ASTM D6630-2008 402 Standard Guide for Low Slope Insulated Roof Membrane Assembly Performance《低坡度绝热屋顶薄膜装配性能的标准指南》.pdf
《ASTM D6630-2008 402 Standard Guide for Low Slope Insulated Roof Membrane Assembly Performance《低坡度绝热屋顶薄膜装配性能的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6630-2008 402 Standard Guide for Low Slope Insulated Roof Membrane Assembly Performance《低坡度绝热屋顶薄膜装配性能的标准指南》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 6630 08Standard Guide forLow Slope Insulated Roof Membrane AssemblyPerformance1This standard is issued under the fixed designation D 6630; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A
2、number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide lists test methods intended to establish aminimum level of performance for insulated roof membraneassemblies, and lists pert
3、inent design guidelines and installa-tion methods in a unified manner. Material tests and evalua-tions are included with and without roof insulation.1.2 It is not possible to establish a precise correlationbetween laboratory tests on roof assemblies and natural weath-ering due to variations in geogr
4、aphical climate, design, mate-rial and installation.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of
5、 regulatory requirements prior to use.2. Referenced Documents2.1 ASTM Standards:2D95 Test Method for Water in Petroleum Products andBituminous Materials by DistillationD 2523 Practice for Testing Load-Strain Properties of Roof-ing MembranesD 4434 Specification for Poly(Vinyl Chloride) Sheet Roof-ing
6、D 4637 Specification for EPDM Sheet Used In Single-PlyRoof MembraneD 4798 Practice for Accelerated Weathering Test Condi-tions and Procedures for Bituminous Materials (Xenon-Arc Method)D 4799 Practice for Accelerated Weathering Test Condi-tions and Procedures for Bituminous Materials (Fluores-cent U
7、V, Water Spray, and Condensation Method)D 5019 Specification for Reinforced CSM (Chlorosul-fonated Polyethylene) Sheet Used in Single-Ply RoofMembraneD 5147 Test Methods for Sampling and Testing ModifiedBituminous Sheet MaterialD 5601 Test Method for Tearing Resistance of Roofing andWaterproofing Ma
8、terials and Membranes3D 5602 Test Method for Static Puncture Resistance ofRoofing Membrane SpecimensD 5635 Test Method for Dynamic Puncture Resistance ofRoofing Membrane SpecimensD 5849 Test Method for Evaluating Resistance of ModifiedBituminous Roofing Membrane to Cyclic Fatigue (JointDisplacement)
9、E 96/E 96M Test Methods for Water Vapor Transmission ofMaterials2.2 ASCE Standard:ASCE-7 Minimum Design Loads for Buildings and OtherStructures42.3 ANSI/SPRI Standard:ANSI/SPRI RP-4 Wind Design Guide for Ballasted SinglePly Roof Systems53. Terminology3.1 roof assembliesthe weathering or waterproofin
10、g ma-terial, whether film, flexible membrane, semi-flexible mem-brane, factory or field manufactured; the underlying substrateincluding insulation (if used) above or below the membrane, orboth; supporting deck structure and method of attachment ofthe entire assembly. Low slope roof assemblies may be
11、 up to25 % slope. Some roof assemblies may accommodate higherslopes.3.2 performancethe ability of the roof system as de-signed, manufactured, and installed to provide adequate levelsof expected service life in terms of watertightness, thermal1This guide is under the jurisdiction of ASTM Committee D0
12、8 on Roofing andWaterproofing and is the direct responsibility of Subcommittee D08.20 on RoofingMembrane Systems.Current edition approved March 15, 2008. Published July 2008. Originallyapproved in 2001. Last previous edition approved in 2001 as D 6630 01.2For referenced ASTM standards, visit the AST
13、M website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn.4Available from American Society of Civil Engineers (ASCE), 1801 AlexanderBell Dr., Reston, VA
14、20191, http:/www.asce.org.5Available from American National Standards Institute and Single Ply RoofingInstitute, 200 Reservoir St., Suite 309A, Needham, MA 02194.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.protection, and condens
15、ation control, while being maintain-able. Live loading of the roof system may also occur.4. Significance and Use4.1 Aroof assembly must work as a system.Any componentof the roof assembly demonstrating an inherent weakness orinability to perform will diminish the roof system performanceand service li
16、fe expected. This guide lists minimum perfor-mance attributes required of low slope roof assemblies. Prod-ucts not previously used as roof membrane materials requireadditional tests beyond the scope of this document. This guideis not intended for use on in-service roofing materials. Roofmembranes an
17、d other components should conform to ASTMproduct standards, if available.5. Roof Design Classifications5.1 Type of Construction:Class ConstructionI New NewII Replace Remove existing roof membrane (and existing insulation, ifnecessary) and replaceIII Re-cover Re-cover existing roof membrane5.2 Method
18、s of Attachment:Roof Membrane Configuration Method of AttachmentMethod A Adhered Uses a variety of adhesives includinghot and cold applied.Method B Loose laid ballasted Uses aggregate ballast or pavers.Structure needs capacity to carry bal-last dead load.Method LD Loose laid air pressureequalization
19、 valvesUses air pressure equalization valvewith loose laid membrane tightly sealedat edge. Needs airtight deck.Method M Partially attached/mechanically fastenedUses a variety of fasteners and attach-ment schemes that anchor membraneto roof deck for uplift resistance.Method P Protected membrane Uses
20、aggregate ballast, pavers, orother dead load devices for wind upliftresistance of extruded polystyrene.6. Roof Material Attributes6.1 The roof membrane and insulated roof system shall betested according to the procedures in Table 1. In addition, theroof membrane shall meet specific test requirements
21、 whereidentified.7. Design of Roofing Assembly7.1 The roofing system may consist of the following func-tional layers from the bottom to the top:7.1.1 Structural deck;7.1.2 Air retarder;7.1.3 Vapor retarder;7.1.4 Thermal insulation; and7.1.5 Roofing membrane7.2 The following paragraphs list the minim
22、um designrequirements for each functional layer of the roof assembly.These may exceed the requirements of the local building code.7.2.1 Structural DeckThe structural deck shall have thecapacity to support the full design load, including dead load,live loads, and environmental loads anticipated or ma
23、ndated bycode. The dead load of the roof system shall be included as partof the design load. Deck deflection should be limited to L/240under full design load. Ponding due to deck deflection shouldnot occur. Provide overflow drains or scuppers when interiordrains are used. The live load capacity shal
24、l not be less than 98Kg/m2(20 psf) and should have adequate capacity to resistconstruction loads.7.2.2 Air RetarderAir retarders are used to retard the flowof air from the interior into the roof system. When air retardersare used properly, they reduce the effects from wind on someroofing systems. Wi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD66302008402STANDARDGUIDEFORLOWSLOPEINSULATEDROOFMEMBRANEASSEMBLYPERFORMANCE 坡度 绝热 屋顶 薄膜 装配 性能 标准

链接地址:http://www.mydoc123.com/p-523100.html