FORD W-ES20-2003 DISCONNECT SWITCHES AND OPERATING MECHANISMS《隔离开关和操作机制[替代 FORD EX3 FORD EX3]》.pdf
《FORD W-ES20-2003 DISCONNECT SWITCHES AND OPERATING MECHANISMS《隔离开关和操作机制[替代 FORD EX3 FORD EX3]》.pdf》由会员分享,可在线阅读,更多相关《FORD W-ES20-2003 DISCONNECT SWITCHES AND OPERATING MECHANISMS《隔离开关和操作机制[替代 FORD EX3 FORD EX3]》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、 Printed copies are uncontrolled. Page 1 of 8 Standard Number: w-ES20 Issue Date: 20030217 Global Manufacturing Standards Rev: 20030220 DISCONNECT SWITCHES AND OPERATING MECHANISMS 1 PURPOSE AND SCOPE: This Standard applies to disconnects and operating mechanisms used in combination motor starters a
2、nd industrial control enclosures at 600 VAC and below. It also applies to separately mounted self-enclosed safety switches used for service disconnects and auxiliary equipment. This Standard does not apply to 480 VAC power distribution equipment, such as unit substations and busways. 1.1 MANDATORY A
3、ND PREFERRED ITEMS Mandatory requirements of this Standard are characterized by the use of the word “shall“. Preferred items are characterized by the use of the word “should“. 1.2 DEFINITIONS: 1.2.1 DISCONNECT (Disconnecting Means): A disconnect switch, circuit breaker, automatic molded case switch
4、(MCS), or safety switch used as an energy isolating device on industrial equipment in accordance with 29 CFR 1910.147. The disconnect shall isolate the equipment from all ungrounded conductors of the supply circuit and shall be capable of being locked out with at least 3 standard Ford-issued padlock
5、s, refer to Section 6.7. 1.2.2 OPERATING MECHANISM: The external handle, linkage, and coupling mechanism to the disconnect. 1.2.3 EXTERNAL HANDLE: That portion of the operating mechanism that is mounted on the right-most enclosure flange for main disconnect switches, or to the front of the switch en
6、closure for IEC rotary switches (see Clause 3.5). 1.2.4 LINKAGE: The connection between the external handle and the coupling mechanism. 1.2.5 COUPLING MECHANISM: The device which operates the disconnect to the ON and OFF positions. 1.2.6 AUTOMATIC MOLDED CASE SWITCH (MCS): An enclosed switching devi
7、ce which looks like a circuit breaker, but that contains a nonadjustable, magnetic instantaneous trip unit providing only short-circuit protection. 1.2.7 CURRENT LIMITING CIRCUIT BREAKER: An enclosed thermal magnetic switching device that does not employ a fusible element and that when operating wit
8、hin its current-limiting range: Printed copies are uncontrolled. Page 2 of 8 Standard Number: w-ES20 Issue Date: 20030217 Global Manufacturing Standards Rev: 20030220 1.2.7.1 Limits the let-through I2t current to a value less than the I2t current of the first half cycle wave of the symmetrical prosp
9、ective current. 1.2.7.2 Interrupts before the current peak and clears the fault completely within the first half cycle. 1.2.8 IEC DISCONNECT: An IEC designed manual motor controller/isolator (load break switch) additionally marked “Suitable As Motor Disconnect“. 2. NORMATIVE REFERENCES: Disconnects
10、shall conform to the latest revisions of the following standards, except where noted. Where differences exist this standard shall take precedence. SAE HS-1738 (1995) Electrical Standard for Industrial Machinery IEC/EN 60204-1 Safety of Machinery Electrical Equipment of Machines, Part 1. General Requ
11、irements ANSI/NFPA 70 - National Electrical Code (N.E.C.) Knife Blade Type Disconnect Switches: National Electrical Manufacturers Association (NEMA) KS-1 “Enclosed Switches“. Underwriters Laboratories (UL) ANSI/UL 0098 “Enclosed and Dead-Front Switches“. Canadian Standards Association (CSA) C22.2.4,
12、 “Enclosed Switches“. Rotary Type Disconnect Switches: Underwriters Laboratories (UL) ANSI/UL 508 “Industrial Control Equipment“. Canadian Standards Association (CSA) C22.2.14, “Industrial Control Equipment“. IEC 60947-3 “Low Voltage Switchgear and Controlgear Part 3: Switches, Disconnectors, Switch
