AIR FORCE A-A-59915-2012 CONVERTER FREQUENCY ELECTRONIC SOLID-STATE 25 kVA 400 Hz.pdf
《AIR FORCE A-A-59915-2012 CONVERTER FREQUENCY ELECTRONIC SOLID-STATE 25 kVA 400 Hz.pdf》由会员分享,可在线阅读,更多相关《AIR FORCE A-A-59915-2012 CONVERTER FREQUENCY ELECTRONIC SOLID-STATE 25 kVA 400 Hz.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、 Comments, suggestions, or questions on this document should be addressed to: Support Equipment distribution is unlimited. A-A-59915 30 October 2012 COMMERCIAL ITEM DESCRIPTION CONVERTER, FREQUENCY, ELECTRONIC, SOLID-STATE 25 kVA, 400 Hz The General Services Administration has authorized the use of
2、this Commercial Item Description for all federal agencies. 1. SCOPE. This Commercial Item Description (CID) describes a 25 kilovolt-ampere (kVA), Solid-State Frequency Converter herein referred to as the SSFC. The SSFC has a 115/200 volt, 400 Hertz (Hz) output rating to provide power for various air
3、craft maintenance tasks as commonly encountered in avionics backshop environments. 2. SALIENT CHARACTERISTICS 2.1 Safety and environmental. The equipment shall meet all safety and environmental requirements as specified in National Fire Protection Association (NFPA) 70 National Electrical Code (NEC)
4、, ANSI/IEEE C2 National Electrical Safety Code, and the latest applicable National Electrical Manufacturers Association (NEMA) standards except as stated herein. 2.2 Component protection. All space in which work is performed during operation, service, and maintenance shall be free of hazardous protr
5、usions, sharp edges, or other features which may cause injury to personnel. All rotating and reciprocating parts and all parts subject to high operational temperatures or subject to being electrically energized, that are of such nature or so located as to be hazardous to personnel, shall be guarded
6、or insulated to eliminate the hazard. All wires, cables, tubes, and hoses shall be supported and protected to minimize chafing and abrasion and shall be located so as to provide adequate clearance from moving parts and high operational temperatures. Grommets shall be provided wherever wires, cables,
7、 tubes, or hoses pass through bulkheads, partitions, or structural members. INCH-POUND Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59915 2 2.3 Design and construction. The SSFC shall be a stand-alone, self-contained unit capable of converting
8、 three phase 50 and 60 Hz Alternating Current (AC) facility electrical power into 115/200 volt 3-phase electrical power at 400 Hz. The SSFC shall accept any power input specified herein; all SSFC operating power shall be derived from the input power source. The SSFC shall be constructed of modular a
9、nd easily replaceable subassemblies and components wherever possible. The SSFC enclosure shall have doors or covers to provide access for maintenance, repair, and replacement of components and subassemblies. All doors shall be vertically hinged and equipped with hold-open devices for satisfactory us
10、e in high wind and jet blast areas. Removable panels, if provided, shall be attached with captive fasteners. The SSFC shall be Underwriters Laboratory (UL) 1012 listed. The SSFC shall be designed and constructed in accordance with all applicable European Union (EU) requirements in order to have the
11、“CE” marking affixed (see 2.6). The SSFC shall be able to withstand the strains, jars, vibrations, and other conditions indicative to shipping, storage, installation, and service. Additional features and capabilities shall be permitted unless otherwise prohibited by this document. 2.4 Foreign object
12、 damage (FOD). All loose metal parts, such as pins or connector covers, shall be securely attached to the SSFC with wire ropes or chains. “Dog tag“ style beaded chains shall not be provided. 2.5 Materials, protective coatings, and finish. 2.5.1 Protective coatings. Materials that deteriorate when ex
13、posed to sunlight, weather, or operational conditions normally encountered during the service life of the item shall not be used or shall have means of protection against such deterioration that does not prevent compliance with the performance requirements specified herein. Protective coatings that
14、chip, blister, crack, peel or scale with age or extremes of climatic conditions or when exposed to heat shall not be used. Fasteners, handles, and fittings used in the assembly of the item shall also be primed and painted unless they are specifically designed to resist corrosion and deterioration wi
15、thout paint. 2.5.1.1 Finish. The exterior finish color of the SSFC shall be Gray, Color Number 26173 of FED-STD-595. 2.5.1.2 Exclusion of water. The design of the SSFC shall be such as to prevent water leaking into, or being driven into, any part of the SSFC interior when either in an operating or t
16、ravelling configuration. All windows, doors, panels, covers, etc., shall be provided with sealing arrangements such that the entry of water is minimized when these items are correctly closed. Particular care shall be taken to prevent wetting of equipment and heat and sound proofing materials. Sharp
17、corners and recesses shall be avoided so that moisture and solid matter cannot accumulate to initiate localized attack. Sealed floors with suitable drainage shall be provided for storage compartments and other areas in the SSFC that could collect and retain water. 2.5.1.2.1 Fluid traps and faying su
18、rfaces. There shall be no fluid traps on the SSFC. Faying surfaces of all structural joints, except welded joints, shall be sealed to preclude fluid intrusion. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59915 3 2.5.1.2.2 Ventilation. Ventila
19、tion shall be sufficient to prevent moisture retention and buildup. 2.5.1.2.3 Drainage. Drain holes shall be provided to prevent collection or entrapment of water or other unwanted fluid in areas where exclusion is impractical. All designs shall include considerations for the prevention of water or
20、fluid entrapment and ensure that drain holes are located to effect maximum drainage of accumulated fluids. The number and location of drain holes shall be sufficient to permit drainage of all fluids when the unit is in a 3 degree incline in any plane. The minimum diameter of the drain holes shall be
21、 0.25 inch. 2.6 Identification and information plates and marking. An identification plate in accordance with MIL-STD-130 shall be securely attached to the SSFC in a readily accessible location. The identification plate shall contain the following information: Nomenclature, part number, serial numbe
22、r, date of manufacture, manufacturers name, Commercial and Government Entity (CAGE) code, date of warranty expiration, and National Stock Number (NSN). The SSFC and any of its components for which the Governments unit cost is more than $5,000, is serially managed, or the procuring agency determines
23、is mission essential, shall have Unique Identification (UID) (also known as Item Unique Identification (IUID) information permanently affixed on or near the respective identification plate(s), marked in accordance with MIL-STD-130. UID information shall be included as both a bar code and human reada
24、ble markings. The “CE” marking shall be affixed in accordance with EU requirements on or adjacent to the identification plate. All external devices and components which require operational or maintenance interface shall be marked using manufacturers standard markings. 2.7 Calibration and maintenance
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAA599152012CONVERTERFREQUENCYELECTRONICSOLIDSTATE25KVA400HZPDF

链接地址:http://www.mydoc123.com/p-427203.html