ASHRAE LV-11-C062-2011 Demand Control Ventilation Lessons from the Field- How to Avoid Common Problems.pdf
《ASHRAE LV-11-C062-2011 Demand Control Ventilation Lessons from the Field- How to Avoid Common Problems.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-C062-2011 Demand Control Ventilation Lessons from the Field- How to Avoid Common Problems.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Brad Acker is Researcher, Kevin Van Den Wymelenberg is a director and assistant professor at the University of Idaho, Integrated Design Lab, Boise, Idaho Demand Control Ventilation: Lessons from the Field- How to Avoid Common ProblemsBrad Acker, PE Kevin Van Den Wymelenberg Member ASHRAE Member ASHR
2、AE Abstract Demand control ventilation (DCV) has the potential to save energy by reducing ventilation rates in accordance with occupancy levels provided by the surrogate indication of CO2levels. However, improperly installed, designed, or operated systems may save energy at the expense of Indoor Air
3、 Quality (IAQ) or enhance IAQ at the expense of energy. These outcomes may have the potential to foul the image of an otherwise viable energy efficiency measure. This paper reports what the authors believe to be common problems in the design, installation and operation of DCV systems which use CO2as
4、 a surrogate for occupancy levels. Six HVAC systems were investigated: two commercial offices, two medical offices, and two school environments. The design drawings, air balance reports, and current equipment set up were investigated. Four systems were controlled locally through roof top unit contro
5、l logic and two systems were controlled by central building energy management systems. Functional testing of equipment was carried out and system parameters were logged including CO2levels, fans states, and air stream temperatures. Functional testing was broken up into three system aspects. First, C
6、O2control signal functional testing was conducted to confirm that the control link between CO2sensors and outside air damper positioning was in place. Second, sensor placement functional testing was conducted to confirm that the sensors placement could accurately report the CO2levels of the controll
7、ed zone. Third, the Outside Air (OSA) level test was conducted by inspecting the air balance reports to determine the OSA rates and to confirm that the system was balanced in accordance with DCV standards. The study found that no systems were functioning properly for a number of reasons, some of whi
8、ch were overlapping. Reasons for non-functionality included poor sensor placement, improper information provided in mechanical schedules or design documents, fan cycling issues, and poor installation. Details on failure modes will be presented. Proper engineering documentation requirements will be e
9、xplained. Test, Adjust, Balance (TAB) specifications and DCV specific requirements for TAB along with information that building operators need to know about system operation will be presented. LV-11-C062502 ASHRAE Transactions2011. American Society of Heating, Refrigerating and Air-Conditioning Engi
10、neers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAES prior written permission.INTRODUCTION Demand control ventilation (DCV) is
11、 a building ventilation control strategy in which the quantity of mechanically supplied outdoor air intake is regulated by some type of occupant density sensing. DCV is intended to save energy by means of supplying design ventilation air t o occupants during periods of h igh occupancy and supplying
12、the minimum required ventilation to dilute building related c ontaminants during low occupancy periods. Reducing the amount of outdoor air that needs to be conditioned can save energy. If air side economizers are in use specific outdoor conditions will have an effect on the amount of energy savings.
13、 Carbon dioxide (CO2) sensors are the industry standa rd to determined space occupancy for DCV. It has been shown that CO2levels are a good determination of space occupancy (Turpin, 2001). It should be noted that CO2is not considered an indoor air quality (IAQ) concern at levels found in typical bui
14、ldings (400-2000ppm) but is used solely as an indication of occupancy level (Emmerich, 2001). DCV systems can be incorporated into existing HVAC equipment and often times operate in conjunction with existing economizer controls, sharing the same outdoor air damper (OAD). Savings from DCV systems are
15、 achieved by the reduction in outdoor supply air (OSA) that requires conditioning as compared to a fixed OSA flow rate during all occupied hours. FIELD RESEARCH Six spaces were randomly chosen from a list of spaces provided by the funding agency, which supplied incentives for the use of DCV. All stu
16、dy spaces were in ASHRAE climate zone 5B. Table 1 below shows the description of the study spaces. Two control types were encountered in the study and listed in Table 1. The control types were roof top unit (RTU) or control with a building energy management system (EMS). DCV is intended for spaces w
17、hich have variable occupancy rates, this was the case in the spaces for building codes 04-09 but buildings 01 and 10 had incorrectly located CO2 sensors which well be ad dressed below. All buildings were fully occupied except for building 10 which was estimated by building management to be 70% lease
18、d out. Specific occupancy patterns within spaces was not studied. Table 1 Study Space Functional testing was broken up into three system aspects. First, CO2 control signal functional testing was conducted to confirm that the control link between CO2 sensors and OA damper positioning was in place. Se
19、cond, se nsor placement functional testing was conducted to confirm that the sensors accurately reported the CO2levels of the controlled zone. Third, the OSA level test was conducted by inspecting the air balance reports to determine the OSA rates and to confirm that the system was balanced in accor
20、dance with DCV standards such as presented in ASHRAE 62.1-2007. Only when DCV systems passed all three functional tests could energy savings estimates be carried out. Building Code Year Installed Control Type Building Type Building Size, SF (m2) Study Space Description Study Space Size SF (m2) 01 2
21、006 EMS Office 68,000 (6317) One third of entire building 22,600 (2099) 04 2008 RTU Office/Medical 21,104 (1961) Break room 300 (28) 06 2 007 BAS Elementary School 63,400(5890) C lassroom 1,000 (93) 08 2007 RTU High School 65,000 (6039) Classroom 800 (74) 09 2 007 RTU High School 102,000 (9476) Clas
22、sroom 78 0 (72) 10 2 008 RTU Office 15,750 (1463) Half of entire building 7,875 (732) 2011 ASHRAE 503Functional testing of DCV systems was done in accordance with the basic control type and differed whether it was managed through an energy management system (EMS) or at the roof top unit (RTU). EMS b
23、ased control systems were tested by manually lowering the CO2setpoints to be below the current levels within a space and watching (on the EMS screen) for the OA damper to open in that space. RTU base d control systems were tested by havi ng one person exhale directly onto the CO2sensor and having an
24、other person located at the RTU watch for the damper to respond and for the DCV indicator light to illuminate (if available) on the logic controller. In addition to physical functional testing, trendlog data and other direct measurement data were analyzed. Care was taken when analyzing data to find
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV11C0622011DEMANDCONTROLVENTILATIONLESSONSFROMTHEFIELDHOWTOAVOIDCOMMONPROBLEMSPDF

链接地址:http://www.mydoc123.com/p-455465.html