1、BRITISH STANDARD BS 6121-1:2005 Mechanical cable glands Part 1: Armour glands Requirements and test methods ICS 21.140 BS 6121-1:2005 This British Standard was published under the authority of the Standards Policy and Strategy Committee on 21 February 2005 BSI 21 February 2005 First published as BS
2、6121 February 1973 Second edition December 1987 Third edition January 1990 Fourth edition February 2005 The following BSI references relate to the work on this British Standard: Committee reference GEL/20/11/1 Draft for comment 98/263249 DC ISBN 0 580 45374 X Committees responsible for this British
3、Standard The preparation of this British Standard was entrusted by Technical Committee GEL/20, Electric cables, to Subcommittee GEL/20/11/1, Cable glands, upon which the following bodies were represented: BEAMA Ltd. Council for Electrical Equipment BEAMA Installation Ltd. British Approvals Service f
4、or Cables British Cables Association Gland Manufacturers Technical Committee Co-opted members Amendments issued since publication Amd. No. Date CommentsBS 6121-1:2005 BSI 21 February 2005 i Contents Page Committees responsible Inside front cover Foreword ii 1S c o p e 1 2 Normative references 1 3T e
5、 r m s a n d d e f i n i t i o n s 1 4 Requirements 1 5 Test samples, test conditions and test schedule 4 6 Marking and information 5 Table 1 Forces for cable retention test 2 Table 2 Test samples and test schedule 4BS 6121-1:2005 ii BSI 21 February 2005 Foreword This part of BS 6121 has been prepar
6、ed by Subcommittee GEL/20/11/1. Together with BS EN 50262:1999, it supersedes BS 6121-1:1989 which is withdrawn. This revision of BS 6121-1 covers only armour glands, which are outside the scope of BS EN 50262 because they do not provide a seal. This publication does not purport to include all the n
7、ecessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 5 and a back c
8、over. The BSI copyright notice displayed in this document indicates when the document was last issued.BS 6121-1:2005 BSI 21 February 2005 1 1 Scope This part of BS 6121 specifies performance requirements for armour glands for use with armoured cables. 2 Normative references The following referenced
9、documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. BS 21:1985 including Amendment 1:1990, Specification for pipe threads for
10、tubes and fittings where pressure-tight joints are made on the threads (metric dimensions). BS 31:1940 including Amendments 1:1965, 2:1967, 3:1969, 4:1970 and 5:1987, Specification for steel conduit and fittings for electrical wiring. BS EN 50262:1999 including Amendments 1:2001 and 2:2004, Cable gl
11、ands for electrical installations. BS EN 60423:1995, Conduits for electrical purposes Outside diameters of conduits for electrical installations and threads for conduits and fittings. BS EN 60529:1992 including Amendments 1:1993 and 2:2000, Degrees of protection provided by enclosures (IP code). BS
12、EN ISO 228-1:2003, Pipe threads where pressure tight joints are not made on the threads Part 1: Dimensions, tolerances and designation. BS ISO 965-3, ISO general purpose metric screw threads Tolerances Part 3: Deviations for constructional screw threads. ANSI/ASME B1.20.1:1983, Pipe threads, general
13、 purpose (inch). 3 Terms and definitions For the purposes of this part of BS 6121, the terms and definitions given in BS EN 50262:1999 and the following apply. 3.1 armour gland device which anchors the armour of an armoured cable at the cable entry point of an enclosure and provides an electrical co
14、nnection to the armour, but which does not provide a seal 4 Requirements 4.1 Construction 4.1.1 General Armour glands shall not have any internal sharp edges, which might cause damage to any cables, flexible cables or insulated conductors which pass through them in service. Those parts of an armour
15、gland that are used for tightening or for holding during installation shall be of hexagonal form. External projecting edges and corners of armour gland components shall be smooth and free from burrs.BS 6121-1:2005 2 BSI 21 February 2005 4.1.2 Entry thread The entry thread of metric armour glands in
16、sizes up to M75 shall be constructed in accordance with BS EN 60423:1995, Table 1. For sizes greater than M75 the entry thread shall be constructed in accordance with BS ISO 965-3 and with a thread pitch of 1.5 mm, 2 mm or 3 mm. The entry thread of non-metric armour glands shall be in accordance wit
17、h one of the following standards: BS 31:1940; BS EN ISO 228-1:2003; BS 21:1985; or shall be of one of the following types: NPSM conforming to ANSI/ASME B1.20.1:1983; NPT conforming to ANSI/ASME B1.20.1:1983. 4.2 Performance NOTE Armour glands specified in this standard are, in normal use, considered
18、 to be passive in respect of electromagnetic emission and immunity, so no requirements for these parameters are specified. 4.2.1 Mechanical performance NOTE The test sequence is given in 5.4. 4.2.1.1 Cable retention After testing in accordance with BS EN 50262:1999, 10.4.1, but using the force speci
19、fied in Table 1, the cable shall not have moved relative to either of the glands by more than 3 mm at the end of a 5 min test. Table 1 Forces for cable retention test 4.2.1.2 Resistance to impact After being assembled on a piece of cable having the smallest armour thickness in the range for which th
20、e gland is suitable, as stated in the information supplied by the manufacturer, and being subjected to the test specified in BS EN 50262:1999, 9.4, using the impact values applicable to the impact category that the gland is claimed to be, as stated by the manufacturer, the armour gland shall show no
21、 visible signs of damage. 4.2.1.3 Resistance to excess torque For armour glands that are assembled by being screwed together, after being assembled on a piece of cable having the largest armour thickness in the range for which the gland is suitable, as stated in the information supplied by the manuf
22、acturer, using a torque 1.5 times the installation torque given in the manufacturers instructions, the armour gland shall show no visible signs of damage. Cable diameter Force mm N 4 k8 6 4 0 8 k11 880 11 k16 1 280 16 k23 1 840 23 k31 2 480 31 k43 3 440 43 k55 4 400 55 k70 5 600 70 80D a a D is the
23、actual cable diameter in millimetres (mm).BS 6121-1:2005 BSI 21 February 2005 3 4.2.2 Electrical performance NOTE The test sequence is given in 5.4. 4.2.2.1 Equipotential bonding When armour glands which are claimed by the manufacturer to provide equipotential bonding are tested in accordance with B
24、S EN 50262:1999, 10.1, in no case shall the resistance exceed 0.1 7. 4.2.2.2 Electrical connection to metallic layer(s) of cable When armour glands are tested in accordance with BS EN 50262:1999, 10.2, the resistance between the gland and the armour shall not exceed 0.1 7. When armour glands which a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS612112005MECHANICALCABLEGLANDSARMOURGLANDSREQUIREMENTSANDTESTMETHODS 机械 电缆 密封 套铠装 试验 方法 要求 PDF

链接地址:http://www.mydoc123.com/p-545754.html