VA 07 71 00-2011 ROOF SPECIALTIES.pdf
《VA 07 71 00-2011 ROOF SPECIALTIES.pdf》由会员分享,可在线阅读,更多相关《VA 07 71 00-2011 ROOF SPECIALTIES.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、10-11 07 71 00 - 1 SECTION 07 71 00 ROOF SPECIALTIES SPEC WRITER NOTE: 1. Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Include standard manufactured components installed on and in roofing other
2、than mechanical, electrical, and structural items. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies roof hatches; equipment supports; gravity ventilators; and metal grating roof walkway system. 1.2 RELATED WORK A. Color and texture of finish: Section 09 06 00, SCHEDULE FOR FINISHES.Sealant ma
3、terial and installation: Section 07 92 00, JOINT SEALANTS. C. General insulation: Section 07 21 13, THERMAL INSULATION. Rigid insulations for roofing: Section 07 22 00, ROOF AND DECK INSULATION 1.3 QUALITY CONTROL A. All roof accessories shall be the products of manufacturers regularly engaged in pr
4、oducing the kinds of products specified. B. Each accessory type shall be the same and be made by the same manufacturer. C. Each accessory shall be completely assembled to the greatest extent possible before delivery to the site. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAW
5、INGS, PRODUCT DATA, AND SAMPLES. B. Samples: Representative sample panel of color anodized aluminum not less than 100 mm X 100 mm (four by four inches), except extrusions shall be a width not less than section to be used. Sample shall show coating with integral color and texture and shall include ma
6、nufacturers identifying label. C. Shop Drawings: Each item specified showing design, details of construction, installation and fastenings. D. Manufacturers Literature and Data: Each item specified. E. Certificates: Stating that aluminum has been given specified thickness of anodizing. Provided by IH
7、SNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 07 71 00 - 2 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extend referenced. The publications are referenced in the text by the basic designation only. B
8、. Federal Specifications (Fed. Spec.): RR-G-1602D . Grating, Metal, Other Than Bar Type (Floor, Except for Naval Vessels) C. American Society for Testing and Material (ASTM): A653/A653M-10 Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) By the Hot-Dip Process B209/209M
9、-07 . Aluminum and Aluminum Alloy-Sheet and Plate B221/221M-08 . Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes C612-10 Mineral Fiber Block and Board Thermal Insulation D1187-97(R2002) Asphalt-Base Emulsions for Use as Protective Coatings for Metal D. National Association of Architectur
10、al Metal Manufacturers (NAAMM): AMP 500 Series . Metal Finishes Manual E. American Architectural Manufacturers Association (AAMA): 2605-11 High Performance Organic Coatings on Architectural Extrusions and Panels. PART 2 - PRODUCTS SPEC WRITER NOTE: Update materials requirements to agree with applica
11、ble requirements (types, grades, classes) specified in the referenced Applicable Publications. 2.1 MATERIALS A. Aluminum, Extruded: ASTM B221/B221M. B. Aluminum Sheet: ASTM B209/B209M. C. Galvanized Sheet Steel: ASTM A526/A526M; G-90 coating. D. Metal Grating for Roof Walkway: Fed. Spec. RR-G-1602.
12、2.2 ROOF HATCH (SCUTTLE) A. Fabricate from aluminum with mill finish. B. Curb and Cover: 1. Exterior facing: Minimum 2.3 mm (0.09 inch) thick sheet aluminum. 2. Interior facing: Minimum 1 mm (0.04 inch) thick sheet aluminum. 3. Minimum of 25 mm (one inch) thick mineral fiber insulation between facin
13、gs of cover and over exterior face of curb. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 07 71 00 - 3 4. Form exterior curb facing with an integral three inch wide roof flange and cap flashing minimum 2.3 mm (0.09 inch) thick sheet aluminum.
14、 SPEC WRITER NOTE: Do not use less than 300 mm (12 inch high) curb above roof surface. Where access is to service roof equipment comply with OSHA for stair size, roof opening 750 mm X 2400 mm (2-6“ by 80“). Show opening size on the drawings. 5. Make curb / 300 mm (12 inches) / /_/. 6. Form cover to
15、lap curb and cap flashing. 7. Size opening as shown. C. Hardware: 1. Provide spring snap latch with inside and outside operating handles and padlock hasp on inside. Provide two snap latches when hinge side is over 2100 mm (7 feet) long. 2. Provide pintle hinges. 3. Provide automatic hold open and op
16、erating arm with enclosed torsion or compression spring lifting mechanism. 4. Covers shall automatically lock in the open position at not less than 70 degrees. 5. Provide weatherstripping at cover closure. 6. Galvanize all hardware items. D. Assembly: 1. Completely shop assemble roof scuttle. 2. Ful
17、ly weld all joints exposed to the weather and built into the roofing. 3. Finish weld smooth where exposed. 4. Operation with minimum force to open and close. SPEC WRITER NOTE: Use following article for roof mounted equipment items other than mechanical equipment items. Prefabricated roof curbs for f
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0771002011ROOFSPECIALTIESPDF