1、Designation: D5305 97 (Reapproved 2007)D5305 12Standard Test Method forDetermination of Ethyl Mercaptan in LP-Gas Vapor1This standard is issued under the fixed designation D5305; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the
2、year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope Scope*1.1 This test method covers a rapid and simple procedure using length of stain tubes for field measurement
3、of ethyl mercaptanin the vapor phase of LP-gas systems. Although length-of-stain tubes are available to detect ethyl mercaptan concentrations in therange of 0.5 to 120 parts per million volume (ppmv), this test method is specifically applicable to systems containing 5 ppmv ormore of ethyl mercaptan
4、in LP-gas vapors.NOTE 1A chromatographic technique can be used for more precise, quantitative determination of ethyl mercaptan in LP-gas.1.2 The values stated in SI (metric) units are to be regarded as the standard. The values in parentheses are for information only.1.3 This standard does not purpor
5、t to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2. Referenced Documents2.1 NFPA Standard:2NFPA 58
6、Standard for the Storage and Handling of Liquefied Petroleum Gases3. Summary of Test Method3.1 Using a manually-operated vacuum pump, a sample of LP-gas from the vapor space of an LP-gas cylinder, storage tank orother closed containment system is drawn through a detector tube made specifically for d
7、etection of mercaptans.The length of stain(color change) produced in the detector tube when exposed to a measured volume of sample is directly proportional to the amountof ethyl mercaptan present in the sample being tested. The length of stain produced in the detector tube is converted toconcentrati
8、on, in parts per million volume (ppmv), by comparison with a calibration scale provided by the manufacturer of the staintubes.tube.4. Significance and Use4.1 LP-gas is colorless and odorless, and not detectable by normal human senses. To provide an olfactory warning in the eventof a leak, LP-gas int
9、ended for domestic or commercial fuel use is intentionally odorized so as to be readily detectable well belowflammable or suffocating concentration levels of LP-gas in air. (See Appendix X1.) The most common odorant for LP-gas is ethylmercaptan. The field use of this test method will rapidly determi
10、ne the presence and concentration of ethyl mercaptan in LP-gasvapor without the necessity for complex laboratory equipment.5. Interferences5.1 Detector tubes can be subject to interferences from materials other than the target substance. Methyl mercaptan will likelyinterfere with tubes designed to m
11、easure ethyl mercaptan. Because of different detection chemistry by different manufacturers,interferences can vary. Consult the manufacturers instructions for specific interference information and observe any instructionsgiven.5.2 Propylene (propene) will cause an interfering (gray) discoloration wi
12、th some tubes designed for ethyl mercaptan. LP-gasfrom natural gas sources usually does not contain propylene (propene). However, LP-gas produced in refinery operations oftendoes contain propylene (propene). Detector tubes calibrated for t-butyl mercaptan eliminate this interference, and should be u
13、sed1 This test method is under the jurisdiction of ASTM Committee D02 on Petroleum Products and Lubricants and is the direct responsibility of Subcommittee D02.H0 onLiquefied Petroleum Gas.Current edition approved May 1, 2007Nov. 1, 2012. Published June 2007February 2013. Originally approved in 1992
14、. Last previous edition approved in 20022007 asD5305 97D530597(2007). (2002). DOI: 10.1520/D5305-97R07.10.1520/D5305-12.2 Available from National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, MA 02169-7471, http:/www.nfpa.org.This document is not an ASTM standard and is intended o
15、nly to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current ver
16、sionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1if the presence of propylene (propene)
17、 is suspected. Some tubes designed for measurement of t-butyl mercaptan are calibrated inmilligrams per cubic metre (mg/m3) and should be converted to ppmv ethyl mercaptan as shown in Annex A1.5.3 The validity of this test method depends on the ethyl mercaptan in the LP-gas vapor phase being in equi
18、librium with ethylmercaptan in the LP-gas liquid phase. If LP-gas vapor has recently been vented, or if a significant volume of vapor relative to thetotal volume of the vapor phase is vented during this test procedure, the concentration of ethyl mercaptan in the vapor phase samplecan be lower than t
19、he equilibrium concentration.6. Apparatus6.1 PumpAmanually-operated vacuum pump, capable of drawing 100 mLper stroke of sample through the detector tube withan accuracy of 62.0 mL.6.2 Detector TubesSealed tubes, made of glass with break-off tips sized to fit the orifice of the pump used (tubes and p
20、umpsfrom different manufacturers shouldshall not be interchanged). The tube used mustshall be appropriate for the determination ofethyl mercaptan and mustshall produce a distinct color change when exposed to a sample of LP-gas containing ethyl mercaptan.Any substance known to interfere mustshall be
21、listed in instructions accompanying the tubes (see 5.2).Acalibration scale or othermarkings referenced to a scale mustshall be etched directly on the tube to allow direct interpretation of ethyl mercaptanconcentration.36.2.1 Detector tubes mustshould be calibrated for a tube temperature of approxima
22、tely 20C and normal atmospheric pressure.Shelf life of the detector tubes mustshall be a minimum of two years when stored according to the manufacturersrecommendations.6.2.2 Detector tubes and pumps form an integrally designed unit, that must are to be used as a unit. Each manufacturer calibratesdet
23、ector tubes to match the flow characteristics of its pump, and the use of one brand of tube with another brand of pump will giveunreliable results.6.3 Gas Sampling ChamberA suitable container can be devised from a half-litre polyethylene bottle (seeAny container of amaterial that is not Fig. 1). A 6
24、 mm outside diameter polyethylene tubing sealed into the bottle and discharging near the bottomof the bottle provides for flow into the sampling container. A 12 mm hole cut into the cap of the bottle provides both access forthe detector tube and a vent for the excess gas flow.reactive with mercaptan
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD53052012STANDARDTESTMETHODFORDETERMINATIONOFETHYLMERCAPTANINLPGASVAPOR 测定 液化 石油 LP 蒸气 硫醇 标准 试验 方法

链接地址:http://www.mydoc123.com/p-519429.html