AHRI 580-2014 Performance Rating of Non-condensable Gas Purge Equipment For Use with Low Pressure Centrifugal Liquid Chillers.pdf
《AHRI 580-2014 Performance Rating of Non-condensable Gas Purge Equipment For Use with Low Pressure Centrifugal Liquid Chillers.pdf》由会员分享,可在线阅读,更多相关《AHRI 580-2014 Performance Rating of Non-condensable Gas Purge Equipment For Use with Low Pressure Centrifugal Liquid Chillers.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、 AHRI Standard 580 2014 Standard for Performance Rating of Non-condensable Gas Purge Equipment For Use with Low Pressure Centrifugal Liquid Chillers Price $10.00 (M) $20.00 (NM) Copyright 2014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U.S.A. Registered United States Paten
2、t and Trademark Office IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that product
3、s be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepte
4、d industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes AHRI Standard 580-2009. AHRI CERTIFICATION PROGRAM PROVISIONS Scope of the Certification Program The Certification
5、Program includes testing purge systems used in conjunction with Low Pressure Centrifugal Liquid Chillers. Certified Ratings The following Certification Program ratings are verified by test: 1. Concentration, ratio of mass of refrigerant to mass of air, g of refrigerant / g of air. TABLE OF CONTENTS
6、SECTION PAGE Section 1. Purpose 1 Section 2. Scope .1 Section 3. Definitions .1 Section 4. Test Requirements .2 Section 5. Rating Requirements .2 Section 6. Minimum Data Requirements for Published Ratings 3 Section 7. Marking and Nameplate Data 3 Section 8. Conformance Conditions .3 APPENDICES Appen
7、dix A. References Normative 4 Appendix B. References Informative 4 Appendix C. Methods of Testing for Rating Performance of Non-condensable Gas Purge Equipment Normative 5 Appendix D. Specific Rating and Testing Instructions for Purges Containing Adsorptive/Absorptive Media Normative10 Appendix E. C
8、alculation of Purge Equipment Concentration Rating for the Activated Carbon Method - Normative 12 Appendix F. Determination of Discharge Gas Concentration for Non-condensable Gas Purge Equipment Testing Normative .13 FIGURES FOR APPENDICES Figure C1. Activated Carbon Sampling Method .7 Figure C2. Ga
9、s Chromatograph Sampling Method .8 AHRI STANDARD 580-2014 1 NON-CONDENSABLE GAS PURGE EQUIPMENT FOR USE WITH LOW PRESSURE CENTRIFUGAL LIQUID CHILLERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for Non-condensable Gas Purge Equipment for use with Low Pressure Centrif
10、ugal Liquid Chillers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers
11、, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to Non-condensable Gas Purge Equipment for use with Low Pressure Centrifugal Liquid Chillers as defined in Section 3. This s
12、tandard defines general equipment requirements, test methods and analysis techniques used to determine the performance rating for Purge Equipment that removes Non-condensable gases from Low Pressure Centrifugal Liquid Chillers. This purge equipment is typically used in conjunction with chillers whic
13、h operate with at least a portion of the system below atmospheric pressure. Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Terminology website (https:/www.ashrae.org/resources-publications/free-resources/ashrae-terminology) unless otherw
14、ise defined in this section. 3.1 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.2 Concentration. Ratio of the mass of refrigerant to the mass of air at the Refrigerant Holding Capacity. 3.3 Dew Point. Refrigerant vapor saturation temperature at a specified pressur
15、e. 3.4 Low Pressure Centrifugal Liquid Chiller. A centrifugal liquid chiller that typically has a portion of the refrigerating system below atmospheric pressure (100 kPa) when operated at typical conditions for comfort cooling applications. 3.5 Non-condensable Gases. Gases, such as nitrogen and oxyg
16、en. which do not condense at normal operating temperatures and pressures in centrifugal water-chiller condensers. 3.6 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These
17、 values apply to all units of like nominal size and type (identification) produced by the same manufacturer. As used herein, the term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled b
18、y the manufacturer, at stated Rating Conditions. 3.6.1 Application Rating. A rating based on tests performed at Application Rating Conditions (other than Standard Rating Conditions). 3.6.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. AHRI STANDARD 580-2014 2 3.7
19、Purge Equipment. A device which will separate Non-condensable Gases from refrigerant and remove them from the refrigeration system. 3.7.1 Automatically Regenerated Media. Media that is recycled at the purge system to remove entrained refrigerant and return this refrigerant to the chiller. The regene
20、ration process is initiated automatically by the purge control system. 3.7.2 Manually Regenerated Media. Media that is recycled at the purge system to remove entrained refrigerant and return this refrigerant to the chiller. The regeneration process is set up and initiated by an operator. 3.7.3 Refri
21、gerant Holding Capacity. The amount of refrigerant, designated by the manufacturer, which the media can hold prior to being replaced or regenerated, g. 3.7.4 Replaceable Media. Media that is removed from the system and replaced with new or recycled media. The media from the system is processed to en
22、sure refrigerant is not released to the atmosphere. 3.8 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.8.1 Standard Rating Conditions. Rating Conditions used as the basis for comparison
23、of performance characteristics. 3.9 “Shall“ or “Should.” “Shall“ or “should“ shall be interpreted as follows: 3.9.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.9.2 Should. “Should“ is used to indicat
24、e provisions which are not mandatory but which are desirable as good practice. Section 4. Test Requirements 4.1 Test Requirements. Non-condensable Gas Purge Equipment shall be tested in accordance with the procedures set forth in Appendices C and D. Calculation of purge equipment concentration ratin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI5802014PERFORMANCERATINGOFNONCONDENSABLEGASPURGEEQUIPMENTFORUSEWITHLOWPRESSURECENTRIFUGALLIQUIDCHILLERSPDF

链接地址:http://www.mydoc123.com/p-422555.html