1、11-11 07 81 00 - 1 SECTION 07 81 00 APPLIED FIREPROOFING SPEC WRITER NOTES: 1. Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Verify that different types of fire rating is clearly defined for loca
2、tions either on the drawings or in a schedule. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies mineral fiber and cementitious coverings to provide fire resistance to interior structural steel members shown. 1.2 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
3、DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Manufacturers complete and detailed application instructions and specifications. 2. Manufacturers repair and patching instructions. C. Certificates: 1. Certificate from testing laboratory attesting fireproofing material and application meth
4、od meet the specified fire ratings. a. List thickness and density of material required to meet fire ratings. b. Accompanied by complete test report and test record. 2. Manufacturers certificate indicating sprayed-on fireproofing material supplied under the Contract is same within manufacturing toler
5、ance as fireproofing material tested. D. Miscellaneous: 1. Manufacturers written approval of surfaces to receive sprayed-on fireproofing. 2. Manufacturers written approval of completed installation. 3. Manufacturers written approval of the applicators of fireproofing material. Provided by IHSNot for
6、 ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 07 81 00 - 2 1.3 PRODUCT DELIVERY, STORAGE AND HANDLING A. Deliver to job-site in sealed containers marked and labeled to show manufacturers name and brand and certification of compliance with the specified requirement
7、s. B. Remove damaged containers from the site. C. Store the materials off the ground, under cover, away from damp surfaces. D. Keep dry until ready for use. E. Remove materials that have been exposed to water before installation from the site. 1.4 QUALITY CONTROL A. Test for fire endurance in accord
8、ance with ASTM E119, for fire rating specified, in a nationally recognized laboratory. B. Manufacturers inspection and approval of surfaces to receive fireproofing as specified under paragraph Examination. C. Manufacturers approval of fireproofing applications. D. Manufacturers approval of completed
9、 installation. E. Manufacturers representative shall observe and advise at the commencement of application, and shall visit the site as required thereafter for the purpose of ascertaining proper application. F. Pre-Application Test Area. SPEC WRITER NOTES: 1. Modify requirement for extent of test ar
10、ea to suit project conditions. 2. Apply test to each type of substrate. 1. Apply a test area consisting of a typical overhead fireproofing installation, including not less than 4.5 m (15 feet) of beam and deck. a. Apply to one column. b. Apply for the hourly ratings used. 2. Install in location sele
11、cted by the Resident Engineer, for approval by the representative of the fireproofing material manufacturer and by the Government. 3. Perform Bond test on painted steel in accordance with ASTM E736. 4. Do not proceed in other areas until installation of test area has been completed and approved. 5.
12、Keep approved installation area open for observation as criteria for sprayed-on fireproofing. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 07 81 00 - 3 1.5 APPLICABLE PUBLICATIONS A. Publications listed below form a part of this specificatio
13、n to the extent referenced. Publications are referenced in the text by the basic designation only. B. American Society for Testing and Materials (ASTM): C841-03(R2008) . Installation of Interior Lathing and Furring C847-10 Metal Lath E84-10 . Surface Burning Characteristics of Building Materials E11
14、9-10 Fire Tests of Building Construction and Materials E605-93(R2006) . Thickness and Density of Sprayed Fire-Resistive Materials Applied to Structural Members E736-00(R2006) . Cohesion/Adhesion of Sprayed Fire-Resistive Materials Applied to Structural Members E759-92(R2005) . The Effect of Deflecti
15、on on Sprayed Fire-Resistive Material Applied to Structural Members E760-92(R2005) . Impact on Bonding of Sprayed Fire-Resistive Material Applied to Structural Members E761-92(R2005) . Compressive Strength of Fire-Resistive Material Applied to Structural Members E859-93(R2006) . Air Erosion of Spray
16、ed Fire-Resistive Materials Applied to Structural Members E937-93(R2005) . Corrosion of Steel by Sprayed Fire-Resistive Material Applied to Structural Members E1042-02(R2008) Acoustically, Absorptive Materials Applied by Trowel or Spray. G21-09 . Determining Resistance of Synthetic Polymeric Materia
17、ls to Fungi C. Underwriters Laboratories, Inc. (UL): Fire Resistance Directory.Latest Edition including Supplements D. Warnock Hersey (WH): Certification Listings . Latest Edition E. Factory Mutual System (FM): Approval Guide . Latest Edition including Supplements Provided by IHSNot for ResaleNo rep
18、roduction or networking permitted without license from IHS-,-,-11-11 07 81 00 - 4 PART 2 - PRODUCTS SPEC WRITER NOTES: 1. Make Material requirements agree with applicable requirements specified in the reference Applicable Publications. 2. Update and specify only that which applies to the project. 3.
19、 Allow option for use of both types of materials. See schedule paragraph. 2.1 SPRAYED-ON FIREPROOFING A. ASTM E1042, Class (a), Category A. 1. Type I, factory mixed cementitious materials with approved aggregate. 2. Type II, factory mixed mineral fiber with integral inorganic binders minimum 240 kg/
20、m3 (15 1b/ft3) density per ASTM E605 test unless specified otherwise. Use in areas that are completely encased. B. Materials containing asbestos are not permitted. C. Fireproofing characteristics when applied in the thickness and density required to achieve the fire-rating specified. Characteristic
21、Test Results 1. Deflection ASTM E759 No cracking, spalling, or delamination when backing to which it is applied has a deflection up to 1/120 in 3m (10 ft.) 2. Corrosion-Resistance ASTM E937 No promotion of corrosion of steel. 3. Bond Impact ASTM E760 No cracking, spalling, or delamination. 4. Cohesi
22、on/Adhesion (Bond Strength) ASTM E736 Minimum cohesive/adhesive strength of 9.57 kPa (200 lbf/ft2) for protected areas. 19.15 kPa (400 lbf/ft2) for exposed areas. 5. Air Erosion ASTM E859 Maximum gain weight of the collecting filter 0.27gm/m2 (0.025 gm/ft2). 6. Compressive Strength ASTM E761 Minimum
23、 compressive strength 48 kPa (1000psf). 7. Surface Burning Characteristics with adhesive and sealer to be used ASTM E84 Flame spread 25 or less smoke developed 50 or less 8. Fungi Resistance ASTM G21 Resistance to mold growth when inoculated with aspergillus niger Provided by IHSNot for ResaleNo rep
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0781002011APPLIEDFIREPROOFINGPDF