5、m) diameter and can be used for most applications,however for special cases, the shield can have different sizes tosuit the protective requirements of the application.1.5 This standard shall be used to measure and describe theproperties of materials, products, or assemblies in response toincident en
6、ergies (thermal-convective, and radiant and pressurewave) generated by an electric arc under controlled laboratoryconditions and does not purport to predict damage from light,resultant pressure impact other than the pressure and thermalaspects measured.1.6 The values stated in inch-pound units are t
7、o be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.7 This standard shall not be used to describe or appraisethe fire hazard or fire risk of materials, products, or assembliesunder a
8、ctual fire conditions. However, results of this test maybe used as elements of a fire assessment, which takes intoaccount all of the factors, which are pertinent to an assessmentof the fire hazard of a particular end use.1.8 This standard does not purport to address all of thesafety concerns, if any
9、, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environmental practices and deter-mine the applicability of regulatory limitations prior to use.Forspecific precautions, see Section 7.1.9 This international standard was dev
10、eloped in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Do
11、cuments2.1 ASTM Standards:2D4391 Terminology Relating to The Burning Behavior ofTextilesF1959/F1959M Test Method for Determining theArc Ratingof Materials for Clothing3. Terminology3.1 Definitions:3.1.1 arc, nconductive path in air for the electric currentcaused by ionization of air between two elec
12、trodes.3.1.2 arc duration, ntime duration of the arc, s.3.1.3 arc energy, vi dt, nsum of the instantaneous arcvoltage values multiplied by the instantaneous arc currentvalues multiplied by the incremental time values during thearc, J.3.1.4 arc gap, ndistance between the arc electrodes, cmin.3.1.5 ar
13、c voltage, nvoltage across the gap caused by thecurrent flowing through the resistance created by the arc gap,V. See also Terminology D4391.1This test method is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommittee
14、F18.35 on Tools & Equipment.Current edition approved Nov. 1, 2017. Published December 2017. Originallyapproved in 2005. Last previous edition approved in 2012 as F2522-12. DOI:10.1520/F2522-12R17.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at
15、 serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accorda
16、nce with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.129 3.1.6 asymmetrical arc current,
17、 nthe total arc currentproduced during closure; it includes a direct component and asymmetrical component, A.3.1.7 blowout, nthe extinguishing of the arc caused by amagnetic field.3.1.8 closure, npoint on supply current wave form wherearc is initiated.3.1.9 effective heat attenuation (EHAF)/cone of
18、protection(COP) factor, nthe percentage of the incident heat energythat is attenuated by the shield at the location of the worker.3.1.10 fragmentation, nmolten metal fragments or otherfragments emitted from an electric arc.3.1.11 heat attenuation factor (HAF), nthe percentage ofthe incident heat ene
19、rgy that is blocked by the safety shieldmaterial.3.1.12 heat flux, nthe thermal intensity indicated by theamount of energy transmitted divided by area and timeW/m2cal cm2s.3.1.13 i2t, nsum of the instantaneous arc current valuessquared multiplied by the incremental time values during thearc, A2/s.3.
20、1.14 ignitability, n (ignitable, adj)in electric arcexposure, the property of a material involving ignition accom-panied by heat and light, and continued burning resulting inconsumption of at least 25 % of the exposed area of the testspecimen.3.1.15 ignition, nthe initiation of combustion.3.1.16 inc
21、ident energy (Ei), nthe amount of energy (totalheat, cal/cm2) received at a surface as a direct result of anelectrical arc discharge as measured by temperature rise oncopper calorimeters.3.1.17 peak arc current, nmaximum value of the AC arccurrent, A.3.1.18 pressure wave, na certain force over an ar
22、eacreated by air movement caused by an electric arc.3.1.19 RMS arc current, nroot mean square of the AC arccurrent, A.3.1.20 sensors, ncopper calorimeter, instrumented with athermocouple contained in a dielectric, heat protective housingfor use in measuring energy.3.1.21 shield mechanical strength v
23、alue (SMS) factor,nthe mechanical ability of the shield to withstand the electricarc pressure wave and fragmentation.3.1.22 X/R ratio, nthe ratio of system inductive reactanceto resistance. It is proportional to the L/R ratio of time constant,and is, therefore, indicative of the rate of decay of any
24、 DCoffset. A large X/R ratio corresponds to a large time constantand a slow rate of decay.4. Summary of Test Method4.1 This test method determines the heat attenuation factor(HAF) of the shield material, the effective heat attenuationfactor (EHAF) at the location where the worker may be whileholding
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTM F2522 12 2017 Standard Test Method for Determining the Protective Performance of Shield Attached on Live Line Tools or Racking Rods Electric Arc Hazards

链接地址:http://www.mydoc123.com/p-286569.html