HD 586 2 S1-1994 Mineral Insulated Cables with a Rated Voltage not Exceeding 750 V Part 2 Terminations《额定电压不超过750 V的矿物绝缘电缆 第2部分 终端 由EN 60702-2-2002替代》.pdf
《HD 586 2 S1-1994 Mineral Insulated Cables with a Rated Voltage not Exceeding 750 V Part 2 Terminations《额定电压不超过750 V的矿物绝缘电缆 第2部分 终端 由EN 60702-2-2002替代》.pdf》由会员分享,可在线阅读,更多相关《HD 586 2 S1-1994 Mineral Insulated Cables with a Rated Voltage not Exceeding 750 V Part 2 Terminations《额定电压不超过750 V的矿物绝缘电缆 第2部分 终端 由EN 60702-2-2002替代》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、1994-09-14 . Tel.: (+32 2) 519 138 71 - Fax: +32 2) 519 69 19 I HO 586.2 Si September 1994 CE F LEC - Rue de Stassart 35 - B - 1050 Bruxelles Mineral insulated cables with a rated voltage not exceeding 750 V Part 2: Terminations SHEET INFORMATION Cibles i isolant minral, de tension assignee ne dpass
2、ant pas 750 V Partie 2: Extrmits Hineralisolierte Leitungen mit einer Nennspannung bis 750 V Teil 2: Endverschlusse Related to Directive: 73/23/EEC This Harmonization Oocument consists of the following: - Title Page - Text prepared by CENELEC Technical Cornittee TC 20 date of ratification : 1994-03-
3、08 date of announcement : 1994-10-01 date of withdrawal : 1995-04-01 date of latest publication : 1995-04-01 LIST OF NATIONAL STANDARDS, IF ANY, IS GIVEN OVERLEAF * HARMONIZATION DOCUMENT .DOCUflENT DHARMONISATION HARMONISIERUNGSDOKUflENT HD 586.2 S1 September 1994 UDC 621.315.687.3:621.315.2:621.31
4、5.613 Descriptors: Termination, electric cable, insulated cable, solid electric insulation, specification, dimension. test ENGLISH VERSION Mineral insulated cables with a rated voltage not exceeding 750 V Part 2: Terminations Cibles a isolant mineral, de tension assignee ne dpassant pas 750 V Partie
5、 2: Extrmits Mineralisolierte Leitungen mit einer Nennspannung bis 750 V Teil 2: Endverschlsse This Harmonization Document was approved by CENELEC on 1994-03-08. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this Ha
6、rmonization Document on a national level. Up-to-date lists and bibliographical references concerning national implementation may be obtained on application to the Central Secretariat or to any CENELEC member. This Harmonization Document exists in three official versions (English, French, German 1. C
7、ENELEC members are the national electrotechnical committees of Austria, Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom. CENELEC European Committee for Electrotechnical Standardizati
8、on Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, 8-1050 Brussels 1994 Copyright reserved to CENELEC members Ref, No. HD 586.2 S1:1994 E = 3404583 0143b80 bb7 Page 2 HD 586.2 S1:1994 FOREWORD This Harmonizatio
9、n Document was prepared by CENELEC Technical Committee TC 20, Electric cables. It was submitted to the CENELEC Unique Acceptance Procedure (UAP) in May 1993 and was approved by CENELEC as HD 586.2 S1 on 1994-03-08. The following dates were fixed: - latest date of announcement of the HD at national l
10、evel (doa) 1994-10-01 - latest date of publication of a harmonized national standard (dop) 1995-04-01 - latest date of withdrawal of conflicting national standards (daw) 1995-04-01 For products which have complied with the relevant national standard before 1995-04-01, as shown by the manufacturer or
11、 by a certification body, this previous standard may continue to apply for production until 1996-04-01. This Part 2 of HD 586 is to be used in conjunction with HD 586.1 S1:1994. Page 3 HD 586.2 S1 :1994 CONTENTS 1. Scope 2. Definitions 2.1 Termination 2.2 Seal 2.3 Gland 3. Marking 3.1 Marking of pac
12、kages 3.2 Marking of seals and glands 4. Construction 4.1 Seals 4.2 Glands 5. Type tests 5.1 General 5.2 Seals 5.3 Glands 5.4 Electrical earth continuity test Page 4 4 4 4 4 4 5 5 3404583 0343682 43T Page 4 HD 586.2 S1:1994 1. ScoDe This standard specifies requirements for terminations for use with
13、mineral insulated cables complying with the requirements of CENELEC harmonised publication HD 586.1 . 2. Definitions The following definitions apply for the purpose of this standard. 2.1 Termination A complete end fitting for a mineral insulated cable, normally comprising a seal and a gland or a com
14、posite seal/gland device, but excluding the locknut and any associated junction box or accessory. 2.2 Seal The part of a termination designed to seal the end of the cable against entry of moisture. The design must be such as to provide insulation between conductors and between conductors and sheath
15、and provide conductor insulation external to the seal. It may also have a means of providing a protective conductor. 2.3 Gland The part of a termination designed to secure the cable in a cable entry. It may or may not be used to ensure earth continuity depending upon the type of construction and mat
16、erial used. 3. Markincl 3.1 Marking of packages Packages in which terminations or parts of terminations are supplied shall be marked with the following particulars if applicable. The manufacturer or supplier. The maximum and minimum operating temperature of the seals. A mark or means of identifying
17、the cables or cables for which it is intended. Whether a protective conductor is provided. Gland thread form and size. 3.2 Marking of seals and glands Seals and glands shall be marked with a mark or means of identifying the cable or cables for which they are intended. In addition, glands certified f
18、or use in hazardous areas shall be marked in accordance with EN50 O1 4, O1 5, O1 6, O1 7, O1 8, O1 9, 020. Page 5 HD 586.2 S1:1994 4. Construction 4.1 Seals 4.1 .1 A seal shall consist of a moisture resistant material contained if necessary within a suitable enclosure, and shall provide electrical i
19、nsulation for the cable conductors. 4.1.2 A protective conductor may be connected to a metallic sealing enclosure by any suitable method (e.g. welding, brazing, crimping or soldering) or it may be connected directly to the metal sheath by any suitable attachment (e.g. clip or clamp). The site of the
20、 protective conductor shall be in accordance with publication HD 384 and the attachment shall meet the electrical continuity test requirement specified in sub-clause 5.4. 4.1.3 A seal for use in potentially explosive atmospheres shall comply with the requirements of this standard and the appropriate
21、 requirements specified in EN50 014, 015, 016, 017, 018, 019, 020. 4.1.4 A seal or enclosure shall be made from material which will ensure freedom from corrosion arising from electrolytic action. 4.1.5 The sealing material used in the termination shall be such that the completed seal is capable of m
22、eeting the test requirements specified in clause 5. 4.1.6 Sleeving for conductor insulation shall be suitable for the range of operating temperatures stated for the seal by the manufacturer. 4.2 Glands 4.2.1 4.2.2 4.2.3 4.2.4 5. TvDe tests 5.1 General A gland may be of any suitable material providin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- HD5862S11994MINERALINSULATEDCABLESWITHARATEDVOLTAGENOTEXCEEDING750VPART2TERMINATIONS 额定 电压 不超过 750 矿物

链接地址:http://www.mydoc123.com/p-1341430.html