ASHRAE ST-16-002-2016 A CFD Study to Identify Methods to Increase Maximum Velocity of Makeup Air for Atrium Smoke Control.pdf
《ASHRAE ST-16-002-2016 A CFD Study to Identify Methods to Increase Maximum Velocity of Makeup Air for Atrium Smoke Control.pdf》由会员分享,可在线阅读,更多相关《ASHRAE ST-16-002-2016 A CFD Study to Identify Methods to Increase Maximum Velocity of Makeup Air for Atrium Smoke Control.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、10 2016 ASHRAEThis paper is based on findings resulting from ASHRAE Research Project RP-1600.ABSTRACTThe primary purpose of this study is to develop engineer-ing methods to assess the impact of increased makeup airvelocity in atria. The current restriction defined by NFPA 92(NFPA2015)states:“Themake
2、upairvelocityshallnotexceed200 ft/min (1.02 m/sec) where the makeup air could come intocontact with the plume unless a higher makeup air velocity issupported by engineering analysis.” This limitation not onlylimits creative and aesthetic atria designs but may also repre-sentasignificantcost.Thisstud
3、yanalyzestheeffectofmakeupair injected by a variety of vent sizes at elevations at or belowthe limiting elevation of the flame through numerical simula-tions. This study focuses on identifying worst-case scenariosfor the interaction of makeup air with an axisymmetric plumeby applying computer modeli
4、ng to simulate multiple configu-rations, observe the results, and adapt further simulations toelicit the most extreme cases. A mass flow rate diagnostic isused to assess the increase in entrainment (i.e., smoke produc-tion.) This mass flow diagnostic is developed to provide acomparative analysis, as
5、sessing the increase in the rate ofsmoke production with a specified makeup air velocity withthat produced with no mechanical makeup air. The propor-tionalincreaseinentrainmentisdefinedasanalphafactor.Themost significant smoke production increase and smoke layerstabilizationdescentisassociatedwitha1
6、MW(950Btu/s)fire,with lesser increases observed for 2.5 and 5 MW (2370 and4740 Btu/s) fires. As the makeup air is introduced further fromtheedgeoftheflame,theapparenteffectoftheairflowvelocityis reduced.INTRODUCTIONThe primary purpose of this study is to develop engineer-ing methods to assess the im
7、pact of increased makeup airvelocity in atria. The current restriction defined by NFPA 92states that makeup air must not exceed 1.02 m/s (200 fpm)during the operation of a mechanical smoke exhaust system(NFPA 2015). The makeup air required for atria during theoperation of a mechanical smoke exhaust
8、system may involvelargeareasofpassiveopeningsandmechanicalventilation,alllocated below the smoke layer. This limitation not only limitscreative and aesthetic atria designs but also involves signifi-cant costs. Many engineering designers use alternative meth-ods to exceed the limit of the code, claim
9、ing that the velocitylimit is too restrictive.PROJECT SCOPEAtria have become increasingly popular design featureswithin large commercial spaces, contemporary hotels, andmultilevel shopping centers. Modern atria serve as prominentaesthetic features, and are often several stories high. Manyatria have
10、glazed roofs and large windows for grandeur and afeeling of space and light.The openings in the floors created to form an atrium posefire and smoke challenges. The large space allows for easiersmoke spread between floors and adjacent openings. A prin-cipal design objective for fire protection system
11、s in an atriumis to protect occupants from the adverse effects of smoke andcontain the fire and smoke to its room of origin. As atria fash-ion larger openings, the ability to compartmentalize smokeA CFD Study to Identify Methods to IncreaseMaximum Velocity of Makeup Air forAtrium Smoke ControlChrist
12、ine Pongratz James A. Milke, PhD, PE Arnaud Trouve, PhDChristine Pongratz is a graduate research assistant at the University of Maryland, College Park, MD, and a graduate fire engineer at Arup,London, UK. James A. Milke is a professor and chair and Arnaud Trouve is a professor in the Department of F
13、ire Protection Engineering,University of Maryland, College Park, MD.ST-16-002 (RP-1600)Published in ASHRAE Transactions, Volume 122, Part 2 ASHRAE Transactions 11and fire decreases. Consequently, alternative designapproaches must be used to maintain life safety objectives.The hazard of smoke spread
14、in atria must be addressed tosatisfy identified objectives. Possible objectives detailed inNFPA 92 (NFPA 2015) include the following:Maintain a tenable environment in the means of egressfrom large-volume building space during the timerequired for evacuationControl and reduce smoke spread between the
15、 fire areaand adjacent spacesProvide conditions within and outside the fire zone toassist emergency response personnel in conductingsearch and rescue operations and in locating and con-trolling the fireContribute to the protection of life and reduction ofproperty lossAid in post fire smoke removalIn
16、 order to accomplish the design objective(s), an engi-neered smoke management system is considered for all atria.NFPA 92 includes requirements for the design of smokemanagement systems (NFPA 2015). By evaluating the designcharacteristics of the atrium, numerous smoke managementapproaches may be cons
17、idered.There are various design approaches for atria that areintended to maintain tenable conditions for occupants. Amechanical smoke exhaust system is a commonly usedapproach in North America (Klote et al. 2012). The system isdesigned to use mechanical exhaust to stabilize the bottom ofthe smoke la
18、yer at a predetermined height. The exhaustremoves smoke from the upper levels of the atrium to preventaccumulationofheatandsmokeandpreventthedescentofthesmoke layer interface below the predetermined height.The mechanical ventilation system assumes the forma-tion of a smoke layer at the ceiling. Fact
19、ors that may affect thesmoke layer include sprinkler activation, HVAC systems, aircurrents striking the plume, upward thrusting airflows, and airforced into the upper layer by means other than the plume.In order to provide effective mechanical ventilation,makeup air supply must be provided. The supp
20、ly of makeupair may enter into the compartment from passive openings,such as doors or windows, or additional mechanical ventila-tion. The amount of air that must be supplied is not dictated inthe model building codes, but several restrictions areaddressed in the design of this component of the syste
21、m.High makeup air velocity may increase air entrainmentintoaflametosignificantlyaffectfiredevelopmentandsmokemovement within a compartment. Increased air entrainmentwill increase mixing between ambient air and smoke toupsurge the volume of smoke produced. Also, the additionalair velocity may tilt th
22、e flame and disturb the upward trajec-tory of the fire plume, which may expose occupants to addi-tionalradiantheatfluxandsmoke.Aschematicdiagramoftheeffect of increased makeup air velocity on the fire plume isshowninFigure1.Theimageillustratesadisturbedfireplumewith smoke entering the balcony levels
23、 of the atrium. Theadverseeffectofthemakeupaircompromisestheabilityofthemechanical exhaust system to achieve the design goals ofmaintaining the smoke layer above a particular elevation.Currently NFPA 92 restricts the makeup air velocity notto exceed 1.02 m/s (200 fpm) to prevent significant plumedef
24、lection and disruption of the smoke layer interface. Thislimitation is further discussed by Klote et al. (2012). NFPA 92permits greater velocities of makeup air if the design issupported by engineering analysis (NFPA 2015).Although there is no restriction on the overall volumetricflow of makeup air,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEST160022016ACFDSTUDYTOIDENTIFYMETHODSTOINCREASEMAXIMUMVELOCITYOFMAKEUPAIRFORATRIUMSMOKECONTROLPDF

链接地址:http://www.mydoc123.com/p-455997.html