1、Designation: D4276 02 (Reapproved 2012)Standard Practice forConfined Area Entry1This standard is issued under the fixed designation D4276; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in paren
2、theses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers recognized procedures necessary toprotect the health and safety of workers required to enterconfined spaces. These procedures are
3、 particularly applicableto entry into the confined areas associated with the use ofhalogenated organic solvents.1.2 Confined areas addressed in this practice include, but arenot limited to: vapor degreasers, cold cleaning tanks, storagevessels, tank cars and trucks, van trailers, ships or barges, pi
4、tsor sumps, and unventilated rooms.1.3 This practice does not necessarily address entry into allconfined spaces nor does it address the decision strategyinvolved in requiring such entry.1.4 Although this practice describes specific safety steps tobe taken for entry into confined spaces, it is not in
5、tended topreclude the use of any additional measures that may bedeemed necessary for a particular situation.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety
6、and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:CFR 1910.146 U.S. Department of Labor, OccupationalSafety and Health Standards, Permit-Required ConfinedSpaces3. Summary of Practice3.1 Confined area entry refers to
7、 the entering of any tank,vessel, sump, pit, duct, tank car, tank truck, van trailer, orenclosed space in which there has been, or may have beenchemicals, chemical vapors, or a lack of ventilation.4. Significance and Use4.1 Vapor inhalation is the primary hazard encountered inthe use of chlorinated
8、solvents. The greatest potential for overexposure to these solvent vapors occurs where the employee isexposed to the high concentrations of vapor that may be foundin confined areas. The seriousness of this hazard is oftenunderestimated by those performing this type of work.4.2 This practice is desig
9、ned for use by employers indeveloping their own specific standards for vessel or confinedarea entry.4.3 Many of these areas are considered as permit-requiredconfined spaces as defined by OSHA (29 CFR 1910.146). Thedetermination of the applicability of these requirements is theresponsibility of the u
10、ser.4.4 This practice represents the minimum requirements forentry into any confined area containing halogenated solvents.4.5 This practice does not address all of the requirementscontained in the OSHAconfined spaces standard. Developmentand implementation of training programs, recordkeeping, andoth
11、er additional requirements of the OSHA standard are theresponsibility of the user.5. Procedure5.1 All personnel working in confined areas must be prop-erly trained in safe entry and rescue procedures. They musthave a working knowledge and understanding of the hazardsthat may exist.5.2 Entry PermitEn
12、try into confined areas must be bywritten entry permit, issued by the responsible supervisor orother qualified person. The purpose of the entry permit is toensure that a checklist of precautions has been reviewed priorto entry. This permit is an authorization, and approval inwriting certifying that
13、all existing hazards have been evaluatedand necessary protective measures have been taken to ensurethe safety of the worker. The permit should be valid for alimited time only, (usually an 8 or 10-h shift) and issuance ofa new permit required in the event of any job interruption orany indication of c
14、hanges in job conditions. Issuance of theentry permit must address all of the following considerations.5.3 Area Preparation:1This practice is under the jurisdiction of ASTM Committee D26 on Haloge-nated Organic Solvents and Fire Extinguishing Agents and is the direct responsi-bility of Subcommittee
15、D26.05 on Industrial Hygiene.Current edition approved Sept. 1, 2012. Published November 2012. Originallyapproved in 1984. Last previous edition approved in 2007 as D4276 02(2007).DOI: 10.1520/D4276-02R12.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-29
16、59. United States15.3.1 IsolationAll process lines exiting or entering theconfined area must be disconnected, capped off, and blinded.Closing of valves alone is not adequate protection.5.3.2 LockoutPumps or any other mechanical or electricalequipment (particularly conveyors), connected to the confin
17、edarea, are to be locked out by locking the main electrical switchin the “OFF” position.5.3.3 CleaningThe space must be cleared, flushed, orpurged of hazardous materials to the extent practical. Thisshould be followed, where practical, by cleaning with water,steam, or other suitable materials.5.3.4
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD427620022012STANDARDPRACTICEFORCONFINEDAREAENTRY 封闭 入口 标准 实施 规程 PDF

链接地址:http://www.mydoc123.com/p-516689.html