DLA W-C-375 15 B-2009 CIRCUIT BREAKERS MOLDED CASE BRANCH CIRCUIT AND SERVICE TYPE I SERIES TRIP THREE POLE (15 THROUGH 100 AMPERES).pdf
《DLA W-C-375 15 B-2009 CIRCUIT BREAKERS MOLDED CASE BRANCH CIRCUIT AND SERVICE TYPE I SERIES TRIP THREE POLE (15 THROUGH 100 AMPERES).pdf》由会员分享,可在线阅读,更多相关《DLA W-C-375 15 B-2009 CIRCUIT BREAKERS MOLDED CASE BRANCH CIRCUIT AND SERVICE TYPE I SERIES TRIP THREE POLE (15 THROUGH 100 AMPERES).pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、 W-C-375/15B 16 June 2009 SUPERSEDING W-C-375/15A 04 August 2004 FEDERAL SPECIFICATION SHEET CIRCUIT BREAKERS, MOLDED CASE, BRANCH CIRCUIT AND SERVICE, TYPE I, SERIES TRIP, THREE POLE (15 THROUGH 100 AMPERES) The General Services Administration has authorized the use of this federal specification sh
2、eet by all federal agencies. The complete requirements for procuring circuit breakers described herein shall consist of this document and the latest issue in effect of W-C-375. FIGURE 1. Interface and physical dimensions. AMSC N/A FSC 5925 INCH-POUND Provided by IHSNot for ResaleNo reproduction or n
3、etworking permitted without license from IHS-,-,-W-C-375/15B 2 Inches mm Inches mm .156 3.96 2.812 71.42 .312 7.92 2.875 73.03 .438 11.13 3.000 76.20 1.250 31.75 3.094 78.59 1.562 39.67 3.281 83.34 2.062 52.37 3.344 84.94 2.312 58.72 NOTES: 1. Dimensions are in inches. 2. Metric equivalents are give
4、n for general information only. 3. Tolerance is .01 (0.25 mm) for two-place decimals and .005 (0.13 mm) for three-place decimals. 4. Lug sizes 15 through 50A #14 thru #4, 60 through 70A #4 through #2, 80 through 100A #4 through 1/0; terminals shall be suitable for aluminum (AL) or copper (CU) wire.
5、FIGURE 1. Interface and physical dimensions - Continued. REQUIREMENTS: Interface and physical dimensions: See figure 1. Trip indication: See figure 1. Common trip: All poles shall make and break simultaneously when operated manually or automatically. Electrical: Interrupting current rating: RMS symm
6、etrical - 10,000 amperes. Voltage rating: 240 V ac or less. Trip current: See table I. Frequency: 60 hertz. Calibration: At +40C. Enclosure for overload, endurance, and short circuit tests: Federal Pacific Electric, Catalog No. 312-24, or equivalent. Provided by IHSNot for ResaleNo reproduction or n
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAWC37515B2009CIRCUITBREAKERSMOLDEDCASEBRANCHCIRCUITANDSERVICETYPEISERIESTRIPTHREEPOLE15THROUGH100AMPERESPDF

链接地址:http://www.mydoc123.com/p-701435.html