ASTM F1793-1997(2010) Standard Specification for Automatic Shut-Off Valves (Also Known as Excess Flow Valves EFV) for Air Or Nitrogen Service《空气或氮服务用自动截流阀(也称为溢流阀)的标准规范》.pdf
《ASTM F1793-1997(2010) Standard Specification for Automatic Shut-Off Valves (Also Known as Excess Flow Valves EFV) for Air Or Nitrogen Service《空气或氮服务用自动截流阀(也称为溢流阀)的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1793-1997(2010) Standard Specification for Automatic Shut-Off Valves (Also Known as Excess Flow Valves EFV) for Air Or Nitrogen Service《空气或氮服务用自动截流阀(也称为溢流阀)的标准规范》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1793 97 (Reapproved 2010)An American National StandardStandard Specification forAutomatic Shut-Off Valves (Also Known as Excess FlowValves, EFV) for Air or Nitrogen Service1This standard is issued under the fixed designation F1793; the number immediately following the designation indic
2、ates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of
3、the Department of Defense.1. Scope1.1 This specification covers self-contained automatic shut-off valves (also known as excess flow valves) for air ornitrogen service. They are intended to be installed as safetydevices to quickly and automatically shut off flow under certainexcess flow conditions ca
4、used by a downstream failure orcasualty, such as a hose rupture.1.2 The values stated in this specification in inch-poundunits are to be regarded as the standard. The SI equivalentsshown in parentheses are provided for information only.2. Referenced Documents2.1 ASTM Standards:2F992 Specification fo
5、r Valve Label Plates2.2 American National Standards Institute (ANSI):3ANSI B1.1 Unified Screw Threads (UN and UNR ThreadForm)ANSI B1.20.1 Pipe Threads, General Purpose (Inch)ANSI B16.11 Forged Steel Fittings, Socket-Welding andThreadedANSI B16.25 Buttwelding EndsANSI B16.34 ValvesFlanged, Threaded,
6、and Welded End2.3 Military Standards and Specifications:4MIL-STD-167-1 Mechanical Vibrations of ShipboardEquipment (Type IEnvironmental and Type IIInternally Excited)MIL-STD-740-1 Airborne Sound Measurements and Ac-ceptance Criteria of Shipboard EquipmentMIL-S-901 Shock Tests, H.I. (High-Impact); Sh
7、ipboardMachinery Equipment and Systems, Requirements forMIL-F-1183 Fitting, Pipe, Cast Bronze, Silver-Brazing,General Specification for2.4 Government Drawings:4NAVAL SEA SYSTEMS COMMAND (NAVSEA)NAVSEA 803-1385884 Unions, Fittings and Adapters Buttand Socket Welding 6000 PSI, WOG, NPSNAVSEA 803-13859
8、43 Unions, Silver Brazing 3000 PSI,WOG, NPS, for UT InspectionNAVSEA 803-1385946 Unions, Bronze Silver Brazing,WOG for UT Inspection3. Terminology3.1 Definitions:3.1.1 automatic shut-off valveautomatic shut-off valvescovered by this specification trip shut in response to thepressure differential acr
9、oss the valve.3.1.2 bubble-tightno visible leakage over a 3-min periodusing either water submersion or the application of bubble fluidfor detection.3.1.3 external leakageleakage from the automatic shut-offvalve that escapes to atmosphere.3.1.4 hydrostatic shell test pressurethe hydrostatic shelltest
10、 pressure that the automatic shut-off valve is required towithstand without damage. Automatic shut-off valve operationis not required during application of shell test pressure, but itmust meet all performance requirements after the shell testpressure has been removed.3.1.5 pressure ratingsthe pressu
11、re ratings of the auto-matic shut-off valves shall be as defined in the documents listedin Table 1. The pressure ratings (also called pressure-temperature ratings) establish the maximum allowable working(service) pressures of a component (valve, end connections,and so forth) at various temperatures.
12、3.1.6 seat tightnessthe ability of the automatic shut-offvalve to prevent leakage from the valve-inlet to the valve-outlet.3.1.7 set pointa combination of inlet pressure and flow, atwhich the valve trips shut.1This specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marine Tech
13、nology and is the direct responsibility of Subcommittee F25.11 onMachinery and Piping Systems.Current edition approved May 1, 2010. Published June 2010. Originallyapproved in 1997. Last previous edition approved in 2004 as F1793 - 97 (2004).DOI: 10.1520/F1793-97R10.2For referenced ASTM standards, vi
14、sit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New Yor
15、k, NY 10036, http:/www.ansi.org.4Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.1.8 set point accura
16、cythe band of accuracy of theautomatic shut-off valve expressed as a range of flow rates at agiven inlet pressure, established by the following two points:3.1.8.1 DiscussionA combination of inlet pressure-flow,at or below which the automatic shut-off valve will not trip shut(valve will remain open)
17、regardless of influences such as springrelaxation, mechanical shock or vibration, and so forth.3.1.8.2 A combination of inlet pressure-flow, at or abovewhich the automatic shut-off valve will trip shut (valve will notremain open) regardless of influences tending to resist closuresuch as breakloose f
18、riction, corrosion, or sludge, and so forth.3.1.9 set-point rangethe range of set points over whichthe automatic shut-off valve can be adjusted. Expressed as arange of flow rates at a given inlet pressure.4. Classification4.1 Automatic shut-off valves shall be of the followingtypes, styles, sizes, p
19、ressure ratings, and end connections:4.1.1 Types:4.1.1.1 Type IValves that can be adjusted or repairedwithout removing the valve from pipe line.4.1.1.2 Type IIValves that cannot be adjusted or repairedwithout removing the valve from pipe line.4.1.2 Styles:4.1.2.1 Style 1Automatic Reset ConstructionT
20、hesevalves are designed to limit the flow of air or nitrogen uponclosure to a small predetermined level. These valves resetautomatically once the service line downstream is made air ornitrogen-tight and pressure is equalized across the valve.4.1.2.2 Style 2Manual Reset ConstructionThese valvesare de
21、signed to stop the flow of air or nitrogen upon closure.These valves must be manually reset.4.1.3 SizesAutomatic shut-off valves shall be of thefollowing NPS sizes:14 (13.5 mm),38 (17.2 mm),12 (21.3mm),34 (26.9 mm), 1 (33.7 mm), 114 (42.4 mm), 112 (48.3mm), and 2 (60.3 mm). Unless otherwise specifie
22、d in 5.0, thevalve inlet size shall be the same as the outlet size.4.1.4 Pressure RatingsAutomatic shut-off valves shallhave pressure rating(s) selected (see 3.1.5) from Table 1. Thepressure rating(s) selected shall be specified in Section 5. Theinlet and outlet pressure ratings of the automatic shu
23、t-off valveshall be the same for any given valve.4.1.5 End ConnectionsAutomatic shut-off valves shallhave end connections selected from those listed in Table 1 andspecified in Section 5.5. Ordering Information5.1 Ordering documentation for automatic shut-off valvesunder this specification shall incl
24、ude the following informa-tion, as required, to describe the equipment adequately:5.1.1 ASTM designation and year of issue,5.1.2 Valve type (see 4.1.1),5.1.3 Valve style (see 4.1.2),5.1.4 Valve size (see 4.1.3),5.1.5 Valve pressure rating (see 4.1.4),5.1.6 End connections (see 4.1.5),5.1.7 Valve inl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF179319972010STANDARDSPECIFICATIONFORAUTOMATICSHUTOFFVALVESALSOKNOWNASEXCESSFLOWVALVESEFVFORAIRORNITROGENSERVICE

链接地址:http://www.mydoc123.com/p-535674.html