1、10-11 08 90 00 - 1 SECTION 08 90 00 LOUVERS AND VENTS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies fixed and operable wall
2、louvers, door louvers and wall vents. 1.2 RELATED WORK A. Louvers in steel doors: Section 08 11 13, HOLLOW METAL DOORS AND FRAMES. B. Color of finish: Section 09 06 00, SCHEDULE FOR FINISHESS. C. Louvers in lead lined wood doors: Section 13 49 00, RADIATION PROTECTION. 1.3 SUBMITTALS A. Submit in ac
3、cordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Shop Drawings: Each type, showing material, finish, size of members, / operating devices, / method of assembly, and installation and anchorage details. C. Manufacturers Literature and Data: Each type of louver and vent. 1.4
4、 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. The Master Painters Institute (MPI): Approved Product List September 2011 C. American Society for Testin
5、g and Materials (ASTM): A167-99(R2009) . Stainless and Heat-Resisting Chromium - Nickel Steel Plate, Sheet, and Strip A1008/A1008M-10 Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved Formability B209/B209M-03(R2007) . Aluminum and Aluminum Alloy, Sheet and Pla
6、te B221-08 Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes B221M-07 . Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire Shapes, and Tubes Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 08 90 00 - 2 D. National Asso
7、ciation of Architectural Metal Manufacturers (NAAMM): AMP 500-06 . Metal Finishes Manual E. National Fire Protection Association (NFPA): 90A-09 . Installation of Air Conditioning and Ventilating Systems G. American Architectural Manufacturers Association (AAMA): 2605-11 High Performance Organic Coat
8、ings on Architectural Extrusions and Panels H. Air Movement and Control Association, Inc. (AMCA): 500-L-07 . Testing Louvers PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify in bo
9、th only that, which applies to the project. 2.1 MATERIALS A. Aluminum, Extruded: ASTM B221/B221M. B. Stainless Steel: ASTM A167, Type 302B. C. Carbon Steel: ASTM A1008/A1008M. D. Aluminum, Plate and Sheet: ASTM B209/B209M. E. Fasteners: Fasteners for securing louvers and wall vents to adjoining cons
10、truction, except as otherwise specified or shown, shall be toggle or expansion bolts, of size and type as required for each specific type of installation and service condition. 1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, an
11、d method of installation. 2. Fasteners for louvers, louver frames, and wire guards shall be of stainless steel or aluminum. F. Inorganic Zinc Primer: MPI No. 19. SPEC WRITER NOTE: Louvers in acid fume areas such as battery rooms, and chlorinate rooms shall be of stainless steel. Verify existence of
12、such spaces with Mechanical and Electrical Engineers. Specify all louvers required or shown, including those shown in connection with mechanical work. 2.2 EXTERIOR WALL LOUVERS A. General: 1. Provide / fixed / and operable / type louvers of size and design shown. Provided by IHSNot for ResaleNo repr
13、oduction or networking permitted without license from IHS-,-,-10-11 08 90 00 - 3 2. Heads, sills and jamb sections shall have formed caulking slots or be designed to retain caulking. Head sections shall have exterior drip lip, and sill sections an integral water stop. 3. Furnish louvers with sill ex
14、tension or separate sill as shown. 4. Frame shall be mechanically fastened or welded construction with welds dressed smooth and flush. SPEC WRITER NOTE: Percent free area, free area velocity, pressure drop and amount of water passage for insertion in following paragraph shall be obtained from Mechan
15、ical Engineer. B. Performance Characteristics: 1. Weather louvers shall have a minimum of _ percent free area and shall pass _ mm/s (fpm) free area velocity at a pressure drop not exceeding _ mm (inch) water gage and carry not more than _ g (ounces) of water per m (square foot) of free area for 15 m
16、inutes when tested per AMCA Standard 500-L. 2. Louvers shall bear AMCA certified rating seals for air performance and water penetration ratings. C. Aluminum Louvers: SPEC WRITER NOTE: Consult Mechanical Engineer to determine if standard or drainable type blades are required. 1. General: Frames, blad
17、es, / sills / and mullions (sliding interlocking type); 2 mm (0.081-inch) thick extruded aluminum. Blades shall be / standard / or / drainable / type and have reinforcing bosses. 2. Louvers, fixed: Make frame sizes 13 mm (1/2-inch) smaller than openings. Single louvers frames shall not exceed 1700 m
18、m (66 inches) wide. When openings exceed 1700 mm (66 inches), provide twin louvers separated by mullion members. 3. Louvers, operable: Louver frame opening sizes, single louver sizes and mullion requirements shall be as specified for fixed louvers. a. Blades: Attach blades to frame with aluminum piv
19、ot pins through nylon bearings. Fasten each blade to stainless steel operation arms that are connected to minimum 3 mm (1/8-inch) thick stainless steel operating / bar / handle / arranged for simultaneous operation of blades. /b. Spring/chain operation: Exposed operator activated by spring attached
20、to operating / bar / handle / and mounted on frame. /Control of louver shall be by pull chain of required length to be operable from floor. Provide pulleys and brackets as required./ Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 08 90 00 - 4
21、/c. Hand crank operation: Hand crank operator activated by case hardened gears concealed in aluminum housing. Operators shall be removable and located at jambs. Provide one right-handed operator for each louver. / /d. Motor operation: Motor operated by approved electric motor. Motors shall be remova
22、ble and located at jambs of louver. Connect motor operator lever arm to operating bar by means of stainless steel connecting rod. / /e. Automatic operation: Louvers shall be complete with / weights, / pull chain, / chain holder and brackets, / cables, / sheaves, / spring, / 70C (160F) fusible link,
23、/ and other related items meeting requirements of NFPA 90A. Provide non-ferrous bearings and spindles of replaceable type. /Control of louver shall be by pull chain of required length to be operable from floor. / Louvers shall close automatically in case of fire. / D. Stainless Steel Louvers: From s
24、tainless steel louvers using 1.6 mm (0.063-inch) thick sheet for frames, blades, sills and mullions. 1. Louver shall have fixed 45 degree / standard / drainable / blades with water baffle. Make overall frame size 13 mm (1/2-inch) less than opening, unless otherwise shown. 2. Single louver sections s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0890002011LOUVERSANDVENTSPDF