ASHRAE 4713-2004 Development of Energy-Efficient Single-Coil Twin-fan Air-Conditioning System with Zonal Ventilation Control《分区通风控制 高耗能高效率的单线圈双风扇空调系统的发展》.pdf
《ASHRAE 4713-2004 Development of Energy-Efficient Single-Coil Twin-fan Air-Conditioning System with Zonal Ventilation Control《分区通风控制 高耗能高效率的单线圈双风扇空调系统的发展》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 4713-2004 Development of Energy-Efficient Single-Coil Twin-fan Air-Conditioning System with Zonal Ventilation Control《分区通风控制 高耗能高效率的单线圈双风扇空调系统的发展》.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、471 3 Development of Energy-Efficient Single-Coil Twin-Fan Air-Conditioning System with Zonal Ventilation Control S.C. Sekhar, Ph.D. Member ASHRAE K.W. Tham, Ph.D. ABSTRACT Indoor air quality (IAQ) is strongly afected by the various sources of indoor pollutants and the eciency of the ventila- tion s
2、ystem. Higher ventilation demands pose an enormous energy pena Wargocki et al. 2000). The importance of effective ventilation distribution has also been investigated in the context of the outdoor air being available at the occupied breathing zone (Sekhar et al. 2000). In certain climatic condi- tion
3、s, such as the tropics, air conditioning is dictated by the stringent requirements of cooling and dehumidification, which becomes a challenge to the designer who is usually confronted with cost-effective design criteria to address ther- mal comfort, indoor air quality (IAQ), and energy issues. The h
4、igh energy penalty of cooling and dehumidification associ- ated with ventilation in the tropical context is apparent from the large enthalpy difference that exists between the outdoor air and the indoor air conditions (Luxton and Marshallsay 1998). Inadequate ventilation would almost invariably lead
5、 to a deterioration of the indoor air quality due to a buildup of indoor pollutants, and adequate ventilation with poor dehu- midiQing performance of the cooling coil would be even worse, as it is likely to result in elevated humidity levels in the air distribution systems and the occupied zones (Se
6、khar et al. 1989). This phenomenon could be considered in the context of humidity as an “indoor” pollutant, which propagates the origin and sustenance of microbial contamination. The issue of high indoor humidity levels in tropical buildings originates from the high ambient humidity levels in the ve
7、ntilation air (outdoor air) and the need to provide adequate ventilation to avoid prob- lems associated with “sick building syndrome.” Therefore, the fundamental objective is to provide an air-conditioning system with superor indoor environmental performance that is achieved in an energy-efficient m
8、anner. S.C. Sekhar is an associate professor, Uma Maheswaran is a research scholar, and K.W. Tham and K.W. Cheong are associate professors in the Department of Building, National University of Singapore. 204 02004 ACHRAE. In the design of ventilation systems, it is not sufficient to ensure an adequa
9、te provision of total outdoor air quantity at the outdoor air intake of an air-handling unit (AHU), but it is equally important to consider the related ventilation charac- teristics. It is essential that the outdoor air reach the localized “breathing zone” of the various occupied zones served by the
10、 particular AHU in the correct proportion and maintain the desirable local air exchange effectiveness characteristics at all times. As the occupancy profile in the various localized zones of an indoor environment can change quite significantly during the course of operation of an AHU on a daily basi
11、s, it becomes necessary to incorporate the response of ventilation systems to such dynamically changing profiles to ensure adequate ventilation provision at all times without excessive energy consumption. Conventional designs of air-condition- ing and mechanical ventilation systems resort to mixing
12、of the centralized outdoor air intake and the recirculated air before being treated by the cooling coil and subsequently distributed to the various occupied zones as “mixed air.” The disadvantage of such designs, particularly with VAV systems, is fairly well established, resulting in complaints of i
13、nadequate ventilation, leading to perceptions of staleness and stuffiness. Such complaints are inevitable due to the inability of these typical designs of VAV systems to maintain adequate outdoor air distribution to the dynamically changing occupancy and “other” space load profiles, as any reduction
14、 of total supply air flow results in a reduction of outdoor air quantity. Demand-controlled ventilation (DCV) strategies are potential solutions in addressing issues related to inadequate ventilation. One of the studies has shown that energy savings from DCV control approaches ranged from 5% to 80%
15、in comparison to fixed ventilation strategy (Emmerich and Pers- ily 1997). A CO, sensor will consider the contribution of infil- tration in a space and only require the mechanical system to make up what is necessary to meet the required ventilation, and this would add on to the savings (Schell and I
16、nt-Hout 200 1). Under unpredictable and varying human occupancy conditions, CO, sensor-based DCV strategy has been shown to have an energy savings potential of up to 50%, (Fisk and Almeida, 1998). Proper distribution of ventilation air to the space is a func- tion of VAV boxes minimum settings, spac
17、e sensible loads, local exhaust and exfiltration, short circuiting paths, and inter- zonal air transfer (Mumma and Lee 1998). When the multiple spaces equation of ASHRAE Standard 62-2001 is used, gener- ally 20% to 70% more outdoor air is required in an effort to ensure proper ventilation air distri
18、bution in all air systems than is required with dedicated outdoor air systems (ASHRAE 2001). The inability to decouple the space sensible and latent loads to high space relative humidity at low sensible loads in the occupied spaces is yet another concern in any typical conventional system. These ina
19、bilities found their solution through having separate outdoor air systems to handle space latent loads as well as the varying ventilation requirements. Research attempts on the use of a separate outdoor air system started with Meckler in 1986, and subsequent works were carried out by Scofield and De
20、s Champs (1993), Brady (1 997), Mumma and Lee (1 998), and others. A dedicated outdoor air system (DOAS) is a 100% outdoor air, constant volume system designed to deliver the volumetric flow rate of venti- lation air to each conditioned space. It is used to place the required and conditioned ventila
21、tion air directly into the space without first mixing it with stale building air as is the current practice, thus always meeting the requirements of ASHRAE Standard 62. A general layout of the DOAS, consisting of a preheat coil, an enthalpy wheel, a deep cooling coil, a sensible heat exchanger, and
22、the prime movers, has been discussed by Mumma and Shank (2001). Conventional air conditioning and air distribution systems seldom consider the relative importance of the follow- ing two components of the conditioned air: the primary outdoor air required for ventilation the secondary recirculated air
23、 required for offsetting thermal loads As the function of each of the above two components is quite different from each other, and as each component is affected by different factors, it is logical to treat them as two separate airstreams. The notion of separate airstreams involv- ing dual-duct conce
24、pt typically consists of hot and cold airstreams. The concept of dual-duct air-conditioning systems is well established from the perspective of better thermal conditions in the occupied zones. Simulation results of a large retail store using a dual-duct system in comparison with a conventional singl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE47132004DEVELOPMENTOFENERGYEFFICIENTSINGLECOILTWINFANAIRCONDITIONINGSYSTEMWITHZONALVENTILATIONCONTROL

链接地址:http://www.mydoc123.com/p-454296.html