CEPT T TR 02-08 E-1986 Conductivity of Floors in Telecommunication Centres《电信中心地板传导性》.pdf
《CEPT T TR 02-08 E-1986 Conductivity of Floors in Telecommunication Centres《电信中心地板传导性》.pdf》由会员分享,可在线阅读,更多相关《CEPT T TR 02-08 E-1986 Conductivity of Floors in Telecommunication Centres《电信中心地板传导性》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、CEPT T/TR*OZ-OB*E 6 E 2326414 O010558 1 I 69 TtTR02-08 Page E 1 Recommendation T/TR 02-08 (Odense 1986) CONDUCTIVITY OF FLOORS IN TELECOMMUNICATION CENTRES Recommendation proposed by Working Group T/WG 12 “Transmission” (TR) Text revised of Recommendation adopted by the “Te2ecomnzuncatons” Commissio
2、n: “The European Conference of Posts In order to avoid measurement error due to contact resistance it may be necessary to insert conductive material, such as a wet electrode consisting of a colloidal suspension of graphite, between the floor covering material and the ground plane. Note 2: To compens
3、ate for unevenness in hard floor covering material it may be necessary to use a contact electrode with a soft underpadding. In this case a measurement should be made of the contact resistance of the underpadding using the same arrangements but without the floor covering material. The specific resist
4、ance of the underpadding should not exceed 10% of the minimum value specified in 4.1.1. Measurement of the resistance of the finished floor Measurement should be carried out not less than four weeks after the floor covering has been laid and should be repeated after a period of 12 months. Measuremen
5、t sites should be uniformly distributed over the surface of the floor and chosen to provide at least one measurement per square metre. The chosen measurement sites should be marked and at each site the floor covering should be cleaned to remove dirt, wax or other insulating layers without damaging t
6、he surface of the floor. The relative humidity within the room should not exceed 40% while measurements are being carried out (See Note). Note. It may be desirable to condition the room with regard to temperature and humidity for a defined period prior to carrying out the measurements. This question
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- CEPTTTR0208E1986CONDUCTIVITYOFFLOORSINTELECOMMUNICATIONCENTRES 电信 中心 地板 传导性 PDF

链接地址:http://www.mydoc123.com/p-593376.html