ASTM E814-2008 346 Standard Test Method for Fire Tests of Through-Penetration Fire Stops.pdf
《ASTM E814-2008 346 Standard Test Method for Fire Tests of Through-Penetration Fire Stops.pdf》由会员分享,可在线阅读,更多相关《ASTM E814-2008 346 Standard Test Method for Fire Tests of Through-Penetration Fire Stops.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 814 08An American National StandardStandard Test Method forFire Tests of Through-Penetration Fire Stops1This standard is issued under the fixed designation E 814; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.INTRODUCTIONCharacteristically fire spread
3、s from one building compartment to another by the collapse of abarrier, or by openings through which flames or hot gases may pass, or by transfer of sufficient heatto ignite combustibles beyond the barrier. Test Methods E119describe the method to be used tomeasure the fire-resistive performance of t
4、hese barriers.However, various techniques of providing for the distribution of services within a structuresometimes require that openings be made in fire-resistive walls and floors to allow the passage of suchpenetrating items as cables, conduits, pipes, trays, and ducts through to the adjacent comp
5、artment.Fire-stop material is installed into these openings to resist the spread of fire.The performance of through-penetration fire stops should be measured and specified according toa common standard that describes the method of fire exposure and rating criteria.1. Scope1.1 This test method is app
6、licable to through-penetrationfire stops of various materials and construction. Fire stops areintended for use in openings in fire-resistive walls and floorsthat are evaluated in accordance with Test Methods E119.1.2 Tests conducted in conformance with this test methodrecord fire-stop performance du
7、ring the test exposure; but suchtests shall not be construed to determine suitability of the firestop for use after test exposure.1.3 This test method also measures the resistance of firestops to an external force stimulated by a hose stream.However, this test method shall not be construed as determ
8、in-ing the performance of the fire stop during actual fire condi-tions when subjected to forces such as failure of cable supportsystems and falling debris.1.4 The intent of this test method is to develop data to assistothers in determining the suitability of the fire stops for usewhere fire resistan
9、ce is required.1.5 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard is used to measure and describe theresponse of mater
10、ials, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire-hazard or fire-riskassessment of materials, products, or assemblies under actualfire conditions.1.7 This standard does not purport to address all of thesafety c
11、oncerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.8 The text of this standard references notes and footnoteswhich provide expla
12、natory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredrequirements of the standard.2. Referenced Documents2.1 ASTM Standards:2E119 Test Methods for Fire Tests of Building Constructionand MaterialsE 2226 Practice for Application of Hose Stream3. Term
13、inology3.1 Definition:3.1.1 fire stopa through-penetration fire stop is a specificconstruction consisting of the materials that fill the openingaround penetrating items such as cables, cable trays, conduits,ducts, and pipes and their means of support through the wall orfloor opening to prevent sprea
14、d of fire.1This method is under the jurisdiction of Committee E05 on Fire Standards andis the direct responsibility of Subcommittee E05.11 on Construction Assemblies.Current edition approved May 1, 2008. Published June 2008. Originallyapproved in 1981. Last previous edition approved in 2006 as E 814
15、 06.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO
16、Box C700, West Conshohocken, PA 19428-2959, United States.3.2 Definitions of Terms Specific to This Standard:3.2.1 test specimenthe penetrating item or items and thematerials or devices, or both, that seal the opening in thefirestop system being tested.3.2.2 test assemblythe wall or floor that is pa
17、rt of thefirestop system being tested into which the test specimen(s) is(are) mounted or installed.4. Summary of Test Method4.1 This method of testing through-penetration firestopsystems exposes firestop systems to a standard temperature-time fire, and to a subsequent application of a hose stream.4.
18、2 Ratings are established on the basis of the period ofresistance to the fire exposure, prior to the first development ofthrough openings, flaming on the unexposed surface, limitingthermal transmission criterion, and acceptable performanceunder application of a hose stream.5. Significance and Use5.1
19、 This test method is used to determine the performanceof a firestop system with respect to exposure to a standardtime-temperature fire test and a hose stream test. The perfor-mance of a firestop system is dependent upon the specificassembly of materials tested including the number, type, andsize of
20、penetrations and the floors or walls in which it isinstalled.5.2 Two ratings are established for each firestop system. AnF rating is based upon flame occurrence on the unexposedsurface, while the T rating is based upon the temperature rise aswell as flame occurrence on the unexposed side of the fire
21、stopsystem. These ratings, together with detailed performance datasuch as the location of through-openings and temperatures ofpenetrating items are intended to be one factor in assessingperformance of firestop systems.6. Control of Fire Tests6.1 Time-Temperature CurveThe fire environment withinthe f
22、urnace shall be in accordance with the standard time-temperature curve shown in Fig. 1. The points on the curve thatdetermine its character are:Ambient at 0 min1000F (538C) at 5 min1300F (704C) at 10 min1550F (843C) at 30 min1700F (927C) at 60 min1850F (1010C) at 120 min2000F (1093C) at 240 min2300F
23、 (1260C) at 480 min or over6.2 Furnace Temperatures:6.2.1 The temperature fixed by the curve shall be theaverage temperature obtained from the readings of thermo-couples symmetrically disposed and distributed within the testfurnace to show the temperature near all parts of the assembly.Use a minimum
24、 of three thermocouples, with not fewer thanfive thermocouples per 100 ft2(9.29 m2) of floor surface, andnot fewer than nine thermocouples per 100 ft2of wall specimensurface.6.2.2 Enclose the thermocouples in sealed protection tubesof such materials and dimensions that the time constant of theprotec
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME8142008346STANDARDTESTMETHODFORFIRETESTSOFTHROUGHPENETRATIONFIRESTOPSPDF

链接地址:http://www.mydoc123.com/p-533584.html