1、8.1CHAPTER 8COMBUSTION TURBINE INLET COOLINGAdvantages 8.2Disadvantages . 8.3Definition and Theory . 8.3System Types . 8.3Calculation of Power Capacity Enhancement and Economics. 8.6OWER OUTPUT capacity of all combustion turbines (CTs)Pvaries with ambient air temperature and site elevation. Therated
2、 capacities of all CTs are based on standard ambient air at15C, 60% rh, 101.35 kPa at sea level, and zero inlet and exhaustpressure drops, as selected by the International Organization forStandardization (ISO). For all CTs, increased ambient air tempera-ture or site elevation decreases power output;
3、 increased ambient airtemperature also reduces fuel efficiency (i.e., increases the heat rate,defined as fuel energy required per unit of electric energy pro-duced). However, the extent of the effect of these changes on outputand efficiency varies with CT design. This chapter provides adetailed disc
4、ussion on combustion turbine inlet cooling (CTIC).Additional information on applying CTIC to combined heat andpower systems (cogeneration) is provided in Chapter 7.There are two types of CTs: aeroderivative and industrial/frame.Figures 1 and 2 show typical effects of ambient air temperature onpower
5、output and heat rate, respectively, for these types of turbines.The actual performance of a specific CT at different inlet air temper-atures depends on its design. Figures 1 and 2 show that aeroderiv-ative CTs are more sensitive to ambient air temperature than areindustrial/frame CTs. Figure 1 (Punw
6、ani and Hurlbert 2005) showsthat, for a typical aeroderivative CT, an increase in inlet air temper-ature from 15 to 38C on a hot summer day decreases power outputto about 81% of its rated capacity: a loss of 19% of the rated capacity.Figure 2 (Punwani 2003) shows that, for the same change in ambient
7、air temperature, the heat rate of a typical aeroderivative CT increases(i.e., fuel efficiency decreases) by about 4% of the rated heat rate atISO conditions. Increasingly, industrial/frame CTs are using aerode-rivative technology to improve performance; thus, their performancecurves are moving towar
8、d those of the classic aeroderivative CT.In cogeneration and combined-cycle systems that use thermalenergy in CT exhaust gases for steam generation, heating, cooling,or more power generation, increases in ambient air temperature alsoreduce the total thermal energy available for these applications, a
9、sshown in Figure 3 (Orlando 1996).CTs in simple- and combined-cycle systems are particularlyqualified to meet peak electricity demand because of their ability tostart and stop more quickly than steam-turbine-based thermal powergeneration systems using coal, oil or gas, and nuclear plants. Forfossil
10、fuel power generation, combined-cycle systems are the mostfuel efficient (lowest heat rate of typically 7400 kJkWh) and steam-turbine-based systems are the least efficient (highest heat rate rangebetween 12 660 and 21 100 kJkWh, depending on turbine age). AThe preparation of this chapter is assigned
11、 to TC 1.10, CogenerationSystems.Fig. 1 Effect of Ambient Temperature on CT Output(Punwani and Hurlbert 2005)Fig. 2 Effect of Ambient Temperature on CT Heat Rate(Punwani 2003)Fig. 3 Effects of Ambient Temperature on Thermal Energy, Mass Flow Rate and Temperature of CT Exhaust Gases(Orlando 1996)8.2
12、2012 ASHRAE HandbookHVAC Systems and Equipment (SI)typical heat rate for a simple-cycle system is about 10 550 kJkWh.Therefore, to minimize fuel cost for power generation, the preferredorder of dispatching power to meet market demand is to operatecombined-cycle systems first, simple-cycle systems ne
13、xt, and steamturbines as the last resort.Electric power demand is generally high when ambient temper-atures are high. An example of an hourly profile of ambient temper-ature, system load, and CT output is shown in Figure 4 (Punwaniand Hurlbert 2005).When high ambient temperatures drive up power dema
14、nd, theuse of less efficient (high-fuel-cost) generation plants is requiredand that drives up the market price of electric energy. Figure 5(Hilberg 2006) shows the hourly load profile in one U.S. region fora single day in the summer. Although the peak electricity demandincreases by 80%, the peak pow
15、er price increases by over 400%.Figures 4 and 5 show that power output capacity decreases justwhen it is most needed, and when power is also most valuable.The trends shown in Figures 4 and 5 are not unique to the UnitedStates. The Middle East is seeing much higher growth rates in powerdemand, and th
16、at demand is also directly linked to hot-weatherpower usage. In some countries in the Middle East, over 40% ofpower usage is linked to air conditioning.CTIC is used by thousands of CT-based power plants to overcomethe ill effects of increased ambient temperature on CT performance.It can provide econ
17、omic and environmental benefits for plant own-ers, ratepayers, and the general public.ADVANTAGESCTIC offers economic as well as environmental benefits.Economic BenefitsMaximizes power output when most needed and most valuableReduces capital cost ($kW) for incremental capacityIncreases CT fuel effici
18、ency (lowers heat rate)Minimizes use of less-efficient steam-turbine-based systems, thushelping to minimize increase in rates to electricity usersEnvironmental BenefitsAllows minimum use of inefficient and polluting power plants byallowing maximum use of efficient and cleaner CT plantsConserves natu
19、ral fuel resourcesReduces emissions of pollutants (SOx, NOx, particulates, andhydrocarbons)Reduces emissions of global warming/climate change gas(CO2)Minimizes/eliminates new power plant siting issuesEmissions reductions from CTIC result from its displacement ofthe very-high-heat-rate steam turbine
20、peaker power plants, as shownin an example in Table 1.CTIC helps reduce the carbon footprint of energy use in twoways: it (1) improves the CTs energy efficiency and (2) increasesthe generation capacity of higher-efficiency systems and thus elim-inates or minimizes use of less-efficient power generat
21、ion systems.There are four major types of thermal power generation systems:Combined cycle (CC)Simple cycle (SC)Combined heat and power (CHP) or cogenerationCondensing steam turbineElectric power generation efficiencies of these systems aretypically in the ranges of 48 to 55% (i.e., heat rates of 690
22、0 to7400 kJ/kWh) for combined cycle, 34 to 42% (i.e., heat rates of8500 to 10550 kJ/kWh) for simple cycle, and 23 to 28% (i.e., heatrates of 12 700 to 15 600 kJ/kWh) for steam turbine. Even thoughpower generation efficiencies of CHP systems are very similar tothose of the CC or SC system that is par
23、t of the CHP, the overallenergy utilization efficiency of a CHP could be highest for facilitiesthat need to meet electric as well as coincidental thermal loads. Theoverall energy utilization efficiency is the lowest for steam-turbinesystems. Examples of electric generation efficiencies, overallFig.
24、4 Typical Hourly Power Demand Profile(Punwani and Hurlbert 2005)Fig. 5 Example of Daily System Load and Electric Energy Pricing Profiles(Hilberg 2006)Combustion Turbine Inlet Cooling 8.3energy utilization efficiencies, and carbon dioxide emissions of allfour systems are shown in Table 1. In this exa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACSYSTEMSANDEQUIPMENTSICH82012COMBUSTIONTURBINEINLETCOOLINGPDF

链接地址:http://www.mydoc123.com/p-455135.html