AHRI 571 SI-2012 Performance Rating of Positive Displacement Carbon Dioxide Refrigerant Compressors and Compressor Units.pdf
《AHRI 571 SI-2012 Performance Rating of Positive Displacement Carbon Dioxide Refrigerant Compressors and Compressor Units.pdf》由会员分享,可在线阅读,更多相关《AHRI 571 SI-2012 Performance Rating of Positive Displacement Carbon Dioxide Refrigerant Compressors and Compressor Units.pdf(30页珍藏版)》请在麦多课文档分享上搜索。
1、 2012 Standard for Performance Rating of Positive Displacement Carbon Dioxide Refrigerant Compressors and Compressor Units AHRI Standard 571 (SI) Price $10.00 (M) $20.00 (NM) Copyright 2012, by Air-Conditioning, Heating and Refrigeration Institute Printed in U.S.A. Registered United States Patent an
2、d Trademark Office IMPORTANT SAFETY RECOMMENDATIONS AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that produc
3、ts be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accept
4、ed industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. This standard is a new standard. For I-P ratings, see AHRI Standard 570 (I-P)-2012. TABLE OF CONTENTS SECTION PAGE Section 1. Purpose .1 Section
5、2. Scope 1 Section 3. Definitions1 Section 4. Test Requirements .3 Section 5. Rating Requirements 3 Section 6. Minimum Data Requirements for Published Ratings 4 Section 7. Operating Requirements 6 Section 8. Marking and Nameplate Data 6 Section 9. Conformance Conditions .6 TABLES Table 1. Standard R
6、ating Conditions for CO2Compressors and Compressor Units for Refrigeration Applications 7 APPENDICES Appendix A. References Normative .8 Appendix B. References Informative .8 Appendix C. Method of Test for Transcritical and Two Stage Subcritical Cycles Normative 9 FIGURES FOR APPENDICES Figure C1. S
7、ingle Stage Refrigeration Cycle Schematic with Thermodynamic State Point Numbers .10 Figure C2. Single Stage Pressure Versus Enthalpy Diagram for the Refrigeration Cycle Shown in Figure C1 .11 Figure C3. Two Stage Refrigeration Cycle Schematic with Thermodynamic State Point Numbers 11 Figure C4. Two
8、 Stage Pressure Versus Enthalpy Diagram for the Refrigeration Cycle Shown in Figure C3 .12 Figure C5. Cycle Process for Subcritical Applications (AHRI Standard 571 Method 1) 22 Figure C6. Cycle Process for Transcritical Applications (AHRI Standard 571 Method 1).23 Figure C7. Cycle Process for Subcri
9、tical Application for Compressor Units with Manufacturer Specified or Supplied Subcoolers (AHRI Standard 571 Method 2) 23 Figure C8. Cycle Process for Transcritical Application for Compressor Units with Manufacturer Specified or Supplied Subcoolers (AHRI Standard 571 Method 2) .24 Figure C9. Cycle P
10、rocess for Subcritical Application for Compressors Applied with Non-Specified Subcoolers (AHRI Standard 571 Method 3) .24 Figure C10. Cycle Process for Transcritical Application for Compressors Applied with Non-Specified Subcoolers (AHRI Standard 571 Method 3) .25 Figure C11. Cycle Process for Subcr
11、itical Applications for Compressors and Compressor Units Applied with Open Flash Style Liquid Subcoolers (AHRI Standard 571 Method 4) .25 Figure C12. Cycle Process for Transcritical Applications for Compressors and Compressor Units Applied with Open Flash Style Liquid Subcoolers (AHRI Standard 571 M
12、ethod 4) .26 AHRI STANDARD 571 (SI)-2012 1 PERFORMANCE RATING OF POSITIVE DISPLACEMENT CARBON DIOXIDE REFRIGERANT COMPRESSORS AND COMPRESSOR UNITS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish for positive displacement carbon dioxide refrigerant compressors and compres
13、sor units: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers
14、, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to electric motor driven, single and variable capacity, single and two stage Positive Displacement Refrigerant C
15、ompressors and Compressor Units operating with carbon dioxide in both Subcritical and Transcritical applications for refrigeration. This standard also applies to the presentation of performance data for Positive Displacement Compressors and Compressor Units operating with carbon dioxide. 2.1.1 Refri
16、gerant. The rating points in this standard are based on R-744 (carbon dioxide). 2.2 Exclusions. 2.2.1 This standard does not apply to compressors and compressor units intended for use in: 2.2.1.1 Household refrigerators and freezers 2.2.1.2 Automotive air-conditioners 2.2.1.3 Dehumidifiers 2.2.1.4 I
17、ndustrial products other than heating and cooling 2.2.2 This standard does not apply to compressors that are coupled with condensers or gas cooler heat exchangers. 2.2.3 This standard does not apply to carbon dioxide compressors used in heat pump and air-conditioning applications. Section 3. Definit
18、ions All terms in this document will follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Coefficient of Performance (COP). A ratio of the cooling capacity in wa
19、tts (W) to the power input value in watts (W) at any given set of Rating Conditions expressed in watts/watt, W/W. 3.2 Compressor Efficiency or Compressor Unit Efficiency. A ratio of theoretical to actual power as defined in Appendix C. 3.3 Positive Displacement Refrigerant Compressor. A machine in w
20、hich an increase in refrigerant vapor pressure is attained by changing the internal volume of the compression chamber through work applied to the compressors mechanism. AHRI STANDARD 571 (SI)-2012 2 This shall include desuperheaters, head fans or other accessories required to sustain operation of th
21、e compressor at the Rating Conditions. 3.3.1 Hermetic Refrigerant Compressor. A compressor and motor assembly, both of which are enclosed in the same housing, with the motor operating in the refrigerant. 3.3.2 Semi-Hermetic Refrigerant Compressor. A compressor and motor assembly contained within a g
22、as-tight housing that contains sealed joints to provide access for servicing internal parts. 3.3.3 Open Drive Compressor. A refrigerant compressor with a shaft or other moving part extending through its casing to be driven by an external source of power. 3.4 Positive Displacement Refrigerant Compres
23、sor. A Positive Displacement Refrigerant Compressor(s) with accessories, such as condensers, gas coolers, interstage coolers, desuperheaters, head fans, strainers, service valves, check valves, suction filters, oil separators, external power source (for Open Drive Refrigerant Compressor), as provide
24、d by the manufacturer. This will also include variable capacity controls, electronic or electro-mechanical, as supplied or specified by the manufacturer. 3.5 Power Input. The time rate of energy usage of the compressor (compressor power) or compressor unit (compressor unit power). 3.6 Published Rati
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI571SI2012PERFORMANCERATINGOFPOSITIVEDISPLACEMENTCARBONDIOXIDEREFRIGERANTCOMPRESSORSANDCOMPRESSORUNITSPDF

链接地址:http://www.mydoc123.com/p-422553.html