1、- 35115789 06114815 1189 CEMP-ET Technical Letter NO. 11 10-3-485 DEPARTMENT OF THE ARMY U.S. Army Corps of Engineers Washington, D.C. 20314-1000 ETL 11 10-3-485 15 October 1997 Engineering and Design FIRE PROTECTION FOR HELICOPTER HANGARS Distribution Restriction Statement Approved for public relea
2、se; distribution is unlimited. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3535789 0834836 035 N CEMP-ET Technical Letter NO. 1 110-3-485 DEPARTMENT OF THE ARMY ETL 1110-3-485 U.S. Army Corps of Engineers Washington, D.C. 203 14-1 O00 15 October
3、1997 Engineering and Design FIRE PROTECTION FOR HELICOPTER HANGARS 1. Purpose. This letter provides criteria relative to the design and construction of fire protection features and systems at Army facilities. 2. e. This letter appiies to all HQUSACE elements and USACE commands having military constr
4、uction and design responsibility. 3. References. See Appendix A 4. - Approved for public release; distribution is unlimited. 5. Objective, There is currently no design criteria applicable to fire protection for helicopter facilities. Neither the Military Handbook (MLHDBK-lOOSC), Fire Protection for
5、Facilities, Engineering, Design and Construction nor NFPA 409, Aircraft Hangars, provides spdc fire protection requirements for helicopters. Consequently, various approaches to fire protection for Army helicopter facilities have been taken, resulting in a lack of uniformity in protection features pr
6、ovided Army-wide. This letter seeks to provide a uniformand cost-effective approach to helicopter hangar fire protection. 6. a. The guidance included in Appendii B to this technical letter will be used for planning, design and construction of fire protection features and systems for Army facilities.
7、 7. . . This technical letter will have special application, as defined in paragraph Sc, ER 11 10-345-100. FOR THE COMMANDER: 2 Appendices APP A - References APP B - Fire Protection For Helicopter Hangars This ETL supersedes ETL 11 10-3-467, dated 30 December 1994 Provided by IHSNot for ResaleNo rep
8、roduction or networking permitted without license from IHS-,-,-3515789 0814817 T51 = ETL 11 10-3-485 15 Oct 97 GOVERNMENT PUBLICATIONS Department of Defense MIL-HDBK 1008C Department of the Army ETL 1 1 10-3-484 APPENDIX A REFERENCES Handbook, Fire Protection For Facilities, Engineering, Design and
9、Construction US. Army Corps of Engineers, Engineering Technical Letter (ETL), Aircraft Hangar Fire Protection Systems, 26 September 1997 NONGOVERNMENT PUBLICATIONS International Conference of Building Officials, 5360 Workman Mill Road, Whittier, CA 90601 Uniform Building Code National Fire Protectio
10、n Association (NFPA), 1 Batterymarch Park, Quincy, MA 02269-9 1 O1 NFPA 10 Portable Fire Extinguishers NFPA 13 Sprinkler Systems NFPA 20 Centrifugal Fire Pumps NFPA 24 NFPA 70 National Electrical Code NFPA 72 NFPA 90A Private Fire Service Mains and Their Appurtenances National Fire Alarm Code Air Co
11、nditioning and Ventilating Systems A- 1 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3535789 0834838 998 W ETL 11 10-3-485 15 Oct 97 NFPA 101 NFPA 256 NFPA 409 Life Safety Code Fire Tests of Roof Systems Aircraft Hangars A-2 Provided by IHSNot for
12、 ResaleNo reproduction or networking permitted without license from IHS-,-,-3535789 OBL48L 824 ETL 11 10-3-485 15 Oct 97 APPENDIX B FIRE PROTECTION FOR HELICOPTER HANGARS TABLE OF CONTENTS Page . 1 . INTRODUCTION B-1 2 . BACKGROUND B-1 . 3 . GENERAL REQUIREMENTS B-1 3.1 Construction Type B-1 3.2 Exi
