CSA CGA 3 2-1976 IndustriaZ and Commercial Gas-Fired Package Furnaces (Errata 1 September 1992)《工业和商业用燃气组式加热炉 更正1 勘误表1 1992年9月》.pdf
《CSA CGA 3 2-1976 IndustriaZ and Commercial Gas-Fired Package Furnaces (Errata 1 September 1992)《工业和商业用燃气组式加热炉 更正1 勘误表1 1992年9月》.pdf》由会员分享,可在线阅读,更多相关《CSA CGA 3 2-1976 IndustriaZ and Commercial Gas-Fired Package Furnaces (Errata 1 September 1992)《工业和商业用燃气组式加热炉 更正1 勘误表1 1992年9月》.pdf(53页珍藏版)》请在麦多课文档分享上搜索。
1、CGA 3.2-1976 IndustriaZ and Commercial Gas-Fired Package Furnaces (Reaf f i r med 2003) September 1992 CGA-3.2-1976 ir ERRATA #I to CGA9.2-1976 INDUSTRIAL AND COMMERCIAL (formerly CSA 8203.2) GAS-FIRED PACKAGE FURNACES This errata contains printing corrections to National Standard of Canada CGA- 3.2
2、-1976, Industrial and Commercial Gas-Fired Package Furnaces (formerly CSA B203.2). This Standard was published in May 1976. The page(s1 of this errata are dated September 1992 and numbered: 23A and 24A to replace page(s) 23 and 24 and the CONTENTS page is dated September, 1992 to show this addition.
3、 NOTE : New and amended clauses are identified by a vertical line (“redline“) in the left margin. The page(s) are to be inserted into your copy of the Standard. t PUBUSHED BY Canadian Standards Association 5060 Spectrum Way, Suite 100 Mississauga, Ontario, Canada L4W 5N6 Copyright 0 Canadian Standar
4、ds Association - September 1992 Reprinted: 1 September. 1992 CONTENTS LIST OF I.G.A.C. MEMBERS . LIST OF COMMITTEE MEMBERS . INTRODUCTION . STANDARDS OF REFERENCE I ERRATA #1 . STANDARD SECTION 1 SCOPE . SECTION 2 CONSTRUCTION REQUIREMENTS AND VALVE TRAIN DIAGRAMS . . 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8
5、 2.9 2.10 2.11 2.12 2.13 2.14 2.15 SECTION 3 General Marking MainBurner Flame Safeguards . Pilots Piping and Fittings Air Control Mechanical Draft . Valve Trains for Low Pressure Gas . Valve Trains for Medium Pressure Gas . Valve Trains for High Pressure Gas Test Openings . Safety Controls Electrica
6、l Equipment and Wiring Draft Hoods PERFORMANCE 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 General Combustion Automatic Pilots and Pilots Furnace Safety Limiting Devices Temperatures . Combustion Safety Controls Other Safety Controls . Operating Controls Manifold and Control Assembly Capacity . . Elect
7、rical Tests . SECTION 4 INSTRUCTIONS . 4.1 4.2 Operating Instructions Installation and Service Instructions . PAGE iii. iv v. vi. vii viii viii ix 1 2 4 6 6 7 8 9 10 12 12 16 16 17 17 18 19 20 20 21 22 23A 24A 25 25 26 26 26 27 27 28 i 3.3.5 I flame sensing device does not sense a flame. The gas sup
8、ply to the pilot shall then be increased sufficiently only for the pilot flame sensing device to sense the pilot flame. pilot shall effectively ignite the gas within 2 s from the time gas is admitted to the main burner(s) . At this pilot input, the Temperatures of automatic ignition and safety shut-
9、off devices shall not exceed those shown in Table I, Column 1, Appendix B. METHOD OF TEST Thermocouples shall be peened into or brazed to the parts of these devices wherever over-heating may be anticipated. The main burner(s1 and pilot burner(s) shall be operated at normal test pressure until equili
10、brium pilot temperatures have been attained. Temperatures attained at the points listed above shall be recorded and shall not be in excess of those shown in Table I, Column 1, Appendix B, when tested in accordance with Section 3.2. 3.4 Furnace Safety Limiting Devices 3.4.1 The safety limit control w
11、hen adjusted to a maximum setting and minimum differential, shall function to shut off the gas at the maximum air outlet temperature specified by the manufacturer but in any event not in excess of 250F. METHOD OF TEST The furnace shall be fired at rated input with the limit control set at its maximu
12、m temperature setting. established by gradually restricting the circulating air flow until the limit control operates to shut off or reduce the fire. The outlet air temperature shall be 3.4.2 Continuous Operation All units intended for heating purposes shall be capable of continuous operation of max
