ASHRAE AB-10-001-2010 Influence of Test Section Entrance Conditions on Straight Flat Oval Duct Apparent Relative Roughness.pdf
《ASHRAE AB-10-001-2010 Influence of Test Section Entrance Conditions on Straight Flat Oval Duct Apparent Relative Roughness.pdf》由会员分享,可在线阅读,更多相关《ASHRAE AB-10-001-2010 Influence of Test Section Entrance Conditions on Straight Flat Oval Duct Apparent Relative Roughness.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、2010 ASHRAE 371ABSTRACTAn experimental program was initiated to study the influ-ence of test section entrance conditions on straight flat oval duct apparent relative roughness. The purpose of these tests was to assess whether deviations from test section entrance geometries as prescribed by ASHRAE S
2、tandard 120 have an impact on friction factor and relative roughness. The observed relative roughness values varied as the entrance length increased. The apparent relative roughness obtained using a test setup in compliance with Standard 120 was considerably lower than the value of relative roughnes
3、s obtained with a test setup that did not conform to the standard. It is recommended that all duct and fitting pressure loss tests be conducted in compliance with Standard 120, and that Standard 120 be modified so that the flow measuring chamber velocity does not exceed 1.5 m/s (300 ft/min). It is a
4、lso recommended that the entrance duct length be increased from 10 hydraulic diameters to 12 diameters.INTRODUCTIONThe straight flat oval duct pressure loss tests reported in and Idem et al. (2008) were performed with the same setups as depicted by Figures 2 and 3, where the larger ducts were tested
5、 with the plenum chamber/bellmouth. The nozzle chamber was (1) not large enough for the bellmouth connection to the test duct setup, and (2) the static pressure was not adequate to be measured downstream. It is noted that upstream conical tran-sitions into the straight duct test apparatus violated A
6、SHRAE Standard 120, which specifies that a bellmouth be located upstream of the test section. Furthermore, the transition angles were not in compliance with Figure 20 of ASHRAE Standard 120. Likewise, ASHRAE Standard 120 requires that all straight duct pressure loss tests be conducted on test setups
7、 having an entrance length exceeding ten hydraulic diameters. This study was initiated to determine the effects of varying the inlet conditions on measured pressure loss characteristics and to establish whether the data are repeatable by comparing to the data of Idem et al. (2008). EXPERIMENTAL PROG
8、RAMIn this project pressure loss characteristics of flat oval ducts were tested with different entrance lengths and condi-tions. The purpose of these tests was to assess whether devi-ations from test section entrance geometries as prescribed by ASHRAE Standard 120 have an impact on the measured fric
9、-tion factor and relative roughness. Referring to Figure 1 (excerpted from ASHRAE Standard 120), pressure loss tests on straight ducts and fittings must be performed with an entrance length exceeding ten hydraulic diameters upstream of the test section. In addition, the standard requires a bell-mout
10、h located upstream of the entrance duct. One entrance geometry employed in this study consisted of a plenum cham-ber with a bellmouth mounted upstream of the duct test section, as depicted schematically by Figure 2. Another entrance condition employed three transitions mounted between the airflow me
11、asuring nozzle chamber and the entrance duct to the test section, as sketched in Figure 3. For either upstream geometry condition the test section entrance length Liwas varied over a range of values from approxi-mately 6 to 12 hydraulic diameters. The flat oval duct cross sections considered in this
12、 study are summarized in Table 1. This table also details the upstream lengths that were employed in the experiments. The ducts were 24-gauge galvanized steel with 1.2 m (4 ft) sections Influence of Test Section Entrance Conditionson Straight Flat Oval Duct Apparent Relative RoughnessS. Khaire S. Id
13、em, PhDMember ASHRAES. Khaire is a research assistant and S. Idem is a professor in the Department of Mechanical Engineering, Tennessee Tech University, Cookeville, TN. AB-10-0012010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRA
14、E Transactions (2010, Vol. 116, Part 2). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.372 ASHRAE Transactionsconnected by beaded slip couplings. In every case the ducts possesse
15、d a spiral seam having a pitch of 122 mm (4.75 in.). Wooden stands were used to support the duct sections, which were aligned visually and sealed using duct tape. The hydrau-lic diameter was determined by measuring the major and minor dimensions of three duct sections chosen at random and averaging
16、these values.For tests performed using the setup depicted in Figure 2 the plenum chamber served a dual purpose. The large cross section permitted the buildup of static pressure upstream of the test section, which was found to be vital when testing large cross section straight ducts and allowed for a
17、 measurable pres-sure loss. Moreover, the plenum chamber acted much like a muffler, in that any pressure fluctuations were effectively Figure 1 Straight duct test setup (ASHRAE 2008, Figure 16).Figure 2 Straight duct test setup with a plenum/bellmouth chamber.2010, American Society of Heating, Refri
18、gerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, Vol. 116, Part 2). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.2010 ASHR
19、AE 373damped out upstream of the test sections. The plenum cham-ber did not possess flow settling screens. The plenum chamber cross section was 1.2 m 1.2 m (4 ft 4 ft), and the overall length was 2.4 m (8 ft). The cross section was chosen so that the maximum air velocity in the plenum was on the ord
20、er of 1.5 m/s (300 ft/min). The walls were constructed from 16-mm (5/8 in.) thick plywood sheets. All joints were reinforced inter-nally by 51 mm 102 mm (2 in. 4 in.) wooden boards nailed directly to the plywood. In addition steel corner brackets were placed along the interior of the chamber to incr
21、ease its strength and ensure the cross section remained square. Referring to Figure 2, the plenum chamber was connected to the nozzle chamber by a 508-mm (20 in.) long 610-mm (24 in.) to 406-mm (16 in.) round transition made of galvanized steel. A commercial-grade flat oval bellmouth having an appro
22、ximate 32 mm (1.3 in.) radius of curvature was mounted on the down-stream end of the plenum chamber to facilitate connection to the test duct. The radius ratio r/Dhin each case violated the requirements in ASHRAE Standard 120 (r/Dh 0.25). All plenum chamber joints and connections were further secure
23、d and sealed using a combination of sheet metal screws and sili-cone caulking.For tests performed using the setup sketched in Figure 3 the transition between the nozzle chamber and the test duct consisted of a 610-mm (24 in.) to 406-mm (16 in.) round tran-sition, a 229 mm (9 in.) long straight duct,
24、 and a 406-mm (16 in.) to 305-mm (12 in.) round transition. These transitions were followed by a round to flat oval transition piece, as shown in Figure 4. The round to flat oval transitions (Table 2) had diverging angles of 22.6 and 4.6 in the flow direction, thus exceeding the maximum of 3.5 permi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEAB100012010INFLUENCEOFTESTSECTIONENTRANCECONDITIONSONSTRAIGHTFLATOVALDUCTAPPARENTRELATIVEROUGHNESSPDF

链接地址:http://www.mydoc123.com/p-454496.html