ASHRAE 4845-2006 Distribution of Water between Vapor and Liquid Phases of Refrigerants《气液双相制冷剂的水分配(RP-1239)》.pdf
《ASHRAE 4845-2006 Distribution of Water between Vapor and Liquid Phases of Refrigerants《气液双相制冷剂的水分配(RP-1239)》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4845-2006 Distribution of Water between Vapor and Liquid Phases of Refrigerants《气液双相制冷剂的水分配(RP-1239)》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、4845 (RP-1239) Distribution of Water between Vapor and Liquid Phases of Refrigerants Andy Gbur ABSTRACT This research determined the vapor-liquid equilibrium distribution ratio (K-value) for the refrigerants 22, 123, 134a, 32,125,143a, 404A, 407C, 410A, and 507A. These data were derived from measuri
2、ng the moisture content of the vapor and liquidphases of specijically contaminated refrigerant samples at temperatures of 40F: 75“e and 120F (4“C, 24“C, and 49C). INTRODUCTION It is well documented that moisture is an undesired contaminant in refrigeration systems. High levels of moisture may cause
3、physical and chemical damage to the system. Excessive moisture can lead to icing of capillary tubes, expan- sion valves, and other evaporating devices. In addition, water can expedite chemical reactions in a system, leading to corro- sion of metal surfaces and copper plating, hydrolysis of POE lubri
4、cants, and breakdown of motor winding insulation mate- rials. The best way to prevent moisture contamination in a system is to ensure proper care is taken in the installation and design of the refrigeration system. However, prevention alone cannot protect against all possible field conditions that m
5、ay introduce moisture into the system. In these situations, an understanding of the behavior of moisture in refrigerant will allow technicians to accurately diagnose problems, implement corrective actions, and ultimately prevent system failures. BACKGROUND Previous moisture saturation and solubility
6、 data published in the ASHRAE Handbook has been limited to chlo- rofluorocarbon (CFC) and a few hydrochlorofluorocarbon John Senediak (HCFC) refrigerants and has been questioned as to its validity. As a precursor to this research, four laboratories used various methods to veri the ratio of moisture
7、distribution between the liquid and vapor phases for R-134a (0.58) stated in the ASHRAE Handbook. The determined ratios were 1.19, 1.08, 0.93, and 0.89 at room temperatures. These results were considerably higher than those published. The first three results were determined experimentally by contami
8、nation of various amounts of refngerant. The last value was calculated using the Peng-Robinson equation-of-state. The suspect ratio published in the ASHRAE Handbook was determined with the rcfrigerant in a state of saturation. Typically refrigeration systems are below these saturation values, yet th
9、ese levels of moisture still have the potential for degradation of the system, thus the need to experimentally measure ratios at conditions below saturation. EXPERIMENT There were many environmental interferences and proce- dural challenges that had to be addressed prior to developing the procedure
10、for this project. Some of these are sampling technique, ambient humidity, accurate quantification of trace levels of moisture in the stock refrigerant, and moisture adsorption by the metal surfaces of the cylinder walls. The plan was to reduce the impact of each of these interferences to maximize th
11、e measurement accuracy of the moisture equilib- rium constants. The recognized standard for the measurement of moisture in refrigerant is the ARI Standard 700, appendix C. The AR1 Standard 700 moisture procedure dictates that aliquots of refrigerant be transferred to small sample cylinders prior to
12、analysis. The liquid sample is then evaporated through a capil- Andy Gbur is business manager and John Senediak is manager of the Refrigeration Chemistry Laboratory at Intertek, Columbus, Ohio. 02006 ASHRAE. 241 lary tube into a Karl Fischer vessel for titration. This method unnecessarily introduces
13、 several variables into the uncertainty contamination was seen, whereas afterward the recoveries were between 93% and 98%. equation, such as transfer efficiency and weighing errors. Additionally, several assumptions are made that cannot be readily supported. First, an assumption is made that a hot e
14、vac- uated sample cylinder is moisture free. Second, the assump- tion is made that moisture will not remain behind in the sample cylinder upon evaporation of the refiigerant. This directly relates to and is affected by the distribution of moisture between the liquid and vapor phases of refrigerants,
15、 which is what the project attempted to quantify. To eliminate as many variables as possible, the choice was made to introduce the refrigerant directly into the Karl Fischer vessel from the refrig- erant batch cylinder utilizing a capillary tube restriction. This ensured that a homogeneous mixture o
16、f moisture and refrig- erant was introduced and eliminated the possibility of using a contaminated sample cylinder. The next challenge was to minimize the effect of environ- mental moisture contamination. Two Liebert environmental conditioners control the laboratory temperature and humidity. The hum
17、idity remains at a constant 40% (*2%) with a consis- tent temperature of 74F (23”C), *2”F. This stable environ- ment allows us to predict and compensate for the infiltration of moisture into the Karl Fischer vessels. In addition, the Accumet Model 100 coulometric titrators being used were equipped w
18、ith a mechanism that monitors and reports the moisture background or “drift rate” of the vessels. All tests were conducted with a “drift rate” of less than 0.05 micro- grams per second. Furthermore, the samples were introduced at a rate of 5 grams per minute. This high rate of sample deliv- ery prod
19、uces a short sample introduction time, thus minimiz- ing the effect of environmental moisture. Moisture adsorption by the metal surfaces ofthe cylinders posed the final challenge. Initial attempts to contaminate a batch of refrigerant demonstrated this effect. After a calcu- lated 50 ppm water conta
20、mination of the refrigerant, analysis showed only 40 ppm. We concluded that the poor recovery was due to the absorption of some of the added water by the steel walls of the new, unconditioned cylinder (standard cylin- der constructed of 1008/1010 cold rolled steel). Our solution was to precondition
21、testing cylinders with wet refrigerant to allow the walls to saturate. First, we heated the cylinders to 100C for 24 hours. The cylinders were then removed from the oven, and pulled into a 200 micron vacuum. Next the cylinders were charged with R- 134a refrigerant contaminated with 120 PPM of moistu
22、re and allowed to react for a minimum of 24 hours. The refrigerant was then recovered and once again the cylinders were heated to 100C for a minimum of 24 hours and then evacuated. The cylinders were now ready for contam- ination. The validation of this technique was seen in the higher recovery numb
23、ers received from the moisture contaminations. Prior to this conditioning, 75% recovery of the moisture The contamination process begins with the precondition- ing of two cylinders with the above procedure and connecting them together, one inverted with respect to the other, using a steel cross fitt
24、ing. Next, the cylinder assembly was pulled into a 200-micron vacuum, and the precalculated weight of water was added through a septum into the cross fitting. The cylinder assembly was then placed on a scale and the required amount of prequantified stock refrigerant was added. To achieve an 80% full
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE48452006DISTRIBUTIONOFWATERBETWEENVAPORANDLIQUIDPHASESOFREFRIGERANTS 气液双相 制冷剂 水分 RP1239PDF

链接地址:http://www.mydoc123.com/p-454391.html