1、*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 76 (August 2011)-Preparing Activity: USACE SupersedingUFGS-28 31 76 (November 2008)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated October 2011*SECTION TABLE OF CONTENTSDIVISION 28 - ELECTRONIC SAFETY AND SECURITYSECTION 2
2、8 31 76INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM08/11PART 1 GENERAL1.1 RELATED SECTIONS1.2 REFERENCES1.3 DEFINITIONS1.4 SYSTEM DESCRIPTION1.4.1 Scope1.4.2 Technical Data and Computer Software1.4.3 Keys1.5 SUBMITTALS1.6 QUALITY ASSURANCE1.6.1 Qualifications1.6.1.1 Design Services1.6.1.2 Superv
3、isor1.6.1.3 Technician1.6.1.4 Installer1.6.1.5 Test Personnel1.6.1.6 Manufacturers Representative1.6.1.7 Manufacturer1.6.2 Regulatory Requirements1.6.2.1 Requirements for Fire Protection Service1.6.2.2 Fire Alarm/Mass Notification System1.6.2.3 Fire alarm Testing Services or Laboratories1.7 DELIVERY
4、, STORAGE, AND HANDLING1.8 OPERATION AND MAINTENANCE (O R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power CircuitsIEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power CircuitsSECTION 28 31 76 Page 7Provided
5、by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)IEC 60268-16 (2003) Sound System Equipment - Part 16: Objective Rating Of Speech Intelligibility By Speech Transmission Index; Ed 3.0INTERNATIONAL ORGANIZATION FOR
6、STANDARDIZATION (ISO)ISO 7240-16 (2007) Fire Detection And Alarm Systems Part 16: Sound System Control And Indicating EquipmentISO 7240-19 (2007) Fire Detection and Alarm Systems Part 19: Design, Installation, Commissioning and Service of Sound Systems for Emergency PurposesNATIONAL FIRE PROTECTION
7、ASSOCIATION (NFPA)NFPA 170 (2009; Errata 2011) Standard for Fire Safety and Emergency SymbolsNFPA 70 (2011; TIA 11-1; Errata 2011) National Electrical CodeNFPA 72 (2010; TIA 10-4) National Fire Alarm and Signaling CodeNFPA 90A (2009; Errata 09-1) Standard for the Installation of Air Conditioning and
8、 Ventilating SystemsU.S. DEPARTMENT OF DEFENSE (DOD)UFC 3-601-02 (2010) Operations and Maintenance: Inspection, Testing, and Maintenance of Fire Protection SystemsUFC 4-021-01 (2008; Change 1 2010) Design and O Reprint Jun 2010) Standard for Speakers for Fire Alarm, Emergency, and Commercial and Pro
9、fessional UseUL 1638 (2001; Reprint Oct 2008) Visual Signaling Appliances - Private Mode Emergency and General Utility SignalingUL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing ImpairedSECTION 28 31 76 Page 8Provided by IHSNot for ResaleNo reproduction or networking permitted witho
10、ut license from IHS-,-,-UL 2017 (2008; Reprint May 2011) General-Purpose Signaling Devices and SystemsUL 268 (2009) Smoke Detectors for Fire Alarm SystemsUL 464 (2009; Reprint Jan 2011) Standard for Audible Signal AppliancesUL 521 (1999; Reprint May 2010) Heat Detectors for Fire Protective Signaling
11、 SystemsUL 864 (2003; Reprint Jan 20110) Standard for Control Units and Accessories for Fire Alarm SystemsUL Electrical Constructn (2009) Electrical Construction Equipment DirectoryUL Fire Prot Dir (2011) Fire Protection Equipment Directory1.3 DEFINITIONSWherever mentioned in this specification or o
12、n the drawings, the equipment, devices, and functions shall be defined as follows:a. Interface Device: An addressable device that interconnects hard wired systems or devices to an analog/addressable system.b. Remote Fire Alarm and Mass Notification Control Unit: A control panel, electronically remot
13、e from the fire alarm and mass notification control panel, that receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devi
14、ces connected to the control unit; and reports to and receives signals from the fire alarm control panel.c. Fire Alarm Control Unit and Mass Notification Autonomous Control Unit (FMCP): A master control panel having the features of a fire alarm and mass notification control unit and fire alarm and m
15、ass notification control units are interconnected. The panel has central processing, memory, input and output terminals, and LCD, LED Display units d. Local Operating Console (LOC): A unit designed to allow emergency responders and/or building occupants to operate the MNS including delivery or recor
16、ded and/or live messages, initiate strobe and textural visible appliance operation and other relayed functions.e. Terminal Cabinet: A steel cabinet with locking, hinge-mounted door that terminal strips are securely mounted.1.4 SYSTEM DESCRIPTION1.4.1 Scope*NOTE: Indicate the location of fire alarm a
17、nd mass SECTION 28 31 76 Page 9Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-notification system devices and riser locations on floor plans. Provide a fire alarm and mass notification system riser diagram indicating circuits and risers.*a. This wor
18、k includes completion of design and providing a new, complete, and modifying the existing fire alarm and mass notification system as described herein and on the contract drawings for the building name. Include in the system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes,
19、control equipment, alarm, and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, and other accessories and miscellaneous items required for a complete operating system even though each item is not specifically mentioned or describ
20、ed. Provide systems complete and ready for operation.b. Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with the required and advisory provisions of NFPA 72, ISO 7240-16, IEC 60268-16, except as modified herein. The system layout on the drawings
21、show the intent of coverage and are shown in suggested locations. Submit plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each conduit, and circuit layouts for all floors. Drawings
22、 shall comply with the requirements of NFPA 170. Final quantity, system layout, and coordination are the responsibility of the Contractor.A single fire alarm control panel is indicated with terminal cabinets at each floor, at each riser location.c. Where remote fire alarm control units are needed, t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYUFGS2831762011INTERIORFIREALARMANDMASSNOTIFICATIONSYSTEMPDF

链接地址:http://www.mydoc123.com/p-449679.html