1、Designation: F 1116 03 (Reapproved 2008)Standard Test Method forDetermining Dielectric Strength of Dielectric Footwear1This standard is issued under the fixed designation F 1116; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers testing to determine the “Di-electric Strength” of dielectric overfoot and overshoe f
3、ootwear.Testing is done over the maximum possible area of thedielectric footwear without permitting flashover between elec-trodes.1.2 The use and maintenance of dielectric footwear isbeyond the scope of this test method.1.3 This standard does not purport to address all of thesafety concerns, if any,
4、 associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. Specific hazardstatements appear in 5.2.2. Referenced Documents2.1 ASTM Standards:2D 149 Test
5、Method for Dielectric Breakdown Voltage andDielectric Strength of Solid Electrical Insulating Materialsat Commercial Power FrequenciesF 1117 Specification for Dielectric Footwear3. Terminology3.1 Descriptions of Terms Specific to This Standard:3.1.1 useras used in 1.3, the entity employing the actua
6、lworker utilizing the equipment; if no separate employer, thenthe individual.3.1.2 overfoot footwearfootwear designed to be worndirectly over the feet as the only source of foot covering.3.1.3 overshoe footwearfootwear designed to be wornover existing footwear.4. Significance and Use4.1 Electrical c
7、ontact injuries to workers may involve acurrent path through the feet of the worker. The footwearcovered by this specification is dielectrically rated to provideadditional insulation and isolation to the wearer. This testmethod will determine that dielectric footwear has dielectricintegrity at the t
8、ime of the test.5. Apparatus5.1 Electrical Test Criteria:5.1.1 Test ProcedureThe footwear shall be immersed inwater or other conducting media to a depth where the flashoverclearance is consistent with the proof test voltage as listed inTable 1. Since the water or other conducting media inside thefoo
9、twear forms one test electrode and the water or the otherconducting media in the container outside the footwear formsthe other electrode, 152 mm or 6 in. of clearance betweenelectrodes consists of 76 mm or 3 in. of clearance from the topof the footwear to the top of the water or other conductingmedi
10、a both inside and outside of the footwear. Water isrecommended as the medium for the electrodes to ensurecomplete coverage of the surfaces of the footwear. Water maywick up the inner lining on certain brands of footwear. Toovercome the wicking effect care needs to be taken to keep theinner area abov
11、e the water dry and conduct the tests promptlyafter placing the water inside the footwear. The water or otherconducting media inside the footwear forms one test electrodeand shall be connected to one terminal of the voltage source bymeans of a metal chain or sliding rod that dips into theelectode. T
12、he water or other conducting media in the containeroutside the footwear forms the other electrode and shall beconnected directly to the other terminal of the voltage source.Due to the weight of water or other types of electrode media,support racks are needed to secure footwear being tested. Themaxim
13、um protective area of the footwear shall be tested. Caremust be taken to thoroughly dry the inside of the footwearfollowing the test and prior to storage. See Fig. 1 and Fig. 2 fortypical test arrangements for dielectric test of rubbers and bootsusing water electrodes.NOTE 1Water used as electrodes
14、should have a minimum conduc-tance of 0.25 mho.5.2 PrecautionsIt is recommended that the test apparatusbe designed to afford the operator full protection in perfor-mance of his duties. Reliable means of de-energizing andgrounding the high-voltage circuit shall be provided. It isparticularly importan
15、t to incorporate a positive means of1This test method is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommittee F18.15 on Worker Personal Equipment.Current edition approved April 1, 2008. Published April 2008. Origin
16、allyapproved in 1988. Last previous edition approved in 20038 as F 111603.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF111620032008STANDARDTESTMETHODFORDETERMININGDIELECTRICSTRENGTHOFDIELECTRICFOOTWEAR 测定 绝缘 绝缘性 标准

链接地址:http://www.mydoc123.com/p-534216.html