VA 07 84 00-2011 FIRESTOPPING.pdf
《VA 07 84 00-2011 FIRESTOPPING.pdf》由会员分享,可在线阅读,更多相关《VA 07 84 00-2011 FIRESTOPPING.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、10-11 07 84 00 - 1 SECTION 07 84 00 FIRESTOPPING SPEC WRITER NOTE: Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 GENERAL 1.1 DESCRIPTION A. Closures of openings in walls, floors, and roof dec
2、ks against penetration of flame, heat, and smoke or gases in fire resistant rated construction. B. Closure of openings in walls against penetration of gases or smoke in smoke partitions. 1.2 RELATED WORK A. Expansion and seismic joint firestopping: Section 07 95 13, EXPANSION JOINT COVER ASSEMBLIES.
3、 B. Spray applied fireproofing: Section 07 81 00, APPLIED FIREPROOFING C. Sealants and application: Section 07 92 00, JOINT SEALANTS. D. Fire and smoke damper assemblies in ductwork: Section 23 31 00, HVAC DUCTS AND CASINGS / Section 23 37 00, AIR OUTLETS AND INLETS. 1.3 SUBMITTALS A. Submit in acco
4、rdance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers literature, data, and installation instructions for types of firestopping and smoke stopping used. C. List of FM, UL, or WH classification number of systems installed. D. Certified laboratory test reports for AS
5、TM E814 tests for systems not listed by FM, UL, or WH proposed for use. 1.4 DELIVERY AND STORAGE A. Deliver materials in their original unopened containers with manufacturers name and product identification. B. Store in a location providing protection from damage and exposure to the elements. 1.5 WA
6、RRANTY Firestopping work subject to the terms of the Article “Warranty of Construction”, FAR clause 52.246-21, except extend the warranty period to five years. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 07 84 00 - 2 1.6 QUALITY ASSURANCE F
7、M, UL, or WH or other approved laboratory tested products will be acceptable. 1.7 APPLICABLE PUBLICATIONS A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. B. American Society for Testing an
8、d Materials (ASTM): E84-10 . Surface Burning Characteristics of Building Materials E814-11 Fire Tests of Through-Penetration Fire Stops C. Factory Mutual Engineering and Research Corporation (FM): Annual Issue Approval Guide Building Materials D. Underwriters Laboratories, Inc. (UL): Annual Issue Bu
9、ilding Materials Directory Annual Issue Fire Resistance Directory 1479-10 Fire Tests of Through-Penetration Firestops E. Warnock Hersey (WH): Annual Issue Certification Listings PART 2 - PRODUCTS 2.1 FIRESTOP SYSTEMS A. Use either factory built (Firestop Devices) or field erected (through-Penetratio
10、n Firestop Systems) to form a specific building system maintaining required integrity of the fire barrier and stop the passage of gases or smoke. B. Through-penetration firestop systems and firestop devices tested in accordance with ASTM E814 or UL 1479 using the “F“ or “T“ rating to maintain the sa
11、me rating and integrity as the fire barrier being sealed. “T“ ratings are not required for penetrations smaller than or equal to 100 mm (4 in) nominal pipe or 0.01 m2 (16 sq. in.) in overall cross sectional area. C. Products requiring heat activation to seal an opening by its intumescence shall exhi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0784002011FIRESTOPPINGPDF