UL SUBJECT 2874-2015 Outline of Investigation for Electric Motors for Use in Class I Division 1 Hazardous (Classified) Locations - Protection by Flammable Atmosphere Maintained abo.pdf
《UL SUBJECT 2874-2015 Outline of Investigation for Electric Motors for Use in Class I Division 1 Hazardous (Classified) Locations - Protection by Flammable Atmosphere Maintained abo.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2874-2015 Outline of Investigation for Electric Motors for Use in Class I Division 1 Hazardous (Classified) Locations - Protection by Flammable Atmosphere Maintained abo.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJULY 1, 20151UL 2874Outline of Investigation for Electric Motors for Use in Class I, Division 1Hazardous (Classified) Locations - Protection by Flammable AtmosphereMaintained above the UFLIssue N
2、umber: 1July 1, 2015Summary of TopicsThis first issue of the Outline of Investigation for Electric Motors for Usein Class I, Division 1 Hazardous (Classified) Locations - Protection byFlammable Atmosphere Maintained above the UFL, UL 2874, covers theexplosion protection of electric motors as permitt
3、ed by the nationalElectrical Code, NEC , Article 501.125 (A)(4) by means of submerging ina liquid that is flammable only when vaporized and mixed with air, or issubmerged in a gas or vapor at a pressure greater than atmospheric thatis flammable only when mixed with air.These requirements are for mac
4、hines that are for use only in industrialestablishments with restricted public access, where the conditions ofmaintenance and supervision ensure that only qualified persons servicethe installation.The machine is so arranged as to prevent energizing it until it has beenpurged with the liquid or gas t
5、o exclude air and also arranged toautomatically de-energize the equipment when the supply of liquid or gasor vapor fails or the pressure is reduced below atmospheric.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation should be alt
6、ered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORD
7、ISTRIBUTION WITHOUT PERMISSION FROM ULJULY 1, 2015UL 28742No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated References 5CONSTRUCTION5 General 56 M
8、otor Explosion Protection by Purging and Pressurization .67 Protection by Immersion 78 Controls and Instrumentation .7TESTING9 Over Pressure 810 Control .8MARKING AND INSTRUCTIONS11 General .812 Operating Manual 8BIBLIOGRAPHYJULY 1, 2015 UL 2874 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER RE
9、PRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover electric motors for installation and use in Class I, Division 1 hazardous(Classified) locations, in accordance with the National Electrical Code, NFPA 70.1.2 These requirements cover motors of a type
10、designed to be continuously submerged in a liquid that isflammable only when vaporized and mixed with air, and which is for use only in industrial establishmentswith restricted public access, where the conditions of maintenance and supervision ensure that onlyqualified persons service the installati
11、on.1.3 These requirements cover motors of a type designed to operate within a gas or vapor that isflammable only when mixed with air at a pressure greater than atmospheric and which is for use only inindustrial establishments with restricted public access, where the conditions of maintenance andsupe
12、rvision ensure that only qualified persons service the installation.1.4 These requirements anticipate common flammable gases, gas mixtures or flammable liquids withsignificant margin between the upper flammable limit and the purged and pressurized state of use for themotor.1.5 These requirements als
13、o cover fused and unfused electrically tripped PV switches.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a featur
14、e or characteristic not required in the application of the component in theproduct covered by this outline; orb) Is superseded by a requirement in this outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomp
15、lete in construction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.JULY 1, 2015UL 28744UL COPYRIGHTED MATERIAL N
16、OT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appeari
17、ng in the requirements of this outline shall beinterpreted as referring to the latest edition of that code or standard.CONSTRUCTION5 General5.1 The motor control means shall be so arranged as to prevent energizing the motor until it has beenpurged with the flammable liquid or flammable gas to exclud
18、e air as described in 6.1 7.1.5.2 The motor control means shall be so arranged to automatically de-energize the equipment when thesupply of liquid or gas or vapor fails or the pressure is reduced to a pre-set minimum pressure aboveatmospheric pressure. The minimum preset pressure shall be not less t
19、han 25 Pa (0.1 inches watercolumn).5.3 The equipment for monitoring the presence of the flammable fluid shall comply with permittedexplosion protection requirements for the Classification of the area in which it is located and be calibratedfor the gases that are present.5.4 Pressurized parts of the
20、equipment shall be compatible with the fluid in which it is in contact.5.5 Materials of construction for pressurized casings shall comply with the requirements found in API 617.5.6 Electrical connections at the interface with the pressurized flammable gas containment shall complywith ISA 12.27.01.5.
21、7 The motor shall comply with the Standard for Rotating Electrical Machines General Requirements,UL 1004-1 and applicable subparts, or IEC 60034-1 and subparts, or the Standard for Electric Motors andGenerators for Use in Hazardous Locations, UL 674 or Outline of Investigation Electric Motors andGen
22、erators for Use in Class I, Division 2, Class I, Zone 2, Class II, Division 2 and Zone 22 Hazardous(Classified) Locations, UL 1836 as is appropriate.5.8 The installation and use shall comply with the National Electrical Code, NFPA 70.JULY 1, 2015 UL 2874 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR F
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT28742015OUTLINEOFINVESTIGATIONFORELECTRICMOTORSFORUSEINCLASSIDIVISION1HAZARDOUSCLASSIFIEDLOCATIONSPROTECTIONBYFLAMMABLEATMOSPHEREMAINTAINEDABOPDF

链接地址:http://www.mydoc123.com/p-1069362.html