UL 917 CRD-2015 UL Standard for Safety Clock-Operated Switches - Section Paragraph Reference 43 2 Table 28 1 (revised) 42 7 Section 29A (new) Subject Addition of Requirements for .pdf
《UL 917 CRD-2015 UL Standard for Safety Clock-Operated Switches - Section Paragraph Reference 43 2 Table 28 1 (revised) 42 7 Section 29A (new) Subject Addition of Requirements for .pdf》由会员分享,可在线阅读,更多相关《UL 917 CRD-2015 UL Standard for Safety Clock-Operated Switches - Section Paragraph Reference 43 2 Table 28 1 (revised) 42 7 Section 29A (new) Subject Addition of Requirements for .pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): WGZRStandard Number: UL 917Standard Title: Standard for Clock-Operated SwitchesEdition Date: November 10, 2006Edition Number: 5Section / Paragraph Reference:
3、 43.2, Table 28.1 (revised), 42.7, Section 29A (new)Subject: Addition of Requirements for the Test Method and Simulated ElectricalLoads for Electronic Ballast, CFL and LED Driver RatingsDECISION:Table 28.1Values of voltage and current for endurance testsDevice rated in Test potential Test current Po
4、wer factor Numberof cyclesCyclesperminuteAmperes, AC, DC Rated Voltage See 24.4 AC rated 0.75 0.80d6000 6aDC rated b 6000 6aHorsepower, AC Rated Voltage See 24.4 AC full-load currentindicated in Table 27.20.75 0.80 6000 6aHorsepower, DC 0.5 times RatedVoltage See 24.4DC full-load currentindicated in
5、 Table 27.3b 6000 6aFull-load andlocked-rotoramperesRated Voltage See 24.4 AC rated full-load current 0.75 0.80 6000 6aDC rated full-load current b 6000 6aAmperes(Tungsten)Rated Voltage See 24.4 AC rated current e 6000 1cDC rated current e 6000 1cAmperes (Inductive) Rated Voltage See 24.4 Two times
6、rated current 0.75 0.80 6000 6aVolt-Amperes PilotDutyRated Voltage See 24.4 See 28.4 See 28.4 6000 See 28.4Electronic ballast,self ballasted LEDand CompactFluorescent Lamps,LED drivers andsimilar loads withcapacitive loadcharacteristicsRated Voltage See 24.4 Rated current per Table29A.1N/A 6000 6aTh
7、e test cycle is to be 1 second on and 9 seconds off, if the nature of device permits the test to be so made.bNoninductive resistive load.cThe test cycle is to be as indicated in 27.2.dIf the device is marked for a resistive load only in accordance with 43.2 the test may be conducted using anoninduct
8、ive load.eThe load shall consist of tungsten filament lamps or a load having equivalent characteristics. See 29.1 29.5.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL29A Electronic ballast, CFLs and LED driver rated controls29A.1 (New) A devi
9、ce having electronic ballast, self-ballasted LED and CFL Lamps, LED fixtures, or LEDdriver load rating shall be tested for Endurance using the load characteristics specified in Tables 28.1 and29A.1. As a result of the testing, there shall be no electrical or mechanical breakdown of the device, norun
10、due burning, pitting, or welding of the contacts.Table 29A.1Peak current requirements for endurance testSteady statecurrent (A)Peak current(A), 120 V ACPulse width120 V AC (mS).See Note 2I2t(A2sec) 120V AC. See Note1Peak current(A), 277 V ACPulse width277 V AC (mS).See Note 2I2t(A2sec) 277V AC. See
11、Note10.5 75 0.34 11 77 0.07 111 107 0.48 24 131 0.71 272 144 0.70 41 205 0.85 763 166 0.89 51 258 0.98 1115 192 1.20 74 320 1.20 2058 221 1.25 98 370 1.25 27410 230 1.50 106 430 1.50 37012 235 1.80 110 440 1.80 38715 239 2.00 114 458 2.00 42016 242 2.10 117 480 2.10 461NOTES1 - The values used to ca
12、lculate I2t are the peak current shown and pulse duration of 2 mS (t).2 - Pulse widths shown will provide adequate performance with electronic ballasts having pulse widths up to 2 ms, inaccordance with the Standard for Lamp Ballasts - High Frequency Fluorescent Lamp Ballasts, ANSI_ANSLG C82.11, or t
13、heStandard for Lamp Ballasts Low-Frequency Square Wave Electronic Ballasts - for Metal Halide Lamps, ANSI_ANSLG C82.14.29A.2 The synthetic load described in 29A.3 and 29A.4 shall be used as the load for testing. Theendurance test shall be completed with that load.29A.3 The series coil values must be
14、 adjusted based on the input line characteristics to achieve the peakcurrents listed in Table 29A.1. The series coil shall be sized such that it does not saturate during testingand shall be able to handle the resulting power dissipation with less than 10C temperature rise. Peakcurrent and pulse widt
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL917CRD2015ULSTANDARDFORSAFETYCLOCKOPERATEDSWITCHESSECTIONPARAGRAPHREFERENCE432TABLE281REVISED427SECTION29ANEWSUBJECTADDITIONOFREQUIREMENTSFORPDF

链接地址:http://www.mydoc123.com/p-1069049.html