UL SUBJECT 1462-2006 Outline of Investigation for Mobile Home Pipe Heating Cable (Issue 4)《活动房屋管道加热电缆调查大纲 发布编号 4》.pdf
《UL SUBJECT 1462-2006 Outline of Investigation for Mobile Home Pipe Heating Cable (Issue 4)《活动房屋管道加热电缆调查大纲 发布编号 4》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1462-2006 Outline of Investigation for Mobile Home Pipe Heating Cable (Issue 4)《活动房屋管道加热电缆调查大纲 发布编号 4》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 21, 20061SUBJECT 1462OUTLINE OF INVESTIGATIONFORMOBILE HOME PIPE HEATING CABLEIssue Number: 4June 21, 2006Summary of TopicsThis fourth issue of the Subject 1462 Outline of Investigation for
2、MobileHome Pipe Heating Cable includes revisions to the Flexing Test for theheating section of the cable.The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard, the current version of the UL Forewor
3、d is located onULStandardsInfoNet at: http:/ 1990, 2006 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 21, 2006SUBJECT 14622No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION
4、 ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .4CONSTRUCTION2 Heating Conductors .43 Grounding Component .44 Jacket .55 Nonheating Leads .56 Thermostats 5PERFORMANCE7 Heating Section Tests .58 Complete Cable Tests .69 Permanence of Cord Tag and Marking Tests .7MARKING10 Detai
5、ls 811 Installation Instructions .9JUNE 21, 2006 SUBJECT 1462 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This outline covers mobile home pipe heating cable intended to reduce the likelihood of water freezingin expo
6、sed pipes of mobile homes in accordance with Article 550 of the National Electrical Code,ANSI/NFPA 70.1.2 Cable units employing different heating conductors, insulation, or other forms of construction may beexamined and tested in accordance with the intent of this outline, and if found to be substan
7、tiallyequivalent, may be covered.CONSTRUCTION2 Heating Conductors2.1 The heating conductors shall be insulated with a suitable insulating compound acceptable for use at75C (167F) or higher in wet locations. The minimum thickness of the insulation shall not be less than1/32 inch (0.8 mm) when not pro
8、vided with a nylon jacket and not less than 1/64 inch (0.4 mm) whenprovided with a 4 mil or thicker nylon jacket.2.2 Heating cables which utilize self-regulating positive temperature coefficient (PTC) materials shall beevaluated in accordance with the requirements for such materials. Reference is ma
9、de to the Appendix tothe Subject 1434 bulletin dated February 9, 1978, or to more current PTC requirements as appropriate.3 Grounding Component3.1 The heating section shall be provided with a grounding component that consists of a metallic sheathor braid. If the heating section consists of more than
10、 one conductor, the grounding component may beincorporated on each conductor or all conductors may be enclosed with a common sheath or braid. If thegrounding component consists of the braid, it shall provide at least 80 percent coverage and shall employmaterial that is corrosion resistant. The groun
11、ding component shall have a current-carrying capacity equalto or greater than that of the unit but not less than that of an 18 AWG (0.82 mm2) copper conductor. Thegrounding braid shall be connected to the grounding lead of the nonheating leads.JUNE 21, 2006SUBJECT 14624UL COPYRIGHTED MATERIAL NOT AU
12、THORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Jacket4.1 An optional insulating jacket may be employed over the grounding component.5 Nonheating Leads5.1 The heating section shall be connected to nonheating leads consisting of Type SJ or heavier flexiblecord acceptable
13、for outdoor use that is at least 2 feet (0.61 m) in length. The flexible cord shall not bemore than 6 feet (1.8 m) in length and shall be terminated by a grounding type attachment plug.6 Thermostats6.1 A thermostat for temperature control may be included in the cable assembly. The thermostat shallco
14、mply with the applicable requirements of the Standard for Temperature-Indicating and -RegulatingEquipment, UL 873.PERFORMANCE7 Heating Section Tests7.1 The heating section of the cable shall be subjected to the tests specified in Table 7.1.Table 7.1Tests for heating section of the cableTest ResultsO
15、vervoltage testa) 135 percent of rated voltage for 2 hours a) There shall be no damage to the insulation on theheating section or surrounding material.b) 200 percent of rated voltage for 2 minutes b) There shall be no damage to the insulation on theheating section or surrounding material.Flexing Tes
16、tThe heating cable shall comply with the Flexing of ShieldedCable Test of the Reference Standard for Electrical Wires,Cables, and Flexible Cords, UL 1581.Conductors shall not open in fewer than 15, 000 cycles.Impact TestWith flat plate, 5 pounds 1-1/4 inch diameter cylindricalweightShall withstand 1
17、5 foot-pounds.Abrasion TestaConducted only when insulating jacket is employed overgrounding component. Samples abraded by No. 1/2 emerycloth mounted on a curved plate, 3-1/2 inch radius, withsample supporting a 3/4 pound weight.Shall withstand 4000 cycles.Ground Component AmpacityThe ground componen
18、t is to be caused to carry a currentof:a) 135 percent of the branch circuit overloadprotection for 1 hour, andb) 200 percent of the branch circuit overloadprotection for 2 minutes.There shall be no damage to the insulation on the heatingsection.Cold BendJUNE 21, 2006 SUBJECT 1462 5Table 7.1 Continue
19、d on Next PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 7.1 ContinuedTest ResultsThe heating section is to be cooled to minus 35C (minus31F) for 1 hour and then wrapped around a metal mandrel3/8 inch (9.5 mm) in diameter.The insula
20、tion shall not crack.Flame TestThe heating section is to be subjected to the flame test inaccordance with the Standard for Thermoplastic-InsulatedWires and Cables, UL 83.The insulation shall not flame more than 1 minute after thefinal application of the test flame nor shall flame beconveyed during,
21、between, or after any application of thetest flame.aMay be omitted for units having outer braid or metallic sheath.8 Complete Cable Tests8.1 The complete cable shall be subjected to the tests specified in Table 8.1. Tests on PVC pipe areconsidered representative of metal pipe as well.Table 8.1Tests
22、for the complete cableTest ResultsInput The input shall be within 5 percent of the rated inputvalue of the unit when in the normal operating airtemperature.Temperature Under normal operation no material shall be exposed to atemperature over its rating. References to be made to theStandard for Electr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT14622006OUTLINEOFINVESTIGATIONFORMOBILEHOMEPIPEHEATINGCABLEISSUE4 活动房屋 管道 加热 电缆 调查 大纲 发布 编号

链接地址:http://www.mydoc123.com/p-1069174.html