ASSE 1032-2004 Performance Requirements for Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers Post Mix Type《混合型碳酸饮料分发机回路抑制器双核对真空管执行要求》.pdf
《ASSE 1032-2004 Performance Requirements for Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers Post Mix Type《混合型碳酸饮料分发机回路抑制器双核对真空管执行要求》.pdf》由会员分享,可在线阅读,更多相关《ASSE 1032-2004 Performance Requirements for Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers Post Mix Type《混合型碳酸饮料分发机回路抑制器双核对真空管执行要求》.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、Performance Requirements forDual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers, Post Mix TypeAmerican Society of Sanitary EngineeringASSE Standard #1032-2004(R2011)ASSE Board Approved: July, 2011 ANSI Approved: August, 2011 An American National StandardDual Check Valve Type
2、 Backflow Preventers for Carbonated Beverage Dispensers, Post Mix Type iASSE 1032-2004(R2011)General InformationNeither this standard, nor any portion thereof, may be reproduced without the written consent of the American Society of Sanitary Engineering.Instructions for receiving authorization to di
3、splay the ASSE Seal are available from ASSEs International Office. Organizations wishing to adopt or list any ASSE Standard should print the ASSE Standard number on the cover page first and in equal or larger type to that of the adopting or listing organization.American Society of Sanitary Engineeri
4、ngWestlake, OhioCopyright 2011, 2004, 1980All rights reserved.ii Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers, Post Mix TypeASSE 1032-2004(R2011)Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers, Post Mix Type iiiASSE 1032-2004(R2011)Forewor
5、dThis foreword shall not be considered a part of the standard. However, it is offered to provide background information.ASSE Product Standards are developed in the interest of consumer safety.The American Society of Sanitary Engineering is dedicated to the preservation of Public Health and Safety th
6、rough “Prevention Rather Than Cure.”Prevention of contamination or pollution of potable water in plumbing systems, which is one of the major objectives of the Societys Standards Program, is addressed by the development and promulgation of Standards embracing performance criteria for manufactured plu
7、mbing components designed to safeguard public health and safety.The recognition of probable sources or causes of contamination or pollution of a potable water system, whereby it becomes unfit or undesirable for human consumption, is vital to the maintenance of the systems continued potability.While
8、backflow into potable water lines is always a potential source of contamination, in connection with Post Mix Type Carbonated Beverage Dispensers, backflow of CO2 gas into copper piping of the potable water system, causing copper carbonate poisoning, is especially serious and must always be protected
9、 against.This standard is focused on those devices known as Dual (Double) Check Valves, which are one type of device recognized for backflow protection for use in connection with Post Mix Type Carbonated Beverage Dispensers. In addition to the inclusion of this device in the system, periodic inspect
10、ion and servicing of the device is essential.This standard is the latest addition to ASSEs current backflow prevention device standards, each of which cover a different type of backflow protection device; each tailored to the protective requirements essential to the specific system conditions in whi
11、ch it is installed and the degree of hazard involved.Recognition is made of the time volunteered by members of the working group and of the support of the manufacturers who also participated in the meetings for this standard.This standard does not imply ASSEs endorsement of a product which conforms
12、to these requirements.iv Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers, Post Mix TypeASSE 1032-2004(R2011)Compliance with this standard does not imply acceptance by any code body.It is recommended that these devices be installed consistent with local codes by qualified
13、 and trained professionals. It is recommended that these devices be replaced periodically per the manufacturers instructions.This standard was promulgated in accordance with procedures developed by the American National Standards Institute (ANSI).Dual Check Valve Type Backflow Preventers for Carbona
14、ted Beverage Dispensers, Post Mix Type vASSE 1032-2004(R2011)Joseph FugeloProduct Standards Committee ChairmanLabov Co. Wholesale Dist. P&HPhiladelphia, Pennsylvania Rand AckroydRand Technical Consulting, LLCNewburyport, MassachusettsWilliam Briggs, Jr.MGJ AssociatesNew York, New YorkMaribel CamposI
15、APMO Research & Testing LaboratoryOntario, CaliforniaJudson Collins Julyco ProfessionalsMannford, OklahomaRon GeorgePlumb-Tech Design & Consulting Services, LLCNewport, MichiganSteven HazzardASSE Staff EngineerWestlake, Ohio Charles HernandezSpears ManufacturingBollingbrook, Illinois2011 Product Sta
16、ndards Committee John F. Higdon, P.E.Apollo Valves / Conbraco IndustriesMatthews, North CarolinaChuck LottPrecision Plumbing ProductsPortland, OregonPeter MarzecPearl River, New YorkHamid NaderiICC-TexasAustin, TexasBrad NollWilkins / A Division of ZurnPaso Robles, CaliforniaThomas PitcherelloBorden
17、town, New JerseyShabbir RawalpindiwalaKohler CompanyKohler, WisconsinDr. Tsan-Liang SuStevens Institute of TechnologyHoboken, New Jerseyvi Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers, Post Mix TypeASSE 1032-2004(R2011)Table of ContentsSection I . 11.0 General . 11.1
18、Application 11.2 Scope . 11.3 Limitations on Design . 11.4 Reference Standards 2Section II 32.0 Test Specimens 32.1 Samples Submitted 32.2 Samples Tested 32.3 Drawings 32.4 Rejection 3Section III . 43.0 Performance Requirements and Compliance Testing 43.1 Hydrostatic Test of Complete Device . 4Figur
19、e 1 43.2 Deterioration at Extremes of Manufacturers Temperature Range Test . 43.3 Endurance Cycling Test 5Figure 2 53.4 Hydrostatic Leakage Test of Check Valves 6Figure 3 63.5 Drip Tightness of Check Valves Test 73.6 Allowable Pressure Loss at Rated Flow Test . 7Section IV 84.0 Detailed Requirements
20、 . 84.1 Materials . 84.2 Instructions for Marking and Installation . 8Section V . 95.0 Definitions . 9Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers, Post Mix Type 1ASSE 1032-2004(R2011)Dual Check Valve Type Backflow Preventers for Carbonated BeverageDispensers, Post Mi
21、x TypeSection I1.0 General1.1 ApplicationDual check valve type backflow preventers (for carbonated beverage dispensers, post mix type), herein referred to as “device,” prevent carbon dioxide gas and carbonated water from backflowing into the potable water system which supplies the carbonating unit.
22、These devices operate under continuous or intermittent pressure conditions.1.2 Scope1.2.1 DescriptionThese devices consist of two (2) independently acting check valves internally force loaded to a normally closed position and designed to operate under intermittent or continuous pressure conditions.T
23、hese devices shall be permitted to be equipped with a supplementary check valve installed downstream of the independently acting check valves.1.2.2 Size RangeThese devices shall be designed to accommodate or inch (8 or 10 mm) nominal pipe sizes.1.2.3 Minimum Working PressureDevices shall be designed
24、 for a working pressure of not less than 200.0 psi (1379.0 kPa).1.2.4 Temperature RangeDevices shall be designed to operate at temperatures of 33.0 F to 110.0 F (0.6 C to 43.3 C).1.3 Limitations on Design1.3.1 Flow CapacityThe device shall meet the flow capabilities at the pressure drop specified in
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASSE10322004PERFORMANCEREQUIREMENTSFORDUALCHECKVALVETYPEBACKFLOWPREVENTERSFORCARBONATEDBEVERAGEDISPENSERSPOSTMIXTYPE

链接地址:http://www.mydoc123.com/p-457121.html