ATIS 0600001-2010 Electrical Protection Standards and Reference Documents Associated with Telecommunication Networks.pdf
《ATIS 0600001-2010 Electrical Protection Standards and Reference Documents Associated with Telecommunication Networks.pdf》由会员分享,可在线阅读,更多相关《ATIS 0600001-2010 Electrical Protection Standards and Reference Documents Associated with Telecommunication Networks.pdf(48页珍藏版)》请在麦多课文档分享上搜索。
1、 ATIS-0600001 Technical Report on - ELECTRICAL PROTECTION STANDARDS AND REFERENCE DOCUMENTS ASSOCIATED WITH TELECOMMUNICATION NETWORKS ATIS is the leading technical planning and standards development organization committed to the rapid development of global, market-driven standards for the informati
2、on, entertainment and communications industry. More than 200 companies actively formulate standards in ATIS 17 Committees, covering issues including: IPTV, Cloud Services, Energy Efficiency, IP-Based and Wireless Technologies, Quality of Service, Billing and Operational Support, Emergency Services,
3、Architectural Platforms and Emerging Networks. In addition, numerous Incubators, Focus and Exploratory Groups address evolving industry priorities including Smart Grid, Machine-to-Machine, Networked Car, IP Downloadable Security, Policy Management and Network Optimization. ATIS is the North American
4、 Organizational Partner for the 3rd Generation Partnership Project (3GPP), a member and major U.S. contributor to the International Telecommunication Union (ITU) Radio and Telecommunications Sectors, and a member of the Inter-American Telecommunication Commission (CITEL). ATIS is accredited by the A
5、merican National Standards Institute (ANSI). For more information, please visit . Notice of Disclaimer illustrates the necessity for care and thoroughness in implementation of grounding, bonding, and shielding; and provides supplemental information to assist in the solution of those problems and sit
6、uations not specifically addressed. In Volume II, Applications, the principles and theories, including RED/BLACK protection, are reduced to the practical steps and procedures which are to be followed in structural and facility development, electronic engineering, and in equipment development, These
7、applications should assure personnel equipment and structural safety, minimize electromagnetic interference (EMI) problems in the final operating system; and minimize susceptibility to and generation of undesirable emanations. The emphasis in Volume II goes beyond development to assembly and constru
8、ction, to installation and checkout, and to maintenance for long term use. MIL-STD-188-124B (1 February 1992), Grounding, Bonding And Shielding For Common Long Haul/Tactical Communication Systems Including Ground Based Communications-Electronics Facilities And Equipments. Objectives The objectives o
9、f this standard are to provide for the protection of personnel, equipments, buildings, and structures against the hazards posed by electrical power faults and lightning strikes. It also provides for the reduction of noise and electromagnetic interference caused by inadequate bonding, grounding and s
10、hielding of ground based military communications installations to acceptable performance levels. It shall be required that the grounding, bonding, and shielding system be engineered to be compatible with the supplemental requirements of the specific equipment or facility supporting these communicati
11、ons. 3. CENTRAL OFFICE: Telecommunication central offices and similar type facilities, such as Remote Switch Units, CEV, etc. are typically grounded following the guidelines in ATIS-0600313. This includes the external ground electrode and all the connections to it. The ground electrode provides the
12、means to equalize voltages. The equipment within these facilities are grounded and bonded following the recommendations in ATIS-0600333. ATIS-0600001 6Newer equipment in use in the central offices and similar facilities include electronic components that could be easily damaged by electrostatic disc
13、harges (ESD) if not handled properly. The test procedures in ATIS-0600308 are intended to provide the methods to determine the sensitivity of the equipment to ESD. Some critical central offices, either by their relative location or by the type of equipment within them, need to be hardened against th
14、e threats imposed by high-energy electromagnetic pulses. The guidelines to accomplish this level of protection are included in ATIS-0632000. 3.1 North American Standards ATIS-0600308.2008 (formerly known as T1.308), Central Office Equipment - Electrostatic Discharge Immunity Requirements. Abstract T
15、his standard provides electrostatic discharge (ESD) immunity criteria and test procedures for equipment assemblies intended for use in telephone central offices. It is intended to establish the capability of central office equipment to function normally after receiving typically encountered electros
16、tatic discharges. ATIS-0600313.2008 (formerly known as T1.313), Electrical Protection for Telecommunications Central Offices and Similar Type Facilities. Abstract Telecommunications central offices and similar type facilities are often subjected to disturbances from lightning and AC power line fault
17、s, either directly or indirectly, through the communications cables and AC power facilities that serve them. This standard provides the minimum electrical protection, grounding, and bonding criteria necessary to mitigate the disruptive and damaging effects of lightning and AC power faults. It is int
18、ended to serve as a guide for designers of such facilities in the application of electrical protection, grounding, and bonding as a function of the electrical environment. ATIS-0632000.2005 (formerly known as T1.320), Basic Protection Against HEMP for Central Offices and Similar Type Facilities (an
19、Above Baseline Standard). Abstract Telecommunications central offices and similar-type facilities may be subjected to the effects of a high-altitude electromagnetic pulse (HEMP). HEMP is a by-product of a high altitude (i.e., above the atmosphere) nuclear explosion. Such a pulse is capable of causin
20、g extensive upset and possibly disabling damage to unprotected telecommunications facilities within line-of-sight of the nuclear device detonation point(s). Central offices and similar-type facilities that incorporate the baseline electrical protection measures specified in T1.313-1996 provide a mea
21、sure of protection against the HEMP contingency. The purpose of this new above-baseline standard is to provide additional mitigation measures that will significantly increase the protection of critical components of the public telecommunications network in the event that it becomes exposed to the ef
22、fects of HEMP. This standard is intended as a guide for the designers of such facilities in the application of basic HEMP protection measures to those central offices and similar-type facilities that may be specifically designated under government contract to receive such measures. ATIS-0600333.2007
23、 (formerly known as T1.333), Grounding and Bonding of Telecommunications Equipment. Abstract This standard defines and describes the grounding and bonding topologies commonly used for the installation of network telecommunications equipment in central offices and similar type facilities. It addresse
24、s the baseline grounding and bonding requirements for telecommunications equipment, the associated DC and AC power facilities, and the interfacing of co-located telecommunications systems installed in central offices and similar facilities. In addition, the document defines a harmonized grounding an
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ATIS06000012010ELECTRICALPROTECTIONSTANDARDSANDREFERENCEDOCUMENTSASSOCIATEDWITHTELECOMMUNICATIONNETWORKSPDF

链接地址:http://www.mydoc123.com/p-541203.html