13、imum normal input without the safety limit control or controls functioning either completely or intermittently to shut off or reduce the fuel input; METHOD OF TEST The furnace shall be fired at rated input and the circulating air flow adjusted to maintain an outlet air temperature 90F (plus or minus
14、 10F) above inlet air temperature. The fan switch, if used, and the limit control shall be operative and each adjusted to the maximum setting and the minimum differential. The limit control shall allow continuous firing of the furnace under the above condition. After equilibrium temperatures are att
15、ained, gradually restrict the cold-air return or filter. The limit control shall function when or before the outlet air temperature reaches the maximum allowed as deter- mined in 3.4.1. If, after the limit control functions, the outlet air temperature exceeds 110 percent of the maximum allowable, th
16、en permit furnace to cycle on limit control until equilibrium or continuously receding temperatures are attained. exceed the limits given in Table I, Column 2, during the first five cycles nor the limits given in Column 1 for succeeding cycles. The maximum temperatures shall not 23A Copyright 0 Cana
17、dian Standards Association - September 1992 3.5 Overatins Temperatures 3.5.1 3.5.2 3.5.3 3.5.4 3.5.5 The temperatures attained by components shall not exceed the values given in Column 1, Table I, Appendix B, when the furnace is operated continuously at rated input. For purposes of this test tempera
18、tures attained will be corrected to an ambient of 77OF. bfETHOD OF TEST The furnace shall be fired as specified in Section 3.2 with the operating control by-passed and the limit control set at the value established by 3.4.1. The furnace shall be operated until maximum temperatures are obtained. The
19、temperature of the components shall not exceed those given in Column 1, Table I, Appendix B. The temperatures attained by combustible construction adjacent to the furnace shall not exceed the temperatures shown in Column 1, Table I, Appendix B. correct to an ambient of 77F. For purposes of this test
20、 temperatures attained will be MZTHOD OF TEST The furnace shall be installed in an enclosure at the clearances specified by the manufacturer. If none are specified, standard clearances of 6 inches above, sides, rear and vent and 18 inches in front shall be used. The furnace will be operated as in 3.
21、5.1. The temperature shall not exceed those given in Column 1, Table I, Appendix B. Blower Failure (Forced Air Units only). described in 3.4.1 fire furnace at rated input until equilibrium temperatures are attained. Then open the electric circuit to fan motor only. equilibrium or receding temperatur
22、es are attained. The maximum temperatures shall not exceed the limits given in Table I, Column 2, Appendix B, during the first five cycles effected by operation of the limit control nor the limits given in Column 1 for succeeding cycles. With the furnace prepared for operation as Continue test, allo
23、wing furnace to cycle on limit control until Blocked Outlet Fire the furnace prepared as for 3.5.3 but with all electrical circuits in order, until equilibrium temperatures are attained. Then close warm-air outlets and allow furnace to cycle on limit control until equilibrium or receding temperature
24、s are attained. temperature shall not exceed the limits given in Table I, Column 2, Appendix B, during the first five cycles effected by operation of the limit control nor the limits given in Column 1 for succeeding cycles. The maximum Blocked Outlet $ Ontario J. F. Zinn Electronics Corp. of America
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CSACGA321976INDUSTRIAZANDCOMMERCIALGASFIREDPACKAGEFURNACESERRATA1SEPTEMBER1992 工业 商业 燃气 加热炉 更正 勘误表 11992

链接地址:http://www.mydoc123.com/p-621463.html