1、Alternator Protection for Emergency Standby Engine Generators,Kenneth L. Box P.E. Regional Sales Manager Power Electronics Cummins Power Generation,Engine Generators,Control Monitoring & Alarms Engine Protection System Protection Paralleling Applications Alternator Protection,IEEE/ANSI Standards 141
2、 & 242,Recommended Practice for Protection & Coordination of Industrial & Commercial Power Systems Recommended Practice for Electric Power Distribution for Industrial Plants,Under & Over Voltage Protection,Protects against a severe overload condition (27) Initiates the starting of an emergency stand
3、by genset (27) Load shed shut down in the event of AVR failure (27) Protect against dangerous over-voltages (59) Backup to internal V/Hz limiters Commonly combined 27/59,Devices 27 59,Reverse Power Protection,Provides backup protection for the prime mover. It detects reverse power flow (kW) should t
4、he prime mover lose its input energy without tripping its generator feeder breaker Prevents motoring, drawing real power from the system,Device 32,Loss of Field Protection,Senses when the generators excitation system has been lost. Important for paralleling generator applications or when paralleling
5、 with the utility. When generator loses excitation it will steal excitation from other gensets & quickly overheat the rotor due to induced slip-frequency currents Reverse VAR protection,Device 40,Phase Balance Current Protection,Unbalanced loads Unbalanced system faults Open conductors Unbalanced I2
6、 currents induce 2X system frequency currents in the rotor causing overheating,Device 46,Backup Overcurrent Protection,The function of generator backup protection is to disconnect the generator if a system has not been cleared by the primary protective device Time delays,Device 51V,Ground Overcurren
7、t Protection,Provides backup protection for all ground relays in the system at the generator voltage level Provides protection against internal generator ground faults Commonly provided as GF alarm.,Device 51G,Voltage Balance Relay,Monitors the availability of PT voltage. Blocks improper operation o
8、f protective relays and control devices in the event of a blown PT fuse,Device 60,Differential Protection,For rapid detection of generator to or -G faults. When NGRs are used, 87G should be used. Used for protection of larger generators Zone protection,Device 87,Temperature Protection,Resistance tem
9、perature detectors are used to sense winding temperatures. A long term monitoring philosophy that is not readily detected by other protective devices,RTDs,IEEE Recommended Protection Schemes,SMALL MACHINES Up to 1000kVA, 600V maximum MEDIUM MACHINES 1000kW to 12,500 kVA regardless of voltage LARGE M
10、ACHINES Up to 50,000 kVA regardless of voltage,Any recommendation based entirely on machine size is not entirely adequate. The importance of the machine to the system or process it serves & the reliability required are the important factors,Small Generators 1000kVA,Device 51V Backup overcurrent Devi
11、ce 51G - GFP Device 32 Reverse Power Device 40 Loss of Field Device 87 - Differential,Medium Size Generators 1 to 12.5 mVA,Device 51V Backup overcurrent Device 51G - GFP Device 32 Reverse Power Device 40 Loss of Field Device 87 - Differential Device 46 Negative phase sequence for paralleling or util
12、ity paralleling,My Opinion 3mW and less,TRIP,NFPA70 - NEC,445.12(A) Overload Protection Generators, except AC generator exciters, shall be protected from overloads by inherent design, circuit breakers, fuses, or other acceptable overcurrent protective means suitable for the conditions of use. 240.15
13、(A) Overcurrent Device Required. A fuse or an overcurrent trip unit of a circuit breaker shall be connected in series with each ungrounded conductor. A combination of a current transformer and overcurrent relay shall be considered equivalent to an overcurrent trip unit. 240.21(G) Conductors from Gen
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ALTERNATORPROTECTIONFOREMERGENCYSTANDBYENGINEPPT

链接地址:http://www.mydoc123.com/p-378227.html