《ASTM F512-2006 Standard Specification for Smooth-Wall Poly(Vinyl Chloride) (PVC) Conduit and Fittings for Underground Installation《地下装置用平坦壁聚氯乙烯(PVC)导管及配件》.pdf》由会员分享,可在线阅读,更多相关《ASTM F512-2006 Standard Specification for Smooth-Wall Poly(Vinyl Chloride) (PVC) Conduit and Fittings for Underground Installation《地下装置用平坦壁聚氯乙烯(PVC)导管及配件》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 512 06An American National StandardStandard Specification forSmooth-Wall Poly(Vinyl Chloride) (PVC) Conduit andFittings for Underground Installation1This standard is issued under the fixed designation F 512; the number immediately following the designation indicates the year oforigina
2、l adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the requirements for smooth-wall poly(v
3、inyl chloride) conduit and fittings for undergroundcommunication and electrical power wire and cables.1.2 The values given in parentheses are for informationonly.1.3 The following safety hazards caveat pertains only to thetest method portion, Section 8, of this specification: Thisstandard does not p
4、urport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.2. Referenced Documents2.1 ASTM Standards:2D
5、618 Practice for Conditioning Plastics for TestingD 1600 Terminology for Abbreviated Terms Relating toPlasticsD 1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)Compounds and Chlorinated Poly(Vinyl Chloride)(CPVC) CompoundsD 2122 Test Method for Determining Dimensions of Ther-moplastic Pipe an
6、d FittingsD 2152 Test Method for Adequacy of Fusion of ExtrudedPoly(Vinyl Chloride) (PVC) Pipe and Molded Fittings byAcetone ImmersionD 2412 Test Method for Determination of External LoadingCharacteristics of Plastic Pipe by Parallel-Plate LoadingD 2444 Test Method for Determination of the Impact Re
7、-sistance of Thermoplastic Pipe and Fittings by Means of aTup (Falling Weight)D 2466 Specification for Poly(Vinyl Chloride) (PVC) Plas-tic Pipe Fittings, Schedule 40D 2564 Specification for Solvent Cements for Poly(VinylChloride) (PVC) Plastic Piping SystemsD 2855 Practice for Making Solvent-Cemente
8、d Joints withPoly(Vinyl Chloride) (PVC) Pipe and FittingsF 412 Terminology Relating to Plastic Piping Systems3. Terminology3.1 Definitions are in accordance with Terminology F 412and abbreviations are in accordance with Terminology D 1600,unless otherwise specified. The abbreviation for poly(vinylch
9、loride) is PVC.3.23.2.1 external recycled materialindustrial rework gener-ated by a different company manufacturing to this specifica-tion. Composition is known by the industrial source of thematerial.3.2.2 post-consumer recycled materialfinished goods thathave been purchased by the public, then ret
10、urned to industryand reprocessed into raw materials. Identity of finished goodsis known by the reprocessing company.3.2.3 certificate of compositiona certificate describing thecertain properties of an external recycled material of a postconsumer recycled material.3.2.4 composition disclosurea docume
11、nt describing theformulation of an external recycled material.4. Classification4.1 This specification covers five types of undergroundconduit. There are two having lesser pipe stiffness values,designed primarily for concrete encased burial (EB), and threewith greater pipe stiffness values, designed
12、primarily for directburial (DB). The complete designations follow:Type EB-20 Designed to be encased in concrete.Type EB-35 Designed to be encased in concrete.Type DB-60 Designed for direct burial without encasement in concrete.Type DB-100 Designed for direct burial without encasement in concrete.Typ
13、e DB-120 Designed for direct burial without encasement in concrete.4.2 This specification covers conduit with integral bells, orwith either separate or attached couplings.1This specification is under the jurisdiction of ASTM Committee F17 on PlasticPiping and is the direct responsibility of Subcommi
14、ttee F17.25 on Vinyl Based Pipe.Current edition approved May 1, 2006. Published June 2006. Originallyapproved in 1977. Last previous edition approved in 2001 as F 512 95(2001)e1.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org.
15、For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.3 This specification covers molded and fabricated fittingsintended
16、 for use with all types of conduit.5. Materials5.1 Basic MaterialsThe conduit shall be made of virginhomopolymer PVC compound having a cell classification of12254, 121643(with a minimum tensile strength of 4000 psi(28 MPa), or 12264(with a minimum tensile modulus of500 000 psi) as defined in Specifi
17、cation D 1784. Moldedfittings shall be made from PVC compound having a cellclassification of 12234 or 13343 as defined in SpecificationD 1784. Homopolymer PVC compounds must equal or exceedthe requirements of the listed cell classification numbers.5.2 Rework MaterialsRework material from the manufac
18、-turers own conduit or fittings production may be used by thesame manufacturer, provided that the conduit or fittings pro-duced meet all of the requirements of this specification.5.3 Recycled PVC MaterialsRecycled PVC materialsconforming to the cell classification of this specification maybe used pr
19、ovided they are clean and free from foreign materialsand provided that the conduit or fittings produced meet allrequirements of this specification.5.4 Solvent CementThe solvent cement shall meet therequirements of Specification D 2564.6. Requirements6.1 WorkmanshipThe conduit and fittings shall be h
20、omo-geneous throughout, and free from visible cracks, holes,foreign inclusions, or other injurious defects. The conduit andfittings shall be as uniform as is commercially practical incolor, opacity, density, and other physical properties.6.2 Dimensions:6.2.1 Dimensions shall be determined in accorda
21、nce withTest Method D 2122.6.2.2 The dimensions and tolerances of the conduit shall beas specified in Table 1.6.2.3 LengthsConduit shall be supplied in lengths of 20 or25 ft, or as otherwise agreed upon between the purchaser andthe seller. A length shall be considered to be the overall lengthof the
22、conduit, including integral bell, or coupling if attached,unless otherwise specified. Tolerance on length shall be 61 in.(625 mm).6.2.4 Integral Bell Dimensions:6.2.4.1 Two systems of fit for integral bells are in commonuse. Unless otherwise specified, the manufacturer may employeither of them.6.2.4
23、.2 Interference Fit SystemThe dimensions and toler-ances listed in Columns A and B of Table 1 in SpecificationD 2466 provide a satisfactory interference fit system betweenpipe and socket.6.2.4.3 Clearance Fit SystemThe dimensions and toler-ances listed in Table 2 of this specification provide a sati
24、sfac-tory clearance fit system.6.2.5 The wall thickness of integral bells and sweeps shallbe considered satisfactory if formed from conduit which meetsthe minimum requirements of this specification.6.2.6 Socket depths for integral bells shall conform to therequirements listed in Table 2.6.2.7 Integr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF5122006STANDARDSPECIFICATIONFORSMOOTHWALLPOLYVINYLCHLORIDEPVCCONDUITANDFITTINGSFORUNDERGROUNDINSTALLATION

链接地址:http://www.mydoc123.com/p-536810.html