13、-Disconnectors, and Fuse-Combination Units“. Circuit Breakers and Molded Case Switches: National Electrical Manufacturers Association (NEMA) AB-1, “Molded Case Circuit Breakers and Switches“. Underwriters Laboratories (UL) ANSI/UL 498, “Molded Case Circuit Breakers and Circuit Breaker Enclosures“. U
14、nderwriters Laboratories (UL) ANSI/UL 1087, “Molded Case Switches“. Canadian Standards Association (CSA) C22.2.5, “Molded Case Circuit Breakers, Molded Case Switches, and Circuit Breaker Enclosures“. 2.1 All disconnecting means shall be UL Listed, CSA Certified, and CE Marked in accordance with the
15、above standards and shall bear these mark(s). Printed copies are uncontrolled. Page 3 of 8 Standard Number: w-ES20 Issue Date: 20030217 Global Manufacturing Standards Rev: 20030220 Note: Safety disconnect switches are either UL Listed or CSA Certified. This is due to differences in requirements for
16、bonding the neutral bar inside the switch enclosure. 3. GENERAL REQUIREMENTS ALL TYPES: 3.1 DISCONNECT SWITCHES shall have visible knife blades OR positive-opening contacts. Both types shall have durable handle position markings that indicate all switch contacts are open in the OFF or “0“ position.
17、3.2 CIRCUIT BREAKERS and MOLDED CASE SWITCHES (MCS) shall have a position indicator which cannot indicate OFF until all contacts are actually open with an adequate isolating distance between the contacts in conformance with NEMA and IEC requirements for its maximum voltage rating. 3.3 SAFETY SWITCHE
18、S shall have NEMA 12 (or minimum IP54) “Heavy Duty“ steel enclosures without knockouts, unless otherwise specified by the requisitioning activity. 3.4 AUXILIARY CONTACTS: N.O./N.C. interlock contact kits, either single or dual, shall be available from the disconnect switch manufacturer. These interl
19、ocks shall open their contact(s) slightly before the disconnect opens. 3.5 OPERATING HANDLE SHALL BE PERMANENTLY AFFIXED to the disconnect so the HANDLE IS IN CONTROL OF THE DISCONNECT AT ALL TIMES, including when the enclosure door(s) are open. This requirement does not preclude removal of the hand
20、le or enclosure cover with tools. 3.6 TERMINAL CONNECTIONS: 3.6.1 Protection: There shall be no exposed live parts when the disconnect is in the OFF (open) position. An insulating cover, shield, or other means shall be provided by the disconnect manufacturer to guard against inadvertent contact with
21、 the line terminals. If test probe holes are provided in this cover, they shall be designed with an IP2X finger-safe rating, and prevent shorting between live parts or live parts and other metal parts. 3.6.2 Terminal Connectors: Connectors shall be pressure screw type for suitable for copper wire an
22、d in conform to UL 98 Section 11.3. Terminals for #8 AWG (10 mm2) or smaller conductors shall be the pressure plate type. 3.7 SUPPLEMENTARY SHIELDS: The Standards listed under the Normative References do not require shields over fusible disconnects. Where local government regulations or Ford Divisio
23、n-level specifications dictate shields, they shall be provided only by the disconnect manufacturer in order to maintain the UL/CSA/CE safety rating of the disconnect. Printed copies are uncontrolled. Page 4 of 8 Standard Number: w-ES20 Issue Date: 20030217 Global Manufacturing Standards Rev: 2003022
24、0 3.8 GROUNDING PROVISIONS: Shall conform to UL 98 Section 16 and Section 17. 3.9 CORROSION PROTECTION: Shall conform to UL 98 Section 7.10 and Section 7.11. 4. DISCONNECTS: Unless otherwise specified by the requisitioning activity, a fusible disconnect switch (Figure A) shall be used where the tota
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDWES202003DISCONNECTSWITCHESANDOPERATINGMECHANISMS 隔离 开关 操作 机制 替代 FORDEX3FORDEX3 PDF

链接地址:http://www.mydoc123.com/p-748370.html