AIR FORCE A-A-59880-2010 LOAD BANK ELECTRICAL 160 kilowatts 60 Hertz《160kW 60 HZ电气负荷组》.pdf
《AIR FORCE A-A-59880-2010 LOAD BANK ELECTRICAL 160 kilowatts 60 Hertz《160kW 60 HZ电气负荷组》.pdf》由会员分享,可在线阅读,更多相关《AIR FORCE A-A-59880-2010 LOAD BANK ELECTRICAL 160 kilowatts 60 Hertz《160kW 60 HZ电气负荷组》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any data that may improve this document should be sent to: WR-ALC/GRVEA, Robins AFB GA 31098-1813. Since contact information can change, you may want to verify the currency of this address information using the ASSI
2、ST Online database at https:/assist.daps.dla.mil/online . FSC 6625 INCH-POUNDA-A-59880 23 Nov 2010 COMMERCIAL ITEM DESCRIPTION LOAD BANK, ELECTRICAL 160 kilowatts, 60 Hertz The General Services Administration has authorized the use of this commercial item description for all federal agencies. 1. SCO
3、PE. This Commercial Item Description (CID) describes an alternating current (AC), 160 kilowatt (kW), 60 Hertz (Hz) portable type, resistive load bank and accessories. The commercially available, portable, enclosed, forced air cooled, industrial load bank is used for electrical performance testing of
4、 tactical power generators and other 60 Hz generator and power supply systems used for ground-based power operations. 2. SALIENT CHARACTERISTICS 2.1 Safety and environmental. The equipment shall meet all safety and environmental requirements as specified in National Fire Protection Association (NFPA
5、) 70 National Electrical Code (NEC), ANSI/IEEE C2 National Electrical Safety Code and the latest applicable National Electrical Manufacturers Association (NEMA) standards except as stated herein. All resistive load element buses shall be over-current protected. Air flow failure shall cause the load
6、bank to automatically drop all connected load before an over-temperature condition occurs. 2.2 Electrical power sources. The load bank shall be completely self-contained to include all controls, connection points, instrumentation, load elements and system protective devices. The operating power for
7、internal circuits, instruments, and fan(s) shall be user selectable between being derived only from the power source under test, or from an external power source. All controls shall be located on a local control panel. 2.3 Operating temperature. The equipment shall meet its performance and accuracy
8、requirements in an operating environment of -20 degrees F to +125 degrees F. 2.4 Non-operating temperature. The equipment shall meet its performance and accuracy requirements (see 2.8.1.1) after being in a non-operating environment (Storage Temperature) of -65 degrees F to +160 degrees F. Provided b
9、y IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59880 2 2.5 Calibration and maintenance adjustments. The design of the system shall provide for readily accessible calibration adjustments and maintenance adjustments. The calibration adjustments, wherever po
10、ssible, shall be accessible without removal of the instrument case or modules. These adjustments shall be provided by variable value components. The calibration by substitution of selected components or parts is unacceptable unless specifically approved. The calibration interval shall be a period of
11、 one year or greater based on an operating time of 2,000 hours. 2.6 Accessories. Accessories to be supplied by the manufacturer with each deliverable load bank shall include standard and optional accessories as provided by the manufacturer and listed in the manufacturers catalog or data sheet. A wri
12、tten users manual, a written programmer reference manual (if applicable), and a traceable calibration certificate shall also be provided with each load bank unit. The user manual(s) shall include complete details for the operation, troubleshooting and maintenance of the load bank and shall include i
13、nterconnect drawings and electrical schematics for all power and control circuits and devices. A complete parts listing shall be delivered with each load bank and shall include, at a minimum, the original manufacturers name, part number, rating, identification and quantity required. 2.7 Environmenta
14、l requirements. The load bank shall be designed for indoor or sheltered use and indoor storage. The load bank shall be clearly marked “NOT FOR USE IN HAZARDOUS LOCATIONS”. 2.8 Performance characteristics. The load bank shall be capable of continuous, resistive load testing of ground power generator
15、sets by providing loads ranging from 0 to not less than 160 kW load at 240 and 480 volts AC, 3 phase, 4 wire, 60 Hz. The load bank shall also be capable of providing loads ranging from 0 to not less than 120 kW at 208 and 416 volts AC, 3 phase, 4 wire, 60 Hz. 2.8.1 Controls. The load bank shall incl
16、ude a local operator control panel containing all meters, switches, alarms, indicators and instructions necessary for the proper operation of the load bank. A latching, hinged cover assembly shall be provided to protect the control panel from damage when not in use. 2.8.1.1 Meters. The control panel
17、 of the load bank shall be equipped with individual meters for monitoring voltage (0-600 volts AC), frequency (45-65 Hz), and current (0-400 amps AC). Meter accuracy shall be within 3%, full scale. 2.8.1.2 Phase selector switch. The load bank shall have a phase selector switch on the control panel f
18、or measuring the current of each phase of incoming power (A, B, C). Voltage measurements shall be selectable for line-to-line for each phase on incoming power. 2.8.2 AC input connections. The load bank input shall be equipped with portable power cables rated for extra hard usage and capable of conti
19、nuously carrying the load banks rated full load current. Input power cable length shall not be less than fifteen (15) feet per phase conductor with terminal lugs on the ends for connection to power supply studs. External control power or cooling fan power input cable shall be designed for 120 volts
20、AC, 60 Hz, single phase, be provided with a properly rated input connector, be rated for extra hard usage and be not less than Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-59880 3 15 feet in length. All input cables shall be highly flexible co
21、pper conductor and rated for 600 volts minimum. Input power cable storage shall be provided on the load bank. 2.8.3 Load elements. The load bank load elements shall be of the purely resistive type and shall be designed so that a load of any magnitude within the range of one to 160 kW may be absorbed
22、. Load elements shall be protected from damage per NEC article 110-10 by the use of user resettable circuit breakers, user replaceable fuses, or automatically resetting thermal switches. All load elements shall be connectable to incoming power by means of electrical contactors. Load balance shall be
23、 within +/- 2.5% between phases. 2.8.4 Step loading. The load bank shall provide a means to apply incremental loading (step loading). The following load steps should be available (at a minimum): 1kw, 2kw, 5kw, 10kw, 20kw and 50kw. The use of multiple load steps of the same size is acceptable. Load s
24、teps of a different resolution may be acceptable, based upon Government review. The tolerance of each load step shall be no more than 5%. These loads shall be selectable individually or in combinations to provide loads up to and including 160 kW. 2.8.5 Shock loading. The load bank shall have a singl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AIRFORCEAA598802010LOADBANKELECTRICAL160KILOWATTS60HERTZ160KW60HZ 电气 负荷 PDF

链接地址:http://www.mydoc123.com/p-427195.html