UL 486C CRD-2014 UL Standard for Safety Splicing Wire Connectors - Section Paragraph Reference 1 1 2 1 3 2 1 4 2 1 5 2 1 6 6 3 10 7 15 8 15 9 15 10 25 Table 8 Annex F Subject Addi.pdf
《UL 486C CRD-2014 UL Standard for Safety Splicing Wire Connectors - Section Paragraph Reference 1 1 2 1 3 2 1 4 2 1 5 2 1 6 6 3 10 7 15 8 15 9 15 10 25 Table 8 Annex F Subject Addi.pdf》由会员分享,可在线阅读,更多相关《UL 486C CRD-2014 UL Standard for Safety Splicing Wire Connectors - Section Paragraph Reference 1 1 2 1 3 2 1 4 2 1 5 2 1 6 6 3 10 7 15 8 15 9 15 10 25 Table 8 Annex F Subject Addi.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): ZMVV/7Standard Number: UL 486CStandard Title: Standard for Splicing Wire ConnectorsEdition Date: January 11, 2013Edition Number: 6Section / Paragraph Referen
3、ce: 1.1, 2.1.3, 2.1.4, 2.1.5, 2.1.6, 6.3.10, 7.15, 8.15, 9.15,10.25, Table 8, Annex FSubject: Addition of Plenum Requirements for Wire ConnectorsDECISION:1.1 This Standard applies to single-polarity, hand- or tool-applied splicing wire and cable connectorsintended for use with all alloys of copper,
4、aluminum conductors, or copper-clad aluminum conductors, orall three, in accordance with the Canadian Electrical Code Part I, C22.1, in Canada, the National ElectricalCode, NFPA-70, in the United States of America, or the Standard for Electrical Installations,NOM-001-SEDE, in Mexico, as follows:Note
5、: Copper-clad aluminum conductors are for use only in the United States in accordance with the NationalElectrical Code, NFPA 70.a) connectors intended to hold two or more conductor(s);b) connectors intended for use in appliances and equipment that comply with the requirementsfor such appliances and
6、equipment;c) connectors intended for use with 6 AWG (13.3 mm2) or smaller conductors; andd) uninsulated connectors that are used in circuits rated 8 000 V and less; ande) connectors intended for use in air-handling spaces.Note: Examples of splicing wire connectors include twist-on connectors, insula
7、tion-piercing or displacement connectors, spring-action connectors, tool-applied crimp,mechanical set-screw connectors, etc.2.1.3 UL StandardsUL 746CPolymeric Materials Use in Electrical Equipment EvaluationsUL 2043 (NEW)Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Ac
8、cessories Installed inAir-Handling Spaces2.1.4 ULC Standards (NEW)UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULULC/ORD-C2043Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products and Their AccessoriesInstalled in Ai
9、r-Handling Spaces2.1.4.5 NFPA* StandardsANSI/NFPA 70-2011National Electrical Code (NEC)* National Fire Protection Association2.1.5.6 NOM Standards - Mexican Secretary of EnergyNOM-001-SEDEStandard for Electrical Installations6.3.10 (NEW) Connectors intended to be installed in air-handling spaces and
10、 marked Suitable for Use inAir-Handling Spaces, or equivalent, as indicated in 10.25, shall comply with System Flammability -Discrete Components Located In Air-Handling Spaces, clause 7.15.7.15 (NEW) System Flammability - Discrete Components Located In Air-Handling Spaces7.15.1 After being subjected
11、 to the test specified in 9.15, each sample set of wire connectors intended tobe installed in air-handling spaces shall comply with the following parameters:a) The peak rate of heat release (HRRc) measured during each test shall be 100 kW or less.b) The peak normalized optical density measured durin
12、g each test shall be 0.50 or less.c) The average normalized optical density (10 min test duration) shall be 0.15 or less.8.15 (NEW) System Flammability - Discrete Components Located In Air-Handling Spaces8.15.1 The sample set for this test shall be the maximum number of wire connectors that will be
13、withinany 6-m (20-ft) square suspended ceiling grid area, as specified in the markings. Wire connectors shallbe tested in sample sets of twenty four (24), unless the markings for the connector identify a largernumber. See 10.25.9.15 (NEW)9.15.1 Wire connectors intended for use in air-handling spaces
14、 shall be subjected to the tests in:In Canada:Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products andTheir Accessories Installed in Air-Handling Spaces, ULC/ORD-C2043.In the United States:STANDARD NUMBER: UL 486C -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRO
15、DUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULStandard for Fire Test for Heat and Visible Smoke Release for Discrete Products andTheir Accessories Installed in Air-Handling Spaces, UL 2043.aaProducts evaluated in accordance with these requirements are considered to comply with the fire retardant
16、and low smokeproducing requirements of Section 300 of National Electrical Code, ANSI/NFPA 70; Chapter 4 of Standard for the Installation ofAir-Conditioning and Ventilating Systems, NFPA 90A; Section 602 of the International Mechanical Code; and Section 602 of theUniform Mechanical Code.10.25 (New) T
17、he connector, unit container or information sheet for a connector that has been foundsuitable for installation in air-handling spaces shall be marked Suitable for use in Air-Handling Spaces(Plenums), or equivalent. The markings shall also state No more than twenty four (24) connectors areto be insta
18、lled within a 20-ft square suspended ceiling grid area unless a larger number is tested per8.15.1, in which case the larger number may be cited.Table 8 Minimum number of specimens for test(Clauses 8.1.1, 8.2.1, 8.3.1, 8.4.1, 8.5.1, 8.6.1, 8.7.1, 8.8.1, 8.9.1, 8.10.1, 8.11.1, 8.12.1, 8.13.1, and8.14.
19、1 and 8.15.1)Clause Test Number of specimens9.2 Current cycling 4 of each combination of connector andtest conductor(s)9.3 Static-heating sequence 4 of each combination of connector andtest conductor(s)9.4Mechanical sequence 2 of each combination of connector andtest conductor(s)Dielectric withstand
20、Thermosetting, e.g., porcelain, cold-molded melamine, phenolic, orurea-compound9.5.2 TestA-asreceived 12a9.5.3 TestB-asreceived 12a9.5.4 TestC-asreceived 12aThermoplastic, e.g., vinyl or nylon9.5.2 TestAasreceived 12a9.5.2 Test A after oven conditioning with specimensassembled to conductor before su
21、ch conditioning12a9.5.2 Test A after oven conditioning with specimensassembled to conductor after such conditioning12a9.5.3 TestB-asreceived 12a9.5.4 TestC-asreceived 6Secureness of insulation9.6.1 As received 69.6.3(a) a) Unassembled as received 6 after oven conditioning 69.6.3(b) b) Assembled as r
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL486CCRD2014ULSTANDARDFORSAFETYSPLICINGWIRECONNECTORSSECTIONPARAGRAPHREFERENCE1121321421521663107158159151025TABLE8ANNEXFSUBJECTADDIPDF

链接地址:http://www.mydoc123.com/p-1068196.html