《ASTM D3612-2002(2009) Standard Test Method for Analysis of Gases Dissolved in Electrical Insulating Oil by Gas Chromatography《用气相色谱分离法分析电绝缘油中溶解的气体成分的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D3612-2002(2009) Standard Test Method for Analysis of Gases Dissolved in Electrical Insulating Oil by Gas Chromatography《用气相色谱分离法分析电绝缘油中溶解的气体成分的标准试验方法》.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 3612 02 (Reapproved 2009)Standard Test Method forAnalysis of Gases Dissolved in Electrical Insulating Oil byGas Chromatography1This standard is issued under the fixed designation D 3612; the number immediately following the designation indicates the year oforiginal adoption or, in the
2、 case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers three procedures for extractionand measurement of gases dissolv
3、ed in electrical insulating oilhaving a viscosity of 20 cSt (100 SUS) or less at 40C (104F),and the identification and determination of the individualcomponent gases extracted. Other methods have been used toperform this analysis.1.2 The individual component gases that may be identifiedand determine
4、d include:HydrogenH2OxygenO2NitrogenN2Carbon monoxideCOCarbon dioxideCO2MethaneCH4EthaneC2H6EthyleneC2H4AcetyleneC2H2PropaneC3H8PropyleneC3H61.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard
5、to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificwarning statements see 6.1.8, 30.2.2 and 30.3.1.2. Referenced Documents2.1 ASTM Standards:D 2140 Practice for Calculating Carbon-Type Compositionof Insulating Oi
6、ls of Petroleum OriginD 2300 Test Method for Gassing of Electrical InsulatingLiquids Under Electrical Stress and Ionization (ModifiedPirelli Method)D 2779 Test Method for Estimation of Solubility of Gasesin Petroleum LiquidsD 2780 Test Method for Solubility of Fixed Gases inLiquidsD 3613 Practice fo
7、r Sampling Insulating Liquids for GasAnalysis and Determination of Water Content2D 4051 Practice for Preparation of Low-Pressure GasBlendsE 260 Practice for Packed Column Gas Chromatography2.2 IEEE Standard:C 57.104 Guide for the Interpretation of Gases Generated inOil-Immersed Transformers32.3 IEC
8、Standard:Publication No. 567 Guide for the Sampling of Gases andof Oil from Oil-Filled Electrical Equipment and for theAnalysis of Free and Dissolved Gases43. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 gas content of oil by volumein Method A, the totalvolume of gases, correc
9、ted to 760 torr (101.325 kPa) and 0C,contained in a given volume of oil, expressed as a percentage.In Methods B and C, the sum of the individual gas concentra-tions corrected to 760 torr (101.325 kPa) and 0C, expressed inpercent or parts per million.3.1.2 headspacea volume of gas phase in contact wi
10、th avolume of oil in a closed vessel. The vessel is a headspace vialof 20-mL nominal capacity.3.1.2.1 DiscussionOther vessel volumes may also beused, but the analytical performance may be somewhat differ-ent than that specified in Method C.3.1.3 parts per million (ppm) by volume of (specific gas) in
11、oilthe volume of that gas corrected to 760 torr (101.325 kPa)and 0C, contained in 106volume of oil.3.1.4 sparging, vagitating the liquid sample using a gas tostrip other gases free.1This test method is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids and Gases and is the
12、direct responsibility of Subcom-mittee D27.03 on Analytical Tests.Current edition approved May 15, 2009. Published June 2009. Originallyapproved in 1977. Last previous edition approved in 2002 as D 3612 02 (2009).2Withdrawn. The last approved version of this historical standard is referencedon www.a
13、stm.org.3Available from IEEE, 345 E. 47th St., New York, NY 10017.4Available from International Electrotechnical Commission (IEC), 3 rue deVaremb, Case postale 131, CH-1211, Geneva 20, Switzerland, http:/www.iec.ch1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken,
14、PA 19428-2959, United States.3.1.5 volume concentration of (specific gas) in the gassamplethe volume of the specific gas contained in a givenvolume of the gas sample at the same temperature and pressure(as the measured total volume), expressed either as a percent-age or in parts per million.4. Summa
15、ry of Test Method4.1 Method ADissolved gases are extracted from a sampleof oil by introduction of the oil sample into a pre-evacuatedknown volume. The evolved gases are compressed to atmo-spheric pressure and the total volume measured.4.2 Method BDissolved gases are extracted from a sampleof oil by
16、sparging the oil with the carrier gas on a strippercolumn containing a high surface area bead.4.3 Method CMethod C consists of bringing an oil samplein contact with a gas phase (headspace) in a closed vesselpurged with argon. The dissolved gases contained in the oil arethen equilibrated in the two p
17、hases in contact under controlledconditions (in accordance with Henrys law). At equilibrium,the headspace is overpressurized with argon and then thecontent of a loop is filled by the depressurization of theheadspace against the ambient atmospheric pressure. The gasescontained in the loop are then in
18、troduced into a gas chromato-graph.4.4 There may be some differences in the limits of detectionand precision and bias between Methods A, B, and C forvarious gases.4.5 Aportion of the extracted gases (MethodA) or all of theextracted gases (Method B) or a portion of the headspace gases(Method C) is in
19、troduced into a gas chromatograph. Calibra-tion curves are used in Method C to establish the concentrationof each species. The composition of the sample is calculatedfrom its chromatogram by comparing the area of the peak ofeach component with the area of the peak of the samecomponent on a reference
20、 chromatogram made on a standardmixture of known composition.5. Significance and Use5.1 Oil and oil-immersed electrical insulation materials maydecompose under the influence of thermal and electricalstresses, and in doing so, generate gaseous decompositionproducts of varying composition which dissol
21、ve in the oil. Thenature and amount of the individual component gases that maybe recovered and analyzed may be indicative of the type anddegree of the abnormality responsible for the gas generation.The rate of gas generation and changes in concentration ofspecific gases over time are also used to ev
22、aluate the conditionof the electric apparatus.NOTE 1Guidelines for the interpretation of gas-in-oil data are given inIEEE C 57.104.6. Apparatus6.1 Apparatus5of the type shown in Fig. 1 or Fig. 2 issuitable for use with up to 50-mL samples of oil and consistsof the following components:NOTE 2This sam
23、ple size has been found to be sufficient for most oils.However, oil that has had only limited exposure to air may contain muchsmaller amounts of nitrogen and oxygen. For these oils it may be desirableto increase the size of the sample and the extraction apparatus.NOTE 3Alternative apparatus designs
24、including the use of a Toeplerpump have also been found successful.6.1.1 Polytetrafluoroethylene (PTFE) Tubing, narrow-bore,terminated with a Luer-Lock fitted glass syringe, and leading toa solid plug, three-way, high-vacuum stopcock.6.1.2 Degassing Flask, with a glass inlet tube, of sufficientvolum
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD361220022009STANDARDTESTMETHODFORANALYSISOFGASESDISSOLVEDINELECTRICALINSULATINGOILBYGASCHROMATOGRAPHY

链接地址:http://www.mydoc123.com/p-515103.html