13、t and Access Requirements . B- 1 3.3 Distance from Other Buildings . B-1 3.4 Fire Area Limitations B-2 3.5 Internal Fire Separations B-2 3.7 Structural Steel Columns . B-2 3.8 Draftcurtains B-2 3.9 Interior Finish 3.1 O Floor Drainage . B-2 3.1 1 Heating Equipment B-3 3.12 Electrical Systems . B-3 3
14、.13 Fire Protection Systems and Equipment B-3 3.6 Roofs B-2 B-2 4 . SPRINKLER PROTECTION FOR HANGAR BAYS B-4 4.2 System Selection B-4 4.3 Foam-Water Sprinkler Systems . B-4 4.4 Water-Only Sprinkler Systems . B-5 4.5 ESFR Sprinkler Systems Design Requirements . B-6 4.1 SystemTypes B-4 B-i Provided by
15、 IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-= 3515789 O814820 546 ETL 11 10-3-485 15 Oct 97 Page 5 . FIRE PROTECTION WATER SUPPLY B-7 5.1 Water Storage . B-7 5.2 Exterior Hose Demand . B-7 5.3 Duration of Supply B-7 5.4 Underground Water Mains B-7 5.5 Firep
16、umps B-7 6 . FIFE PROTECTION SYSTEM DESIGN REQUIREMENTS B-8 6.1 Designer Qualifications . B-8 6.2 Technical Center of Expertise (TCX) B-8 6.3 Design Procedures B-8 6.3.1 Design Analysis B-8 6.3.3 Specifications B-9 6.3.2 Drawings . B-8 B-ii Provided by IHSNot for ResaleNo reproduction or networking
17、permitted without license from IHS-,-,-3535789 O834821 482 = ETL 11 10-3-485 15 Oct 97 1. INTRODUCTION Army helicopters are routinely housed in hangars and similar facilities in order to perform maintenance, make repairs, and provide protection from adverse weather. Because these aircraft are usuall
18、y fueled, they present a fire potential to the facility and the other valuable helicopters and equipment also contained in it. In order to protect against a possible mishap, various fire protection features and systems are essential. Sound fire protection engineering principles mandate a protection
19、system commensurate with the loss potential. Although the probability of a catastrophic fire event may be low, the severity can be high. To mitigate the loss potential, this ETL establishes requirements for cost-effective construction features and fire protection systems. This ETL recognizes the dif
20、ference in fire potential presented by helicopters as compared to fixed-wing aircraft and provides an alternative to conventional foam fire protection systems. 2. BACKGROUND This ETL has been prepared because there are currently no design criteria applicable to fire protection for facilities housing
21、 helicopters. Currently-published criteria focus on the hazards and fire potential associated with various sizes of fixed-wing aircraft. Attempts have been made by designers to apply the provisions of NFPA 409, Aircraft Hangars, to facilities housing helicopters. Unfortunately, NFPA 409 is applicabl
22、e only to facilities housing fixed-wing aircraft, not helicopters. Thus, in the absence of criteria specifically applicable to helicopter hangars, various approaches to fire protection have been taken. This has resulted in a lack of uniformity of protection features provided for Army helicopter hang
23、ars. This ETL specifically addresses the hazards and loss potential posed by helicopters and provides criteria for fire protection features and systems in new Army helicopter hangars as well as in retrofitting existing facilities. 3. GENERAL REQUIREMENTS 3.1 Construction Type. New hangar facilities
24、will be of noncombustibleconstruction (UBC Type I or Type II) in accordance with MIL-HDBK-1008C. 3.2 Exit and Access Requirements. Means of egress from aircraft facilities will comply with NFPA I 01, Life SafeS Code. 3.3 Distance from Other Buildings. Clear space around hangars will be provided to r
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- COEETL111034851997FIREPROTECTIONFORHELICOPTERHANGARS 直升飞机 机库 防火 PDF

链接地址:http://www.mydoc123.com/p-620700.html